November 21,2019
Mr.Brian Connor
Avoca,LLC
841 Avoca Farm Road
Merry Hill,NC 27957
Subject: Avoca Incorporated
Merry Hill,Bertie County,North Carolina
Facility ID 0800044,Permit No. 01819T53
Proposed Particulate Matter, Hydrogen Chloride,Carbon Monoxide and Mercury
Emissions Testing of Biomass Boilers ES-BB 1 and ES-BB2
By McHale Emissions Measurement Services(EMS),December 2019
DAQ Tracking No. 2019-311 ST
Dear Mr. Connor:
The North Carolina Division of Air Quality(DAQ)has reviewed the protocol submittal form(PSF)for
the emissions testing of biomass boilers ES-BB 1 and ES-BB2. McHale EMS has proposed
EPA Method 5 for particulate matter(PM), EPA Method 26A for hydrogen chloride(HCl),EPA
Method 10 for carbon monoxide(CO), and EPA Method 30B for mercury(Hg). The proposed testing is
acceptable for demonstrating compliance with the applicable regulations.
ES-BB 1 and ES-BB2 are two biomass/bio-based solids-fired boilers(24 million Btu per hour maximum
permitted heat input rate each)controlled by bagfilter CD-BB1BH. 15A NCAC 2D .0503 Particulates
From Fuel Burning Indirect Heat Exchangers and 40 CFR 63 Subpart DDDDD National Emissions
Standards for Hazardous Air Pollutants for Industrial, Commercial, and Institutional Boilers and Process
Heaters apply to the biomass boilers. The emissions limits and regulations are shown in the table below.
Pollutant EPA Test Method Emission Limit' Re ulation
Filterable PM 5 0.33 lb/mmBtu 2D.0503
0.0301b/mmBtu
HCl 26A 0.0221b/mmBtu
CO 10 620 ppmvd@3%O2 63 Subpart DDDDD
3-run average)
H 30B 8.0E-071b/mmBtu
' lb/mmBtu=pounds per million Btu;ppmvd@3%02=parts per million by volume dry at 3%oxygen
M26A requires an audit sample be present during sampling for inspection if commercially available.
However, since provider does not meet the requirement,NC DAQ continues to recommend obtaining an
audit sample to support the data generated during a compliance test.
E
NORTH CnROLIN� f
North Carolina Department of Environmental Quality I Division of Air Quality
217 West Jones Street 1 1641 Mail Service Center I Raleigh,North Carolina 27699-1641
919.707.8400
Mr.Brian Connor
Page 2
DAQ Tracking No. 2019-311 ST
The proposed testing is acceptable for demonstrating compliance with the applicable regulations.
Approval of the proposed methods does not exempt the tester from the minimum requirements of the
applicable test methods. Any deviations from the applicable methods remain subject to approval by
DAQ. If there are any questions regarding this review,please contact me at(919)707-8427 or
Brent.Hall(u)ncdenr. ov.
Sincerely, p�
rent W. Hall
Special Projects Engineer
Cc: Michael Dickerson,McHale EMS Robert Fisher,WARO
Central Files,Bertie County IBEAM Documents-0800044