January 15,2020
Hamilton Stolpen, Project Manager
AMH NC Development, LP _
18805 W. Catawba Avenue
Suite 102
Cornelius, NC 28031 •
Subject: Application Returned
Application No.WQ0040438
Riley Meadows
Dear Mr. Stolpen:
This letter is in reference to your permit application received November 15, 2018 for the construction and
operation of the subject sewer extension. In emails sent February 13, 2019 and December 19, 2019, by
Christyn Fertenbaugh, P.E., your engineer was asked to provide additional information (copy attached) in
accordance with 15A NCAC 02T.0107(e). As of today, this information has not been received, therefore the
Division must return your application as incomplete in accordance with 15A NCAC 02T.0107(e)(2).
Please be advised that construction and/or operation of wastewater collection,treatment,and/or disposal
facilities without a valid permit is a violation of North Carolina General Statute§143-215.1 and may subject
the owner/operator to appropriate enforcement actions in accordance with North Carolina General Statute
§143-215.6A-6C. Civil penalties of up to$25,000 per day per violation may be assessed for failure to secure a
permit required by North Carolina General Statute§143-215.1.
When you have obtained the requested information that is needed to make your application package
complete,you may submit a new application package with the appropriate permit processing fee. If you have
any questions or would like to discuss this matter further, please contact Christyn Fertenbaugh, P.E. at(919)
707-3625 or via e-mail at Christvn.Fertenbaugh@ncdenr.gov.
Sincere! ,
Christyn L. Fertenbaugh, P.E.
Pretreatment, Emergency Response, Collection System Unit
Division of Water Resources, NCDEQ
enclosure: Additional Information Request Email
cc: Brian Smith, P.E., Urban Design Partners(brian(a)urbandesignpartners.com)
Mooresville Regional Office,Water Quality Section Regional Operations
Water Resources Central Files:WQ0040438
PERCS(electronic copy) ,
1 .•D E ^- North Carolina Department of Environmental Quality I Division of Water Resources
�) 512 North Salisbury Street 11617 Mail Service Center I Raleigh,North Carolina 27699-1617
NORM CAROUNA
Oepartmeatal6n'aaaaaa"vlQuality 919.707.9000
Fertenbaugh, Christyn L
From: Fertenbaugh, Christyn L
Sent: Thursday, December 19, 2019 7:14 PM
To: Brian Smith; hstolpen@ah4r.com
Cc: Basinger, Corey
Subject: RE:Additional Information Request:WQ0040438 Riley Meadows
Hello,
As I am doing my end-of-year file cleanup, I have noted that my records indicate that I have not yet received a response
for the additional information request as sent on February 13, 2019 (copied below),for the subject permit application
for the Riley Meadows sewer extension located in Mecklenburg County. Please provide a complete response to the
comments below by Friday,January 10,2020. Failure to respond will result in the application being returned as
incomplete and the documents recycled, per 15A NCAC 02T.0107(e)(2). If you have decided to not pursue this permit
application, please let me know and I will withdraw the application.
Please be advised that operating a non-discharge system (including sewer extensions)without a valid Wastewater
Collection Permit may subject the responsible party to a civil penalty of up to$10,000 per day.
If you have any questions, please let me know.Thanks!
Christyn L. Fertenbaugh, P.E.
Environmental Engineer
PERCS Unit
Division of Water Resources
Department of Environmental Quality
**Subscribe to Collection System &Sewer Permitting Updates**
Meese note that my phone number has changed to 9i9 707- 25,
919-707-3625—Office
919-807-6489—Fax
ch ristyn.ferten ba ugh Cai ncden r.gov
Mailing: 1617 Mail Service Center
Raleigh,NC 27699-1617
Physical: 512 N.Salisbury Street, Rm.925S
Raleigh, NC 27604-1170
Imo+
"irttlEQ
`oii 1 ii"A.ro,1is2�+1
thri nrlrnont f:r1►rarun¢nial Oii.,bity
Email correspondence to and from this address is subject to the
North Carolina Public Records Law and may be disclosed to third parties.
1
From: Fertenbaugh, Christyn L
Sent:Wednesday, February 13, 2019 4:28 PM
To: Brian Smith<brian@urbandesignpartners.com>; hstolpen@ah4r.com
Subject:Additional Information Request: WQ0040438 Riley Meadows
Hello,
A review of the application and supporting documents for the subject application has been completed by this office. In
accordance with 15A NCAC 02T.0107, please provide the additional or revised information for the following comments:
General Review:
1. Please provide a set of revised,final plans,specifications, and supplementary information on digital media (CD
or other digital format such as a flash drive)for our records.
Application/FTSE:
1. Please provide a complete ASEA application form that lists only the length of line/flow to be included in this
permit—including the following items that are missing:
a. Section V is blank.
b. Please provide the applicable flow reduction approval letter, per Section VI(7)of the application.
c. Sections VII(2-8) are blank.
d. Section X(1) appears to include line that is indicated to be permitted separately by Charlotte Water's
delegated program. Please clarify and/or revise.
2. Please clarify Mr. Hamilton Stolpen's relationship to AMH NC Development, LP,as his name is not listed on the
NC Secretary of State's business search as a general partner, per 15A NCACO2T.0106(b). If Mr.Stolpen is not a
general partner, please provide a written delegation of authority to sign the permit application, per 15A NCAC
02T.0106(c).
3. Please provide a completed copy of the Developer's Operational agreement, indicating the name of the HOA
that shall be formed to take ownership of the permit at the time of certification on Page 1, Item 5; per 15A NCAC
02T.0115.
4. As the provided FTSE document was nearly a year old at the time of submission of this application,and is now
over a year old—please provide an updated FTSE with the most recent information for Charlotte Water's
downstream facilities. Please be sure to utilize the updated form,dated 10-18, as found on our website HERE.
a. Please also clarify the relationship of Santee Land Group to AMH NC Development, LP, as the entity
requesting allocation on the FTSE should be the same as the permit applicant.
Calculations:
1. Please provide calculations for the following: buoyancy resistance,wet well storage above the pump-on
position, and downstream capacity analysis, per 15A NCAC 02T.0305(b)(2). Please note that provision of the
FTSE or a letter from Charlotte Water does not negate the requirement for downstream capacity analysis
calculations per 15A NCAC 02T.0304(g). All design calculations must be signed/sealed by a Professional Engineer.
Plans/Specifications:
1. Please provide specifications for the low-pressure and gravity sewer portions of this project, including the
materials, methods of construction, and quality assurance testing, per 15A NCAC 02T.0305(b)(3).The provided
specifications only appeared to include limited information regarding the grinder pumps.
2. Please provide profile views of all sewers to be installed as part of this permit application, depicting their
proximity to other utilities and natural features, per 15A NCAC 02T.0305(b)(1).
2
3. Please provide the appropriate detail depictions on the plans for the sanitary sewer, including but not limited to:
manholes,tapping fixtures,cleanouts,ARVs,trenching, utility crossings, and other appurtenances/installation
requirements.
4. Please provide the appropriate detail depiction(s)for the proposed simplex grinder pump stations on the
appropriate plan sheet(s), including but not limited to: pump selection per lot, elevations/dimensions, storage
capacity above the pump-on elevation, buoyancy resistance, and the presence of a screened vent,audible and
visual high-water alarms, and an emergency contact placard/sticker, per 15A NCAC 02T.03O5.
A response to the above comments is considered required in order to proceed with the review of the application and
issuance of the permit. If a complete response is not received within 30 days,the application and supporting documents
will be returned to you in accordance with 15A NCACO2T.O107(e)(2).
If you have any questions, please let me know.Thanks!
Christyn L. Fertenbaugh, P.E.
Environmental Engineer
PERCS Unit
Division of Water Resources
Department of Environmental Quality
**Subscribe to Collection System &Sewer Permitting Updates**
Please note that my phone number has changed to 919 7O7- 5.
919-707-3625—Office
919-807-6489—Fax
christyn.fertenbaugh@ncdenr.gov
Mailing: 1617 Mail Service Center
Raleigh, NC 27699-1617
Physical: 512 N.Salisbury Street, Rm.925S
Raleigh, NC 27604-1170
--"` 'Not ling Compares--,....
Email correspondence to and from this address is subject to the
North Carolina Public Records Law and may be disclosed to third parties
3
Fertenbaugh, Christyn L
From: Fertenbaugh, Christyn L
Sent: Wednesday, February 13, 2019 4:28 PM
To: 'Brian Smith'; 'hstolpen@ah4r.com'
Subject: Additional Information Request:WQ0040438 Riley Meadows
Hello, .
A review of the application and supporting documents for the subject application has been completed by this office. In
accordance with 15A NCAC 02T.0107, please provide the additional or revised information for the following comments:
General Review:
1. Please provide a set of revised,final plans, specifications,and supplementary information on digital media (CD
or other digital format such as a flash drive)for our records.
Application/FTSE:
1. Please provide a complete ASEA application form that lists only the length of line/flow to be included in this
permit—including the following items that are missing:
„a. Section V is blank.
b. Please provide the applicable flow reduction approval letter, per Section VI(7)of the application.
c. Sections VII(2-8) are blank.
d. Section X(1) appears to include line that is indicated to be permitted separately by Charlotte Water's
delegated program. Please clarify and/or revise.
2. Please clarify Mr. Hamilton Stolpen's relationship to AMH NC Development, LP, as his name is not listed on the
NC Secretary of State's business search as a general partner, per 15A NCAC 02T.0106(b). If Mr.Stolpen is not a
general partner, please provide a written delegation of authority to sign the permit application, per 15A NCAC
02T.0106(c).
3. Please provide a completed copy of the Developer's Operational agreement, indicating the name of the HOA
that shall be formed to take ownership of the permit at the time of certification on Page 1, Item 5; per 15A NCAC
02T.0115.
4. As the provided FTSE document was nearly a year old at the time of submission of this application, and is now
over a year old—please provide an updated FTSE with the most recent information for Charlotte Water's
downstream facilities. Please be sure to utilize the updated form, dated 10-18, as found on our website HERE.
a. Please also clarify the relationship of Santee Land Group to AMH NC Development, LP, as the entity
requesting allocation on the FTSE should be the same as the permit applicant.
Calculations:
1. Please provide calculations for the following: buoyancy resistance,wet well storage above the pump-on
position, and downstream capacity analysis, per 15A NCAC 02T.0305(b)(2). Please note that provision of the
FTSE or a letter from Charlotte Water does not negate the requirement for downstream capacity analysis
calculations per 15A NCACO2T.0304(g). All design calculations must be signed/sealed by a Professional Engineer.
Plans/Specifications:
1
1. Please provide specifications for the low-pressure and gravity sewer portions of this project, including the
materials, methods of construction,and quality assurance testing, per 15A NCACO2T.0305(b)(3).The provided
specifications only appeared to include limited information regarding the grinder pumps.
2. Please provide profile views of all sewers to be installed as part of this permit application, depicting their
' proximity to other utilities and natural features, per 15A NCAC 02T.0305(b)(1).
3. Please provide the appropriate detail depictions on the plans for the sanitary sewer, including but not limited to:
manholes,tapping fixtures, cleanouts,ARVs,trenching, utility crossings, and other appurtenances/installation
requirements.
4. Please provide the appropriate detail depiction(s)for the proposed simplex grinder pump stations on the
appropriate plan sheet(s), including but not limited to: pump selection per lot, elevations/dimensions, storage
capacity above the pump-on elevation, buoyancy resistance, and the presence of a screened vent, audible and
visual high-water alarms, and an emergency contact placard/sticker, per 15A NCAC 02T.0305.
A response to the above comments is considered required in order to proceed with the review of the application and
issuance of the permit. If a complete response is not received within 30 days,the application and supporting documents
will be returned to you in accordance with 15A NCAC 02T.0107(e)(2).
If you have any questions, please let me know.Thanks!
Christyn L. Fertenbaugh, P.E.
Environmental Engineer
PERCS Unit
Division of Water Resources
Department of Environmental Quality
**Subscribe to Collection System &Sewer Permitting Updates**
Fileaxe nets that my phone nurnber ibas changed to -701-36-25,
919-707-3625—Office
919-807-6489—Fax
christvn.fertenbaugh@ncdenr.gov
Mailing: 1617 Mail Service Center
Raleigh, NC 27699-1617
Physical: 512 N.Salisbury Street, Rm.925S
Raleigh, NC 27604-1170
0Nothing Compares...,...
Email correspondence to and from this address is subject to the
North Carolina Public Records Law and may be disclosed to third parties.
2