Loading...
HomeMy WebLinkAboutAQ_F_0100010_20220419_ST_RvwMemo Department of Environmental Quality Division of Air Quality Winston-Salem Regional Office Phone (336) 776-9800 Fax (336) 776-9797 MEMORANDUM To: T. Ray Stewart Jr,P.E.,CPM,Regional Supervisor,DAQ-WSRO From: Thomas J. Gray, Stack Testing Coordinator,DAQ-WSRO Subject: Stericyle,Inc. Haw River,Alamance,North Carolina Facility ID 0100010,Permit No. 05896T25 Visible Emissions Testing of ES-01 &ES-02 Performed February 24,2022 by TRC Solutions Tracking No.2022-009ST The report of the subject testing has been reviewed. The testing was performed by Gabriel Duncan of TRC Solutions, in accordance with Air Permit No. 05896T25. The average visible emissions from the sources during the testing were demonstrated to be below the applicable standard. Both incinerators were operating at approximately 1700 pounds per hour charge rate during the testing. This rate is acceptable. The visible emissions limit as established in 15A NCAC 2D .1206 "Hospital, Medical and Infectious Waste Incinerators, " 15A NCAC 2D A 100 "Control of Toxic Air Pollutants, " and 40 CFR Part 62 Subpart HHH "Federal Plan Requirements for Hospital/Medical/Infectious Incinerators Constructed on or Before June 20, 1996" is 6% for a rolling 6-minute block average. The final results are provided below. Source Description Opacity Limit Maximum Opacity Average Opacity p % Observed dual chamber hospital,medical and infectious waste incinerator(HMIWI) firing natural gas(4.6 million Btu/hr 6 0 0 primary chamber burner and 6.0 million Btu/hr secondary chamber burner) ES-01 dual chamber hospital,medical and infectious waste incinerator(HMIWI) firing natural gas(4.6 million Btu/hr 6 0 0 primary chamber burner and 6.0 million Btu/hr secondary chamber burner) ES-02 Compliance is indicated.