HomeMy WebLinkAboutNC0039608_Compliance Evaluation Inspection_20191115ROY COOPER Governor MICHAEL S. REGAN Secretary LINDA CULPEPPER Director Mr. Jadd Brewer P.O. Box 1167 Banner Elk, NC. 28604 �ry 44, NORTH CAROLINA EnNlmnmrrtlnl Quality November 15, 2019 SUBJECT: Compliance Evaluation Inspection Summit Woods WWTP NPDES Permit No. NCO039608 Watauga County Dear Mr. Brewer, On November 14, 2019, Kelli Park, of this office, met with Dylan Markland and Josh Cagle, Operator in Responsible Charge (ORC), to perform a Compliance Evaluation Inspection at the Summit Woods wastewater treatment plant. This type of inspection consists of two basic parts: an in -office file review and an on -site inspection of the treatment facility. The attached EPA inspection form details the areas that were evaluated during this inspection. The inspection of the facility was satisfactory. If you have any questions regarding the inspection or this report, please contact Kelli Park or me at (336) 776-9800 or by email at kelli.park(o-)ncdenr.gov or lon.snider(a)ncdenr.gov. Sincerely, Docu Siiggned by: ��. 1_.49E225C94EA... Lon Snider Regional Supervisor Water Quality Regional Operations Division of Water Resources Attachments: EPA Water Compliance Inspection Report cc: WSRO United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I 2 IF I 3 I NCO039608 111 12 I 19/11/14 I17 18 I S J 19 L G] 201 I 211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved ------------------- 671 70 I I 71 I I 72 I r I 73 I I 174 751 I I I I I I I80 u I� I I i Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES oermit Number) 11:15AM 19/11/14 16/08/01 Summit Woods Apartments WWTP 237 Bloomfield Dr Exit Time/Date Permit Expiration Date Blowing Rock NC 28605 11:30AM 19/11/14 21/03/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Joshua Kenneth Cagle/ORC// Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Heather Sofield,355 Industrial Park Dr Boone NC 28607//828-268-0994/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenance 0 Records/Reports Self -Monitoring Program 0 Facility Site Review Effluent/Receiving Waters Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Kelli A Park DWR/WSRO WQ/336-776-9689/ Signature of Management Q A Revie Docusiyned by: Agency/Office/Phone and Fax Numbers Date L" 'r Sti,dcc 11/15/2019 145B49E225C94EA... EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type (Cont.) NCO039608 I11 121 19/11/14 117 18 ICI Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) On November 14, 2019, Kelli Park, of this office, met with Dylan Markland and Josh Cagle, Operator in Responsible Charge (ORC), to perform a Compliance Evaluation Inspection at the Summit Woods wastewater treatment plant. This type of inspection consists of two basic parts: an in -office file review and an on -site inspection of the treatment facility. The attached EPA inspection form details the areas that were evaluated during this inspection. The inspection of the facility was satisfactory. If you have any questions regarding the inspection or this report, please contact Kelli Park or me at (336) 776-9800 or by email at kelli.park@ncdenr.gov or Ion.snider@ncdenr.gov. Note: There is no bar screen at this plant. Instead the inflow goes through a paper chamber before entering the plant. Page# Permit: NCO039608 Owner - Facility: Summit Woods Apartments WWTP Inspection Date: 11/14/2019 Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ ❑ application? Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ 0 ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ ❑ on each shift? Is the ORC visitation log available and current? ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? ❑ ❑ ❑ Page# 3 Permit: NCO039608 Owner - Facility: Summit Woods Apartments WWTP Inspection Date: 11/14/2019 Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑ Comment: ORC and bORC are grade 3 Aeration Basins Yes No NA NE Mode of operation Ext. Air Type of aeration system Diffused Is the basin free of dead spots? 0 ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ 0 ❑ Are the diffusers operational? 0 ❑ ❑ ❑ Is the foam the proper color for the treatment process? 0 ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? 0 ❑ ❑ ❑ Is the DO level acceptable? 0 ❑ ❑ ❑ Is the DO level acceptable?(1.0 to 3.0 mg/1) 0 ❑ ❑ ❑ Comment: DO was reported to be around 2.5 mg/I in the first AB and 2 mg/I in the second AB Secondary Clarifier Is the clarifier free of black and odorous wastewater? Is the site free of excessive buildup of solids in center well of circular clarifier? Are weirs level? Is the site free of weir blockage? Is the site free of evidence of short-circuiting? Is scum removal adequate? Is the site free of excessive floating sludge? Is the drive unit operational? Is the return rate acceptable (low turbulence)? Is the overflow clear of excessive solids/pin floc? Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth) Comment: Sludge blanket was reported to be around 2.5 ft. Sludge has not been pumped recently due to the low flow coming into the plant. Disinfection -Tablet Are tablet chlorinators operational? Are the tablets the proper size and type? Yes No NA NE ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ Page# 4 Permit: NCO039608 Inspection Date: 11/14/2019 Owner - Facility: Summit Woods Apartments WWTP Inspection Type: Compliance Evaluation Disinfection -Tablet Yes No NA NE Number of tubes in use? 1 Is the level of chlorine residual acceptable? ❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup? 0 ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? ❑ ❑ ❑ Comment: De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? 0 ❑ ❑ ❑ Is storage appropriate for cylinders? 0 ❑ ❑ ❑ # Is de -chlorination substance stored away from chlorine containers? 0 ❑ ❑ ❑ Comment: Are the tablets the proper size and type? 0 ❑ ❑ ❑ Are tablet de -chlorinators operational? 0 ❑ ❑ ❑ Number of tubes in use? 1 Comment: Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? 0 ❑ ❑ ❑ Is flow meter calibrated annually? 0 ❑ ❑ ❑ Is the flow meter operational? 0 ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? 0 ❑ ❑ ❑ Comment: The Stevens flow meter was calibrated in 6/2019 Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? ❑ ❑ 0 ❑ Are the receiving water free of foam other than trace amounts and other debris? ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment: The flow from the plant goes directly into a storm drain. so there is no standard effluent pipe. The effluent can be seen leaving the plant and again in a small holding box on its way down the hill away from the plant before it goes under the highway (321) and into the storm drain. The holding box is covered by a silver metal lid and is next to the road heading up to the apartment complex. Page# 5 Permit: NCO039608 Owner - Facility: Summit Woods Apartments WWTP Inspection Date: 11/14/2019 Inspection Type: Compliance Evaluation Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? ❑ ❑ 0 ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑ representative)? Comment: Grab samples are taken from the holdina box awav from the Dlant mentioned above. and then put on ice. The effluent was clear the day of inspection. Upstream / Downstream Sampling Yes No NA NE Is the facility sampling performed as required by the permit (frequency, sampling type, and 0 ❑ ❑ ❑ sampling location)? Comment: taken in the middle fork of the new river Page# 6