SUBJECT: NOTICE OF VIOLATION & INTENT TO ASSESS CIVIL PENALTY
Tracking Number: NOV-2020-PC-0115
Permit No. NCO023337
Scotland Neck WWTP
Halifax County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Scotland Neck WWTP on
February 25, 2020. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in Permit No. NC0023337. A summary of the findings and comments noted
during the inspection are provided in the enclosed copy of the inspection report.
The inspection was conducted by Division of Water Resources staff from the Raleigh Regional Office. The following
violation(s) were noted during the inspection:
Inspection Area Description of Violation_ _
Disinfection Liquid Half of the contact chamber was not in service at the time of inspection. 1.75 feet
of stud a was noted in the contact chamber (with about 5 feet of water depth)
Secondary Clarifier No. 2 clarifier was not operable (with no RAS pumps)
Filtration (High Rate Tertiary) One of two filters was not operable. The filter in service appeared to be blinded
and nartialivbypassed.
Oxidation Ditches One of two rotor aerators was not operable. Mixed liquor was black in color, and
se tic. The one operable aerator was turned on for 15 minutes every three hours.
Pumps-RAS-WAS Two original pumps in the wasted sludge wet well were not in place, a portable
pump was used to transfer sludge from the wet well to the digester. A pump was
laced in the scum well of No. 1 Clarifier and served as RAS pump
Grit Removal Unit was not operable and bypassed
In addition, the issues below must also be addressed: The permittee must designate one Operator in Responsible
Charge (ORC) and one or more Back-up Operator(s) in Responsible Charge (Back-up ORCs) by March 2, 2020.
Compliance Issue(s): Based on the above observations, the permittee was found to have violated
Section C. 2. of the NPDES Permit for failure to properly operate and maintain all facilities and
systems of treatment and control (and related appurtenances) which are installed or used by the
Permittee to achieve compliance with the conditions of this permit.
A Notice of Violation/Intent to Issue Civil Penalty is being issued for the noted violation of North Carolina General
Statute (G.S.) 143-215.1 and the facility's Permit. Pursuant to G.S. 143-215.6A, a civil penalty of not more
than twenty-five thousand dollars ($25,000.00) may be assessed against any person who violates or fails to act
in accordance with the terms, conditions, or requirements of any permit issued pursuant to G.S. 143-215.1.
If you wish to provide additional information regarding the noted violation, request technical assistance, or discuss
overall compliance please respond in writing within ten 10 business days after receipt of this Notice. A review of
your response will be considered along with any additional information provided. You will then be notified of any
civil penalties that may be assessed regarding the violations. If no response is received in this Office
within the 10-day period, a civil penalty assessment may be prepared.
Remedial actions should have already been taken to correct this problem and prevent further occurrences in the
future. The Division of Water Resources may pursue enforcement action for this and any additional violations of
State law. If the violations are of a continuing nature, not related to operation and/or maintenance problems, and
you anticipate remedial construction activities, then you may wish to consider applying for a Special Order by
Consent.
Reminder: Pursuant to Permit Condition 6 in Section E, the Permittee is required to verbally notify the Regional
Office as soon as possible, not to exceed 24 hours, from first knowledge of any non-compliance at
the facility including limit violations, bypasses of, or failure of a treatment unit. A written report may
be required within 5 days if directed by Division staff. Prior notice should be given for anticipated or
potential problems due to planned maintenance activities, taking units off-line, etc.
If you should have any questions, please do not hesitate to contact Cheng Zhang with the Water Quality Regional
Operations Section in the Raleigh Regional Office at 919 791 4200.
Sincerely,
Scott Vinson, Regional Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: WQS Raleigh Regional Office - Enforcement File
NPDES Compliance/Enforcement Unit - Enforcement File
Laserfiche
United States Environmental Protection Agency
Form Approved,
EPA W30ington, D C 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A. National Data System Coding (i.e , PCS)
Transaction Code NPDES yrlmolday Inspection Type
Inspector Fac Type
1 u 2 1S 1 3 NCO023337 11 12 20102125 17 18 I D I
1=J
19 I s J I 201 LJ
L
21
6
Inspection Work Days Facility Self -Monitoring Evaluation Rating at CA
Reserved
67 70 !J 71 IJ 72 I 73 �74 751 I I I i I I I80
�j ! I
Section 8 Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW. also include Entry Time/Dale
Permit Effective Date
POTW name and NPDES Permit Number)
1010AM 20102/25 15/08101
Scotland Neck WWfP
NC Hwy 258 S Exit TimelDate
Permit Expiration Date
ScoOand Neck NC 27874 12:OOPM 20102/25 19110131
Name(s) of Onsite Represenlative(s)lTtles(suPhone and Fax Number(s) Other Facility Data
A!
P6 ,r-ks r U
Name, Address of Responsibte Official/Title/Phone and Fax Number
Chades Baisey,PO Box 537 Scotland Neck NC 27874f1252.826-31521 Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Operations 8 Maintenance ■ Facility Site Review
Section D• Summary of Finding+Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature{s) of Ina pector{s) AgencylOfficelPhone and Fax Numbers
Date
w
Cheng Zhang [~ t J
�` DWR,'RRO W01919-791-42001
Z/ Z8r2.0249
Mitchell S Hayes DWR'RRO W01919-791-4200.
01 �
' 2-9 17e 2—G
/
Signature of Management 0 A Reviewe• Agency101ficelPhone and Fax Numbers
Date
EPA Form 3560-3;Rev 9-94, Previous editions are obsolete.
#gage#
Permit: NCO023337 Owner - Facility: Scotland Neck wWTP
Inspection Date: 02t25f2020 Inspection Type: Technical Assistance
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
❑
b.Mechanical
.
Are the bars adequately screening debris?
❑
❑
❑
Is the screen free of excessive debris?
■
❑
❑
❑
Is disposal of screening in compliance?
❑
❑
❑
Is the unit in good condition?
❑
❑
❑
Comment:
Grit Removal
Yes No NA NE
Type of grit removal
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?
❑
❑
❑
Is the grit free of excessive odor?
❑
❑
❑
# Is disposal of grit in compliance?
❑
■
❑
❑
Comment: The unit was not operable and bypassed
Pump Station - Influent
Yes No NA NE
Is the pump wet well free of bypass lines or structures?
❑
❑
❑
Is the wet well free of excessive grease?
❑
❑
❑
Are all pumps present?
❑
❑
❑
Are all pumps operable?
❑
❑
❑
Are float controls operable?
M❑
❑
❑
Is SCADA telemetry available and operational?
❑
❑
❑
Is audible and visual alarm available and operational?
❑
❑
❑
■
Comment: One of three pumps was not operable
Page# 3
Permit: NCO023337 Owner • Facility.. Scotland Neck wwrP
Inspection Date: 02/2512020 Inspection Typo: Technical Assistance
Oxidation Ditches
Yes No NA NE
Are the aerators operational?
0
El
❑
Are the aerators free of excessive solids build up?
❑
11
El
* Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
❑
El
El
Is the DO level acceptable?
rl
Are settleometer results acceptable (> 30 minutes)?
Is the DO level acceptable?(1.0 to 3.0 mgll)
Are settelometer results acceptable?(400 to 800 ml/l in 30 minutes)
❑
❑
Comment: One of two rotor aerators was not operable. Mixed liquor was black in color, appeared
septic. The one operable aerator was turned on for 15 minutes every three hours.
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
❑
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately % of the sidewall depth)
11
❑
Comment: Sludge blanket was 3.5 feet 10-foot side wall depth)
Pumps-RAS-WAS
Yes No NA NE
Are pumps in place?
❑ M
11
❑
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment: Two original Pumps in the wasted sludge wet well were not in place, a
Dortable Pump,was
used to transfer sludge from the wet well to the digester, A 13ump was
glaced in the scum
well and served as RA5 Rump.
Filtration (High Rate Tertiary)
Yes No NA NE
Page# 4
Permit: NCO023337 Owner -Facility: 5c3tiand Neck wWTP
Inspection Date: 02J25M20 Inspection Type.. Technical Assistance
Filtration (High Rate Tertiary)
Yes No NA NE
Type of operation
Down flow
Is the filter media present?
❑
❑
El
Is the filter surface free of clogging;
0
❑
❑
Is the filter free of growth?
❑ ❑
❑
0
Is the air scour operational?
El M
El
El
Is the scouring acceptable?
Is the clear well free of excessive solids and filter media?
Comment, One of two filters was not operable. The filter in service a eared to be blinded and Partially
bypassed.
Disinfection -Liquid
Yes No NA NE
Is there adequate reserve supply of disinfectant?
1:1
❑
(Sodium Hypochlorite) Is pump feed system operaticnal?
D
1:1
Is bulk storage tank containment area adequate? (free cf leakslopen drains)
❑
Is the level of chlorine residual acceptable?
0
L1
El
❑
Is the contact chamber free of growth, or sludge bu!ldup?
❑
M
El
❑
Is there chlorine residual prior to de-chlorinatoon?
0
❑
❑
Comment: Half of the contact chamber was in service at the time of inspection. 1.75 feet of sludge was
noted in the contact chamber with about 5 feet of water depth)
De -chlorination Yes No NA NE
Type of system ? Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)? M ❑
Is storage appropriate for cylinders? MCl
El F1
# Is de -chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type? M
Are tablet de -chlorinators operational? El El M D
Number of tubes in use?
Comment: