Loading...
HomeMy WebLinkAboutNC0066991_Compliance Evaluation Inspection_20191021ROY COOPER Governor MICHAEL S. REGAN Secretary LINDA CULPEPPER Director Mr. Danny Clark, Director of Facilites Watauga County Schools P.O. Box 1790 Boone, NC 28607 �ry 44, NORTH CAROLINA EnNlmnmrrtlnl Quality October 21, 2019 SUBJECT: Compliance Evaluation Inspection Bethel Elementary School WWTP NPDES Permit No. NCO066991 Watauga County Dear Mr. Clark, On October 16, 2019, Kelli Park and Mike Turner, of this office, met with Eric Bolick, Operator in Responsible Charge (ORC), to perform a Compliance Evaluation Inspection at the Bethel Elementary School wastewater treatment plant. This type of inspection consists of two basic parts: an in -office file review and an on -site inspection of the treatment facility. The attached EPA inspection form details the areas that were evaluated during this inspection. The inspection of the facility was satisfactory. If you have any questions regarding the inspection or this report, please contact Kelli Park or me at (336) 776-9800 or by email at kelli.park(a-_)ncdenr.gov or lon.snider(c-_)ncdenr.gov. Sincerely, Docu Siiggned by: L-VA. 1 _.49E225C94EA.. Lon Snider Regional Supervisor Water Quality Regional Operations Division of Water Resources Attachments: EPA Water Compliance Inspection Report cc: WSRO United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I 2 IF I 3 I NC0066991 111 12 I 19/10/16 I17 18 I S J 19 L G] 201 I 211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved ------------------- 671 70 I I 71 I I 72 I r I 73 I I 174 751 I I I I I I I80 u I� I I i Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES oermit Number) 12:OOPM 19/10/16 17/10/01 Bethel Elementary School 138 Bethel School Rd Exit Time/Date Permit Expiration Date Sugar Grove NC 28679 12:30PM 19/10/16 22/09/30 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Eric R Bolick/ORC/828-268-4630/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Danny Clark,175 Pioneer Trl Boone NC 286071790/Facilities Director/828-264-6393/8282649670 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenance 0 Records/Reports Self -Monitoring Program 0 Facility Site Review Effluent/Receiving Waters Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Kelli A Park DWR/WSRO WQ/336-776-9689/ Signature of Management Q /�o ulgnedby: Agency/Office/Phone and Fax Numbers Date —r SWer 10/21/2019 FLI EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type (Cont.) NCO066991 I11 121 19/10/16 117 18 JCJ Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) On October 16, 2019, Kelli Park and Mike Turner, of this office, met with Eric Bolick, Operator in Responsible Charge (ORC), to perform a Compliance Evaluation Inspection at the Bethel Elementary School wastewater treatment plant. This type of inspection consists of two basic parts: an in -office file review and an on -site inspection of the treatment facility. The attached EPA inspection form details the areas that were evaluated during this inspection. The inspection of the facility was satisfactory. If you have any questions regarding the inspection or this report, please contact Kelli Park or me at (336) 776-9800 or by email at kelli.park@ncdenr.gov or Ion.snider@ncdenr.gov. Page# Permit: NCO066991 Owner - Facility: Bethel Elementary School Inspection Date: 10/16/2019 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ 0 ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: Has not historically analyzed for these in the past due to the small size and low flow of the plant. Plans to start using sludge fudge soon. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ ❑ on each shift? Is the ORC visitation log available and current? ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? ❑ ❑ ❑ Page# 3 Permit: NCO066991 Owner - Facility: Bethel Elementary School Inspection Date: 10/16/2019 Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑ Comment: Water Tech Labs is used for sample analysis Flow Measurement - Influent Yes No NA NE # Is flow meter used for reporting? ❑ 0 ❑ ❑ Is flow meter calibrated annually? ❑ ❑ 0 ❑ Is the flow meter operational? ❑ ❑ 0 ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Comment: flow is reported by using the drinking water's meter reading. Septic Tank Yes No NA NE (If pumps are used) Is an audible and visual alarm operational? ❑ ❑ 0 ❑ Is septic tank pumped on a schedule? 0 ❑ ❑ ❑ Are pumps or syphons operating properly? 0 ❑ ❑ ❑ Are high and low water alarms operating properly? ❑ ❑ 0 ❑ Comment: pumped yearly Aeration Basins Yes No NA NE Mode of operation Ext. Air Type of aeration system Diffused Is the basin free of dead spots? 0 ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ 0 ❑ Are the diffusers operational? 0 ❑ ❑ ❑ Is the foam the proper color for the treatment process? 0 ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? 0 ❑ ❑ ❑ Is the DO level acceptable? ❑ ❑ ❑ Is the DO level acceptable?(1.0 to 3.0 mg/1) ❑ ❑ ❑ Comment: Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? 0 ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ ❑ 0 ❑ Are weirs level? 0 ❑ ❑ ❑ Page# 4 Permit: NC0066991 Owner - Facility: Inspection Date: 10/16/2019 Inspection Type: Bethel Elementary School Compliance Evaluation Secondary Clarifier Yes No NA NE Is the site free of weir blockage? 0 ❑ ❑ ❑ Is the site free of evidence of short-circuiting? 0 ❑ ❑ ❑ Is scum removal adequate? 0 ❑ ❑ ❑ Is the site free of excessive floating sludge? 0 ❑ ❑ ❑ Is the drive unit operational? ❑ ❑ 0 ❑ Is the return rate acceptable (low turbulence)? 0 ❑ ❑ ❑ Is the overflow clear of excessive solids/pin floc? 0 ❑ ❑ ❑ Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth) 0 ❑ ❑ ❑ Comment: Pumped each summer by Appalachian Pumping. Records were not available showing how many gallons were pumped. Please begin maintaining records of how many gallons are pumped per visit, who did the pumping, and the date. Disinfection -Tablet Yes No NA NE Are tablet chlorinators operational? 0 ❑ ❑ ❑ Are the tablets the proper size and type? M ❑ ❑ ❑ Number of tubes in use? 2 Is the level of chlorine residual acceptable? ❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup? 0 ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? ❑ ❑ ❑ Comment: De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? 0 ❑ ❑ ❑ Is storage appropriate for cylinders? 0 ❑ ❑ ❑ # Is de -chlorination substance stored away from chlorine containers? 0 ❑ ❑ ❑ Comment: Are the tablets the proper size and type? 0 ❑ ❑ ❑ Are tablet de -chlorinators operational? 0 ❑ ❑ ❑ Number of tubes in use? 2 Comment: Page# 5 Permit: NCO066991 Owner - Facility: Inspection Date: 10/16/2019 Inspection Type: Bethel Elementary School Compliance Evaluation Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment: Effluent was clear the day of inspection Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units? M ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑ representative)? Comment: Grab samples are taken and put on ice. Standby Power Yes No NA NE Is automatically activated standby power available? ❑ 0 ❑ ❑ Is the generator tested by interrupting primary power source? ❑ ❑ 0 ❑ Is the generator tested under load? ❑ ❑ 0 ❑ Was generator tested & operational during the inspection? ❑ ❑ 0 ❑ Do the generator(s) have adequate capacity to operate the entire wastewater site? 0 ❑ ❑ ❑ Is there an emergency agreement with a fuel vendor for extended run on back-up power? 0 ❑ ❑ ❑ Is the generator fuel level monitored? M ❑ ❑ ❑ Comment: A larae aenerator was recentiv purchased as backup for the 3 Watauaa schools with NPDES permits. It is located at the main shop and will be taken to the plants when needed. Upstream / Downstream Sampling Yes No NA NE Is the facility sampling performed as required by the permit (frequency, sampling type, and 0 ❑ ❑ ❑ sampling location)? Comment: Page# 6