HomeMy WebLinkAboutAQ_F_1900134_20200127_CMPL_AltTMRR Y n ROY COOPER NORTH CAROLINA Governor Environmental Quality MICHAEL S.REGAN Secretary MICHAEL ABRACZINSKAS January 27, 2020 Director Ms. Cynthia Winston, P.E. Manager, Carolinas Permitting and Compliance Duke Energy,NCRH 15 410 S. Wilmington Street Raleigh,NC 27601-1849 Subject: Approval of Sulfur Dioxide Continuous Emissions Monitoring Systems Use of Diluent Cap During Periods of Start-up and Shutdown on Ash Beneficiation—STAR®Process Reference: Buck Combined Cycle Facility, Permit No. 03786T,Facility No. 8000004 H.F. Lee Steam Electric Plant, Permit No. 01812T,Facility No. 9600017 Cape Fear STAR Facility, Permit No. 10583R, Facility No. 1900134 Dear Ms. Winston: Your letter of June 6, 2019, to Gary Saunders, requested approval for the usage of a sulfur dioxide(S02) continuous emissions monitoring systems(CEMS) diluent cap during periods of startup and shutdown on the fly ash beneficiation staged turbulent air reactor (STAR®)process. The S02 CEMS will be used to determine compliance with the 2.3 lb/mmBtu emission standard in 15A NCAC 2D .0516—Sulfur Dioxide Emissions from Combustion Sources. The CEMS measures S02 concentration(ppm)that is used in conjunction with an Fc-factor(scf CO2/mmBtu) and diluent concentration(%)to convert measurements to units of the standard(lb/mmBtu). Diluent concentration is used in the denominator of the conversion equation and approaches zero during periods of startup and shutdown thereby causing nonrepresentative pollutant emission results. Based on our review, and in conjunction with our authority under 15A NCAC 2D .0606(g), the Division of Air Quality approves your request to revise the above-referenced permits to include a diluent cap; however,we ask that you include the following footnote within the permit as indicated by an asterisk to read, "*The S02 monitored value subject to the 0.03 lb/mmBtu limit will have a 5% CO2 diluent cap, or a 14%02 diluent cap, substituted in the emission rate calculation whenever the actual CO2 concentration is lower than 5%or whenever the actual 02 concentration is higher than 14%." NfJR ,JAJL A OWb� North Carolina Department of Environmental Quality I Division of Air Quality 217 West Jones Street 11641 Mail Service Center I Raleigh.North Carolina 27699-1641 919.707.8400 Ms. Cynthia Winston January 27, 2020 Page 2 If you should have any questions,please contact Dennis Igboko at(919) 707-8410 or dennis.igboko@ncdenr.gov. Sincerely, 'Z/ d- Z�-w Stephen G. Hall, Chief Technical Services Section Division of Air Quality,NCDEQ SGH/ad c: Randy Wooten,Duke Energy Erin Wallace,Duke Energy Dan Markley, Duke Energy Geoff Russell, Duke Energy Todd Wilson, SEFA (e-copy) Gary Saunders, DAQ SSCB William Willets, DAQ Permits Central File: Rowan County,Wayne County, Chatham County IBEAM Documents, 8000004, 9600017, 1900134