HomeMy WebLinkAboutAQ_F_0400016_20181002_PRMT_Permit ROY COOPER STA7Za
µn m IAA
Governor
MICHAEL S.REGAN
Secretory
QVAM
MICHAEL A.ABRACZINSKAS NORTH CAROLINA
Director Environmental Quality
October 2, 2018
Mr. Bernard Hodges
President
Wade Manufacturing Co - Wadesboro
PO Box 32
Wadesboro,NC 28170
Subject: Air Permit No. 03577R19
Wade Manufacturing Co -Wadesboro
Wadesboro, Anson County,North Carolina
Permit Class: Synthetic Minor
Facility ID# 0400016
Dear Mr. Hodges:
In accordance with your completed application received August 23, 2018, we are forwarding
herewith Permit No. 03577RI9 to Wade Manufacturing Co- Wadesboro, Wadesboro, Anson
County,North Carolina for the construction and operation of air emissions sources or air cleaning
devices and appurtenances. Additionally, any emissions activities determined from your air permit
application as meeting the exemption requirements contained in 15A NCAC 2Q .0102 have been
listed for information purposes as an "ATTACHMENT" to the enclosed air permit. Please note the
records retention requirements are contained in General Condition 2 of the General Conditions and
Limitations.
If any parts, requirements, or limitations contained in this permit are unacceptable to you,
you have the right to request a formal adjudicatory hearing within 30 days following receipt of this
permit, identifying the specific issues to be contested. Such a request will stay the effectiveness of
the entire permit. This hearing request must be in the form of a written petition, conforming to G.S.
150B-23 of the North Carolina General Statutes, and filed with the Office of Administrative
Hearings, 6714 Mail Service Center, Raleigh,NC 27699-6714. The form for requesting a formal
adjudicatory hearing may be obtained upon request from the Office of Administrative Hearings.
Unless a request for a hearing is made pursuant to G.S. 150B-23,this air permit shall be final and
binding.
You may request modification of your air permit through informal means pursuant to G.S.
150B-22. This request must be submitted in writing to the Director and must identify the specific
provisions or issues for which the modification is sought. Please note that the permit will become
final and binding regardless of a request for informal modification unless a request for a hearing is
also made under G.S. 150B-23.
North Carolina Department of Environmental Quality I Division of Air Quality
.:,. Fayetteville Regional Office 1 225 Green Street,Suite 714 1 Fayetteville,NC 28301-5094
iJOR7H C.11fYOLiN.4
910,433,3300 T 1 910.485.7467 F
Bernard Hodges
October 2, 2018
Page 2
Unless exempted by a condition of this permit or the regulations, construction of new
air pollution sources or air cleaning devices, or modifications to the sources or air cleaning
devices described in this permit must be covered under a permit issued by the Division of Air
Quality prior to construction.Failure to do so is a violation of G.S. 143-215.108 and may
subject the Permittee to civil or criminal penalties as described in G.S. 143-215.114A and 143-
' 215.114B.
This permit shall be effective from October 2, 2018 until September 30, 2026, is
nontransferable to future owners and operators, and shall be subject to the conditions and limitations
as specified therein.
Changes have been made to the permit stipulations. The Permittee is responsible for
carefully reading the entire permit and evaluating the requirements of each permit
stipulation. The Permittee shall comply with all terms,conditions, requirements,limitations
and restrictions set forth in this permit. Noncompliance with any permit condition is grounds
for enforcement action, for permit termination, revocation and reissuance, or modification, or
for denial of a permit renewal application. Should you have any questions concerning this matter,
please contact Jeffrey D. Cole at 410-433-3300.
Sincerely,
Heather Carter,Regional Supervisor
Division of Air Quality,NC DEQ -
JDC
Enclosures
c: Fayetteville Regional Office
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENTAL QUALITY
DIVISION OF AIR QUALITY
AIR PERMIT NO. 03577R19
Issue Date: October 2, 2018 Effective Date: October 2, 2018
Expiration Date: September 30, 2026 Replaces Permit: 03577R18
To construct and operate air emission source(s) and/or air cleaning device(s), and for the
discharge of the associated air contaminants into the atmosphere in accordance with the provisions
of Article 21 B of Chapter 143, General Statutes of North Carolina(NCGS) as amended, and other
applicable Laws, Rules and Regulations,
Wade Manufacturing Co -Wadesboro
Highway 74 East
Wadesboro, Anson County,North Carolina
Permit Class: Synthetic Minor
Facility ID#0400016
(the Permittee) is hereby authorized to construct and operate the air emissions sources and/or air
cleaning devices and appurtenances described below:
.................................
..._.........._.m_._.......................................................ro _. ........_._......._..........._.........._..__...._.....__._�._ W_.W..._. w. ...
B 1 Natural gas/No.6 fuel oil-fired boiler NIA NIA
(72 mmBtu/hr maximum heat input)
__. - .W - _ _
B2 Natural gas/No 6 fuel oil-fired boiler N/A NIA
�(24.76 mm$tu/hr maximum heat input) i I
__._. w
Textile roller printer(3,600 pounds of cloth
i
per hour process capacity)consisting of- l I
PR3 i a)8 print stations N/A N/A
b) 1 natural gas direct-fired dryer
(2 mmBmq r maximum heat input)
Textile screen printer(3,600 pounds of cloth
per hour process capacity)consisting of.
PR4 a)8 rotary screen printing stations N/A N/A
b) 1 natural gas direct-fired dryer
(4.8 mmBtu/hr maximum heat input)with
four zones
------------
Textile screen printer(3,600 pounds of cloth
per hour process capacity)consisting of:
PRS j a) 12 rotary screen printing stations NIA NIA
b) 1 natural gas direct-fired dryer
(4.8 mmBtuAu maximum heat input)with I
four zones
Permit No. 03577R19
!, Page 2
.................MMMMM
Finishing range(5,760 pounds of cloth per
hour process capacity)consisting of:
j TEN2 a) 1 pad applied finishing station I
I b) 1 natural gas direct-fired(12.0 mmBtu/hr NIA NIA i
maximum heat input)eight zone tenter frame
oven ...._....
..... . ... ......_..........
Finishing range(4,320 pounds of cloth per
hour process capacity)consisting of:
TEN3 a) 1 pad applied finishing station NIA NIA
b) 1 natural gas direct-fired(6.0 mmBtu/hr
maximum heat input)two zone tenter frame
oven
One(1)bleach range and one(1)natural gas
i BLI and TEN4 direct-fired(8.5 mmBtu/hr maximum heat NIA NIA
1
input)three zone tenter frame oven
NIA I CR1 Steam heated cotton dye range NIA
_..... _. .
Pigment range(4,800 pounds of cloth per hour;
process capacity)consisting of:
PIG a) 1 natural gas direct-fired dryer(4.0 N/A NIA
mmBtu/hr maximum heat input)predryer
b) 1 pad applied ink dyeing station
_l c) 1 steam heated dryer _m_.P. ) - ....... ..
Thermasol range(4,800 pounds of cloth per
hour process capacity)consisting of:
j TRI a} 1 pad applied finishing station i NIA N/A
b) 1 natural gas direct-fired dryer j
E
(7 0 TTBtu/hr maximum heat input)dryer ( �
ESL1 Shop lathe(500 pounds per hour of rubber SL-1C Cyclone
covered pad rolls) L115 inch diameter)
BF-1 Bagfilter
(12 square feet of filter
area)
' SS 1 Starch storage silo In parallel with In parallel with
s (22.5 tons per hour filling rate)
i
BF-2 Bagfilter E
(12 square feet of filter
area)
OP-1CA Paper Panel Filter
(6.55 square feet of filter
area)
Blendomat
ON In series with In series with
(2,600 pounds per hour of cotton fiber)
OP-1CB Rotary Drum Filter
(46.5 square feet of filter
_......__..___.......... ,__...i.. .-.- __ _.__,_....___..___._.__._.._.. _ _....__..__.._____.._m .. ,_,....,.-., _.. area)
Carding and drawing operation Rotary Drum Filter
AClICARDl (2100 pounds per hour of cotton fiber) CARD1-1C (545u square feet of
surface area)
Permit No. 03577R19
Page 3
............. _.... _....... .
I
I Spinning operation
Paper Filter
AC2 AC24 C (266.8 square feet of
(2100 pounds per hour of cotton fiber)
surface area)
AC3 j AC3-1C Paper Filter
(371.2 square feet of
surface area)collecting
from AC-3
AC4 AC4-1C Rotary Drum Filter
Three(3)weaving areas(1,870 pounds (834.9 square feet of
per hour of cotton yarn,total capacity of [
AC3,AC4, and AC5) surface area)collecting '
AC-4.
1 '
AC5 1 AC5-lC Rotary Drum Filter
(545.3 square feet of j
surface area)collecting
[ AC-5.
NAP 1 NAP 1-1 C Rotary Drum Filter
483.3 square feet of
( q I
surface area)collecting
Two(2)napping areas(2,370 pounds per hour: from NAP 1.
of cotton cloth,total capacity of NAP 1 and [
NAP2 NAP2) NAP24 C Rotary Drum Filter
(142.1 square feet of
surface area)collecting
j from NAP 2.
RP Retention Pond
._._...._...._____l N/A W ..... NIA.
in accordance with the completed application 0400016.18A received August 23, 2018 including any
plans, specifications,previous applications, and other supporting data, all of which are filed with the
Department of Environmental Quality, Division of Air Quality (DAQ) and are incorporated as part
of this permit.
This permit is subject to the following specified conditions and limitations including any
TESTING,REPORTING, OR MONITORING REQUIREMENTS:
A. SPECIFIC CONDITIONS AND LIMITATIONS
1. Any air emission sources or control devices authorized to construct and operate above must
be operated and maintained in accordance with the provisions contained herein. The
Permittee shall comply with applicable Environmental Management Commission
Regulations, including Title 15A North Carolina Administrative Code (NCAC), Subchapter
2D .0202, 2D .0503, 2D .0515, 2D .0516, 2D .0521, 2D .0535, 2D .0540, 2D .0611, 2D
.1100, 2D .1806, 2Q .0315 and 2Q .0317 (Avoidance).
Permit No. 03577R19
Page 4
2. PERMIT RENEWAL AND EMISSION INVENTORY REQUIREMENT -The Permittee,
at least 90 days prior to the expiration date of this permit, shall request permit renewal by
letter in accordance with 15A NCAC 2Q .0304(d) and(f).Pursuant to 15A NCAC 2Q
.0203(i), no permit application fee is required for renewal of an existing air permit(without
a modification request). The renewal request(with AA application form) should be
submitted to the Regional Supervisor, DAQ. Also, at least 90 days prior to the expiration
date of this permit, the Permittee shall submit the air pollution emission inventory report
(with Certification Sheet) in accordance with 15A NCAC 2D .0202,pursuant to N.C.
General Statute 143 215.65. The report shall be submitted to the Regional Supervisor, DAQ
and shall document air pollutants emitted for the 2025 calendar year.
3. PARTICULATE CONTROL REQUIREMENT -As required by 15A NCAC 2D .0503
"Particulates from Fuel Burning Indirect Heat Exchangers," particulate matter emissions
from the fuel burning indirect heat exchangers shall not exceed the allowable emission rates
listed below:
MIMEMMO N. sm
(Boiler B1)Natural gas/No. 6 fuel oil-fired boiler 0.33 lb/rnmBtu {:
(72 mmBtu/hr maximum heat input)
(Boiler B2)Natural gas/No. 6 fuel oil-fired boiler
{24.76 mmBtu/hr maximum heat input) 0.471b/mmBtu
._.__...__._..........................
.�
4. PARTICULATE CONTROL REQUIREMENT- As required by 15A NCAC 2D .0515
"Particulates from Miscellaneous Industrial Processes," particulate matter emissions from
the emission sources shall not exceed allowable emission rates. The allowable emission rates
are, as defined in 15A NCAC 2D .0515, a function of the process weight rate and shall be
determined by the following equation(s), where P is the process throughput rate in tons per
hour(tons/hr) and E is the allowable emission rate in pounds per hour(lbs/hr).
E=4.10 * (P) 0.67 for P<= 30 tons/hr,or
E= 55 * (P) 1,11- 40 for P>30 tons/hr
5. SULFUR DIOXIDE CONTROL REQUIREMENT -As required by 15A NCAC 2D .0516
"Sulfur Dioxide Emissions from Combustion Sources," sulfur dioxide emissions from the
combustion sources shall not exceed 2.3 pounds per million Btu heat input.
6. VISIBLE EMISSIONS CONTROL REQUIREMENT -As required by 15A NCAC 2D
.0521 "Control of Visible Emissions," visible emissions from source ID Nos. PR4,PR5,
TEN2, TENS, TRl,B1, B2, BL1, TEN4, OP1, SU, and SS1, manufactured after July 1,
1971, shall not be more than 20 percent opacity when averaged over a six-minute period,
except that six-minute periods averaging not more than 87 percent opacity may occur not
more than once in any hour nor more than four times in any 24-hour period. However,
sources which must comply with a visible emissions standard in 15A NCAC 2D .0524 "New
Source Performance Standards" or .1110 "National Emission Standards for Hazardous Air
Pollutants" shall meet that standard instead of the 2D .0521 visible emissions standard.
Permit No. 03577R19
Page 5
7. VISIBLE EMISSIONS CONTROL REQUIREMENT - As required by 15A NCAC 2D
.0521 "Control of Visible Emissions," visible emissions from source ID Nos. PIG1, PR3,
ACl/CARD1, AC2, AC3, AC4,AC5,NAP and NAP2,manufactured as of July 1, 1971,
shall not be more than 40 percent opacity when averaged over a six-minute period, except
that six-minute periods averaging not more than 90 percent opacity may occur not more than
once in any hour nor more than four times in any 24-hour period. However, sources which
must comply with a visible emissions standard in 15A NCAC 2D .0524 "New Source
Performance Standards" or .1110 "National Emission Standards for Hazardous Air
Pollutants" shall meet that standard instead of the 2D .0521 visible emissions standard.
8. NOTIFICATION REQUIREMENT - As required by 15A NCAC 2D .0535,the Permittee of
a source of excess emissions that last for more than four hours and that results from a
malfunction, a breakdown of process or control equipment or any other abnormal
conditions, shall:
a. Notify the Director or his designee of any such occurrence by 9:00 a.m. Eastern time
of the Division's next business day of becoming aware of the occurrence and
describe:
i. the name and location of the facility,
ii. the nature and cause of the malfunction or breakdown,
iii. the time when the malfunction or breakdown is first observed,
iv. the expected duration, and
V. an estimated rate of emissions.
b. Notify the Director or his designee immediately when the corrective measures have
been accomplished.
This reporting requirement does not allow the operation of the facility in excess of
Environmental Management Commission Regulations.
9. FUGITIVE DUST CONTROL REQUIREMENT -As required by 15A NCAC 2D .0540
"Particulates from Fugitive Dust Emission Sources," the Permittee shall not cause or allow
fugitive dust emissions to cause or contribute to substantive complaints or excess visible
emissions beyond the property boundary. If substantive complaints are received or excessive
fugitive dust emissions from the facility are observed beyond the property boundaries for six
minutes in any one hour (using Reference Method 22 in 40 CFR, Appendix A), the owner or
operator may be required to submit a fugitive dust plan as described in 2D .0540(f).
"Fugitive dust emissions" means particulate matter that does not pass through a process
stack or vent and that is generated within plant property boundaries from activities such as:
unloading and loading areas,process areas stockpiles, stock pile working,plant parking lots,
and plant roads (including access roads and haul roads).
Permit No. 03577R19
Page 6
10. CYCLONE REQUIREMENTS - As required by 15A NCAC 2D .0611, particulate matter
emissions shall be controlled as described in the permitted equipment list.
a. Inspection and Maintenance Requirements -To comply with the provisions of this
permit and ensure that emissions do not exceed the regulatory limits,the Permittee
shall perform an annual (for each 12 month period following the initial inspection)
inspection of the cyclone system. In addition, the Permittee shall perform periodic
inspections and maintenance (I&M) as recommended by the manufacturer.
b. Recordkeeping Requirements -The results of all inspections and any variance from
the manufacturer's recommendations or from those given in this permit(when
applicable) shall be investigated with corrections made and dates of actions recorded
in a cyclone logbook. Records of all maintenance activities shall be recorded in the
logbook. The cyclone logbook(in written or electronic format) shall be kept on-site
and made available to DAQ personnel upon request.
11. FABRIC FILTER REQUIREMENTS including cartridge filters, baghouses, and other ddar
filter particulate collection devices - As required by 15A NCAC 2D .0611,particulate matter
emissions shall be controlled as described in the permitted equipment list.
a. Inspection and Maintenance Requirements -To comply with the provisions of this
permit and ensure that emissions do not exceed the regulatory limits, the Permittee
shall perform, at a minimum, an annual (for each 12 month period following the
initial inspection) internal inspection of each particulate collection device system. In
addition,the Perrittee shall perform periodic inspections and maintenance as
recommended by the equipment manufacturer.
b. Recordkeeping Requirements -The results of all inspections and any variance from
manufacturer's recommendations or from those given in this permit(when
applicable) shall be investigated with corrections made and dates of actions recorded
in a logbook. Records of all maintenance activities shall be recorded in the logbook.
The logbook(in written or electronic format) shall be kept on-site and made
available to DAQ personnel upon request.
Permit No. 03 577R19
Page 7
12. TOXIC AIR POLLUTANT EMISSIONS LIMITATION AND REPORTING
REQUIREMENT - Pursuant to 15A NCAC 2D .1100 "Control of Toxic Air Pollutants," and
in accordance with the approved application for an air toxic compliance demonstration,the
following permit limits shall not be exceeded:
_.. _ _ _..._ _... ... w..........__.._.....---------__..._._......_._... ..__. _.__...._.._.___ _ _...._... -.. ........._ __..._..m....
i
Ammonia 0.30 pounds per hour
Tenter frame(ID No. TEN2) Formaldehyde 0.128 pounds per hour
MIBK(methyl isobutyl ketone) 6.32 pounds per hour
Styrene 0.21 pounds per hour
Ammonia 0.228 pounds per hour
Tenter frame(ID No. TEN3) Formaldehyde 0.104 pounds per hour
MIDK(methyl isobutyl ketone) 6.32 pounds per hour
Styrene 0.21 pounds per hour
l � ;
Tenter frame(ID No. TEN4) IF
Ammonia 0.004 pounds per hour
Boiler(ID No B 1) Formaldehyde
mmm _a 0 0204 pounds per hour
A Boiler(ID No. B2) Formaldehyde ] 0.0007 pounds per hour
Ammonia 3.36 pounds per hour
Printer ID No.PR3 Formaldehyde 0.084 pounds per hour
( ) � Y P
Styrene 1.24 pounds per hour
1 Ammonia 2.86 pounds per hour
Printer(ID No. PR4) Formaldehyde 0.084 pounds per hour
Styrene 1.24 pounds per hour
Ammonia 2.86 pounds per hour E
Printer(ID No. PR5) Formaldehyde 0.084 pounds per hour
Styrene 1.24 pounds per hour
Pigment range(ID No.PIG 1) Formaldehyde 0.0008 pounds per hour
Thermasol range (ID No.TRl) Ammonia 1.12 pounds per hour
Formaldehyde 0.002 pounds per hour
Ammonia i 0.0012 pounds per hour
Retention Pond(ID No.RP) Formaldehyde 0.00 16 pounds per hour
a. Restrictions - To ensure compliance with the above limits, the following restrictions
shall apply:
i. The input rate of ammonia to the roller printer(ID Nos. PR3) shall not
exceed 3.35 pounds per hour,
ii. The input rate of ammonia to each screen printer (ID Nos. PR4 and PR5)
shall not exceed 2.85 pounds per hour,
Permit No. 03577R19
Page 8
iii. The input rate of formaldehyde to the tenter frame (ID Nos. TEN3) shall not
exceed 0.104 pounds per hour, and
iv. The input rate of formaldehyde to the tenter frame (ID No. TEN2) shall not
exceed 0.126 pounds per hour.
b. Reporting Requirements - For compliance purposes, within 30 days after each
calendar year, regardless of the actual emissions,the following shall be reported to
the Regional Supervisor, DAQ:
i. The maximum hourly rate of ammonia input to each printer(ID Nos. PR3,
PR4, PR5) for each day of production, and
ii. The maximum hourly rate of formaldehyde input to each tenter frame (ID
Nos. TEN2, TEN3) for each day of production.
c. Recordkeeping Requirements - The following recordkeeping requirements apply:
i. The maximum hourly rate of ammonia input to each printer (ID Nos. PR3,
PR4,PR5)for each day of production, and
ii. The maximum hourly rate of formaldehyde input to each tenter frame (ID
Nos. TEN2, TEN3) for each day of production.
13. CONTROL AND PROHIBITION OF ODOROUS EMISSIONS -As required by 15A
NCAC 2D .1806 "Control and Prohibition of Odorous Emissions"the Permittee shall not
operate the facility without implementing management practices or installing and operating
odor control equipment sufficient to prevent odorous emissions from the facility from
causing or contributing to objectionable odors beyond the facility's boundary.
14. LIMITATION TO AVOID 15A NCAC 20 .0501 -Pursuant to 15A NCAC 2Q .0315
"Synthetic Minor Facilities,"to avoid the applicability of 15A NCAC 2Q .0501 "Purpose of
Section and Requirement for a Permit," as requested by the Permittee,facility-wide
emissions shall be less than the following:
PM10 100
S02 100
NOx 100
a. Operations Restrictions - To ensure emissions do not exceed the limitations above,
the following restrictions shall apply:
i. The No.6 Fuel Oil combusted shall be less than 601,000 gal per consecutive
12-month period.
ii. The sulfur content of the No. 6 Fuel Oil shall be limited to 2.1% sulfur by
weight.
Permit No. 03577R19
Page 9
iii. PMio emissions shall be controlled by cyclones, bagfilters,paper panel filters,
or rotary drum filters as described in the emission source table.
iv. The Permittee shall perform all inspection and maintenance requirements as
required by the 15A NCAC 2D .0611 "Cyclone Requirements" and "Fabric
Filter Requirements," permit conditions.
b. Recordkeeping_Requirements
i. The Permittee shall record monthly and total annually the following:
A. the amount of No. 6 fuel oil combusted in the boilers and
ii. Fuel supplier certification shall be kept on-site and made available to DAQ
personnel upon request.
iii. The Permittee shall perform all recordkeeping requirements as required by
the 15A NCAC 2D .0611 "Cyclone Requirements" and "Fabric Filter
Requirements," permit conditions.
c. Reporting Requirements - Within 30 days after each calendar year, regardless of the
actual emissions, the Permittee shall submit the following:
i. emissions and/or operational data listed below. The data should include
monthly and 12 month totals for the previous 12 month period.
A. The amount of No. 6 fuel oil combusted in the boilers.
15. AVOIDANCE CONDITION FOR AREA SOURCES SUBJECT TO 40 CFR 63 Subpart
JJJJJJ (6J) - In accordance with 15A NCAC 2Q .0317,the Permittee is avoiding
applicability of 40 CFR 63 Subpart JJJJJJ(6J) "Industrial,Commercial, and Institutional
Boilers Area Sources." The Permittee is permitted to operate natural gas/No. 6 fuel oil-
fired boilers (ID Nos. B 1 and B2). Per 40 CFR 63.11195(e),these sources are exempt from
this Subpart because they are defined as gas-fired boilers in 40 CFR 63.11237. In order to
maintain this exemption,the Permittee is allowed to fire liquid fuel only during periods of
gas curtailment, gas supply interruptions, startups, or for periodic testing on liquid fuel
(periodic testing not to exceed a combined total of 48 hours during any calendar year).
a. The Permittee shall maintain records that document the time periods when liquid fuel
is fired and the reasons the liquid fuel is fired.
b. If the Permittee fires liquid fuel for reasons other than gas curtailment, gas supply
interruptions, startups, or for periodic testing on liquid fuel,the Permittee is no
longer exempt from Subpart JJJJJJ (6J). As required by 40 CFR 62.11225(g),the
Permittee must provide notice within 30 days of the fuel switch. The notification
must identify:
L The name of the owner or operator of the affected source, the location of the
source, the boiler(s) that have switched fuels, and the date of the notice.
ii. The date upon which the fuel switch occurred.
Permit No. 03577R19
Page 10
As required by 40 CFR 63.11210(h), the Permittee must demonstrate compliance within
180 days of the effective date of the fuel switch.
16. LIMITATION TO AVOID 15A NCAC 2D .0530 "PREVENTION OF SIGNIFICANT
DETERIORATION" - In accordance with 15A NCAC 2Q .0317, to comply with this permit
and avoid the applicability of 15A NCAC 2D .0530 "Prevention of Significant
Deterioration," as requested by the Permittee, emissions shall be limited as follows:
i
Facility Wide ;�S022 250
W.__.. _ ._ _ .._.._. ..._ _.,I. ._. _ _
a. Operations Restrictions, Recordkeeping Requirements, and Reporting Requirements
- By complying with the operations restrictions, recordkeeping requirements, and
reporting requirements in stipulation 15A NCAC 2Q .0315, Limitation to Avoid 15A
NCAC 2Q .0501, in a correct and timely manner,-the Permittee shall have also
complied with the operations restrictions,recordkeeping and reporting requirements
for 15A NCAC 2Q .0317, Limitation to Avoid 15A NCAC 2D .0530.
Permit No. 03577R19
Page 11
B. GENERAL CONDITIONS AND LIMITATIONS
1. In accordance with G.S. 143-215.108(c)(1), TWO COPIES OF ALL DOCUMENTS,
REPORTS TEST DATA MONITORING DATA NOTIFICATIONS REQUESTS FOR
RENEWAL AND ANY OTHER INFORMATION REQUIRED BY THIS PERMIT shall
be submitted to the:
Regional Supervisor
North Carolina Division of Air Quality
Fayetteville Regional Office
Systel Building
225 Green Street, Suite 714
Fayetteville,NC 28301-5094
910-433-3300
For identification purposes, each submittal should include the facility name as listed on the
permit, the facility identification number, and the permit number.
2. RECORDS RETENTION REQUIREMENT - In accordance with 15A NCAC 2D .0605,
any records required by the conditions of this permit shall be kept on site and made available
to DAQ personnel for inspection upon request. These records shall be maintained in a form
suitable and readily available for expeditious inspection and review. These records must be
kept on site for a minimum of 2 years, unless another time period is otherwise specified.
3. ANNUAL FEE PAYMENT -Pursuant to 15A NCAC 2Q .0203(a), the Perrnittee shall pay
the annual permit fee within 30 days of being billed by the DAQ. Failure to pay the fee in a
timely manner will cause the DAQ to initiate action to revoke the permit.
4. . EQUIPMENT RELOCATION - In accordance with 15A NCAC 2Q .0301, anew air permit
shall be obtained by the Permittee prior to establishing,building, erecting, using, or
operating the emission sources or air cleaning equipment at a site or location not specified in
this permit.
5. REPORTING REQUIREMENT - In accordance with 15A NCAC 2Q .0309, any of the
following that would result in previously unpermitted, new, or increased emissions must be
reported to the Regional Supervisor, DAQ:
a. changes in the information submitted in the application regarding facility emissions;
b. changes that modify equipment or processes of existing permitted facilities; or
c. changes in the quantity or quality of materials processed.
If appropriate,modifications to the permit may then be made by the DAQ to reflect any
necessary changes in the permit conditions. In no case are any new or increased emissions
allowed that will cause a violation of the emission limitations specified herein.
Permit No. 03577R19
Page 12
6. In accordance with 15A NCAC 2Q .0309, this permit is subject to revocation or
modification by the DAQ upon a determination that information contained in the application
or presented in the support thereof is incorrect, conditions under which this permit was
granted have changed, or violations of conditions contained in this permit have occurred. In
accordance with G.S. 143-215.108(c)(1), the facility shall be properly operated and
maintained at all times in a manner that will effect an overall reduction in air pollution.
Unless otherwise specified by this permit, no emission source may be operated without the
concurrent operation of its associated air cleaning device(s) and appurtenances.
7. In accordance with G.S. 143-215.108(c)(1), this permit is nontransferable by the Permittee.
Future owners and operators must obtain a new air permit from the DAQ.
8. In accordance with G.S. 143-215.108(c)(1), this issuance of this permit in no way absolves
the Permittee of liability for any potential civil penalties which may be assessed for
violations of State law which have occurred prior to the effective date of this permit.
9. In accordance with G.S. 143-215.108(c)(1),this permit does not relieve the Permittee of the
responsibility of complying with all applicable requirements of any Federal, State, or Local
water quality or land quality control authority.
10. In accordance with 15A NCAC 2D .0605, reports on the operation and maintenance of the
facility shall be submitted by the Permittee to the Regional Supervisor, DAQ at such
intervals and in such form and detail as may be required by the DAQ. Information required
in such reports may include, but is not limited to, process weight rates, firing rates,hours of
operation, and preventive maintenance schedules.
11. A violation of any term or condition of this permit shall subject the Permittee to enforcement
pursuant to G.S. 143-215.114A, 143-215.114B, and 143-215.114C, including assessment of
civil and/or criminal penalties.
12. Pursuant to North Carolina General Statute 143-215.3(a)(2), no person shall refuse entry or
access to any authorized representative of the DAQ who requests entry or access for
purposes of inspection, and who presents appropriate credentials, nor shall any person
obstruct, hamper, or interfere with any such representative while in the process of carrying
out his official duties. Refusal of entry or access may constitute grounds for permit
revocation and assessment of civil penalties.
13. In accordance with G.S. 143-215.108(c)(1),this permit does not relieve the Permittee of the
responsibility of complying with any applicable Federal, State, or Local requirements
governing the handling, disposal, or incineration of hazardous, solid, or medical wastes,
including the Resource Conservation and Recovery Act(RCRA) administered by the
Division of Waste Management.
14. PERMIT RETENTION REQUIREMENT- In accordance with 15A NCAC 2Q .0110,the
Permittee shall retain a current copy of the air permit at the site. The Permittee must make
available to personnel of the DAQ, upon request,the current copy of the air permit for the
site.
Permit No. 03577RI9
Page 13
15. CLEAN AIR ACT SECTION 112(r)REQUIREMENTS -Pursuant to 15A NCAC 2D .2100
"Risk Management Program," if the Permittee is required to develop and register a risk
management plan pursuant to Section 112(r) of the Federal Clean Air Act, then the
Permittee is required to register this plan with the USEPA in accordance with 40 CFR Part
68.
16. PREVENTION OF ACCIDENTAL RELEASES - GENERAL DUTY- Pursuant to Title I
Part A Section 112(r)(1) of the Clean Air Act "Hazardous Air Pollutants -Prevention of
Accidental Releases - Purpose and General Duty," although a risk management plan may not
be required, if the Permittee produces, processes, handles,or stores any amount of a listed
hazardous substance, the Permittee has a general duty to take such steps as are necessary to
prevent the accidental release of such substance and to minimize the consequences of any
release. This condition is federally-enforceable only.
17. GENERAL EMISSIONS TESTING AND REPORTING REQUIREMENTS - If emissions
testing is required by this permit, or the DAQ, or if the Permittee submits emissions testing
to the DAQ in support of a permit application or to demonstrate compliance,the Permittee
shall perform such testing in accordance with 15A NCAC 2D .2600 and follow all DAQ
procedures including protocol approval,regional notification,report submittal, and test
results approval. Additionally, in accordance with 15A NCAC 2D .0605,the permittee shall
follow the procedures for obtaining any required audit sample and reporting those results.
Permit issued this the 2nd of October,2018.
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
Heather Carter
Regional Supervisor
By Authority of the Environmental Management Commission
Air Permit No. 03577R19
ATTACHMENT to Permit No. 03577R19, October 2, 2018
Insignificant/Exempt Activities
i
. . _.._... - .._......_...._ ......_......_........................... .__ ..
I-SD1 and I-SD2
2Q .0102 (h)(5) € No Yes
Two steam heated slasher dryers
I-DFM
[ D e and finish mixing room 2Q .0102 {h)(5) Yes Yes
E Y g i
1. Because an activity is exempted from being required to have a permit or permit modification
does not mean that the activity is exempted from an applicable requirement or that the owner
or operator of the source is exempted from demonstrating compliance with any applicable
requirement.
2. When applicable, emissions from stationary source activities identified above shall be
included in determining compliance with the permit requirements for toxic air pollutants
under 15A NCAC 2D .1100 "Control of Toxic Air Pollutants" or 2Q .0711 "Emission Rates
Requiring a Permit."
3. Sample permit conditions showing the regulatory requirements for exempt sources subject to
NESHAP,NSPS, and NCAC rules may be found here:
https://deq.ne.gov/about/divisions/air-quality/air-quali ty_pertnits/specific-permit-conditions-
regulatory-guide