HomeMy WebLinkAboutNC0021971_Compliance Evaluation Inspection_20200305ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
S. DANIEL SMITH
Director
Keith Friedmann, Terminal Manager
Marathon Petroleum Company, LP
7401 Old Mount Holly Road
Charlotte, North Carolina 28214
Dear Mr. Friedmann:
NORTH CAROLINA
Environmental Quality
March 5, 2020
Subject: Compliance Evaluation Inspection
Blanchard Terminal Company
Charlotte East Terminal
NPDES Permit No. NCO021971
Mecklenburg County
Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject
facility on February 26, 2020, by Mr. Wes Bell of this Office. Please inform the staff that oversee the NPDES
operations at this facility by forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions concerning this report, please do
not hesitate to contact Mr. Bell at (704) 235-2192 or at wes.belIgncdenr.gov.
Sincerely,
Docu Signed by:
p"'� H pl' u`'z for
F161 FB69A2D84A3...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, DEQ
Enclosure:
Inspection Report
�� Office
Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NOR7H ORROLINA i
kmrlaam m EnNromi Wuwi\ /`� 704.663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NCO021971 111 12 I 20/02/26 I17 18 I S J 19 L G] 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 70 71 [.. I 72 73 L_LJ74 751 I I I I I I I80
u u
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
12:11 PM 20/02/26
15/07/01
Charlotte Terminal
7401 Old Mount Holly Rd
Exit Time/Date
Permit Expiration Date
Charlotte NC 28214
03:03PM 20/02/26
20/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Keith Friedmann/Manager Term i nal/41 9-619-5089 /
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Angela S Brown,539 S Main St Findlay OH 45840Nice President/419-421-2629/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program 0 Facility Site Review Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
cuSigned by:
Wes Bell DWR/MRO WQ/704-663-1699 Ext.2192/ 3/5/2020
Be&
E�:96D90=437...
Docusigned by: Date
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numb
[A*-.10 H P44-ft
Andrew Pitner DWR/MRO WQ/704-663-1699 Ext.2180/ 3. 5. 2020
F1611`669A21D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NC0021971 I11 121 20/02/26 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On -Site Representatives:
The following Company personnel were in attendance during the inspection: Keith Friedmann, Brad
Lambert, Darryl Thompson and Terry Pridgen.
Page#
Permit: NCO021971 Owner - Facility: Charlotte Terminal
Inspection Date: 02/26/2020 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The Division had received the facilitv's Dermit renewal aDDlication Dackaae on 12/16/19.
The last compliance evaluation inspection at the facility was performed by
Charlotte -Mecklenburg Stormwater Services/Water Quality Program staff on 9/14/17.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Diesel fuel, gasoline, ethanol, butane and fuel additives are stored on -site.
The facility is inspected on a daily basis. Site grounds including secondary containment
structures (berms) were well maintained. The runoff from the loading rack area is collected
in a storage tank and disposed of by a contracted company (Shamrock Environmental).
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
on each shift?
Is the ORC visitation log available and current?
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Page# 3
Permit: NCO021971 Owner - Facility: Charlotte Terminal
Inspection Date: 02/26/2020 Inspection Type: Compliance Evaluation
Record Keeping
Yes No NA NE
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
0
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
0
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment: The records reviewed durina the inspection were oraanized and well maintained. Discharae
Monitoring Reports (eDMRs) were reviewed for the period January 2019 through December
2019. No effluent limit violations were reported and all monitoring frequencies were correct.
The facility staff must ensure that only the turbidity results from the effluent discharge are
reported on future eDMRs. Please note that as of July 2019, field turbidity analyses were
approved: therefore, if the contracted laboratory is field certified to perform effluent turbidity
analyses and both effluent analyses (field and in the laboratory) were performed on the
same day, then the average of the two results would be reported on the eDMR.
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
0
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: Pace Analytical Services has been contracted to collect and analyze effluent samples.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: The subject permit requires effluent grab samples.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Yes No NA NE
❑ ❑ ■ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
Page# 4
Permit: NCO021971 Owner - Facility: Charlotte Terminal
Inspection Date: 02/26/2020 Inspection Type: Compliance Evaluation
Flow Measurement - Effluent Yes No NA NE
Is the flow meter operational? 0 ❑ ❑ ❑
(If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑
Comment: Outfalls 009 and 010 are equipped with an in -line flow meter. The flow meters are calibrated
annually by Sparling Instruments.
Spare in -line flow meters (calibrated) are also maintained on -site.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: No discharges were observed from both Outfalls during the inspection.
The manual discharge valves for both outfalls are kept locked in closed positions.
Page# 5