HomeMy WebLinkAboutAQ_F_0100237_20220209_ST_ProtRvw �c STA7E ti
ROY COOPER
Governor
ELIZABETH S.BISER
Secretary
MICHAEL ABRACZINSKAS NORTH CAROLINA
Director Environmental Quality
February 9,2022
Kristie Hill
Canfor Southern Pine-Graham Plant
4408 Mount Herman Rock Creek Road
Graham,North Carolina 27253
Subject: Canfor Southern Pine-Graham Plant
Graham,Alamance County,North Carolina
Facility ID 0100237,Air Permit No. 06740T20
Particulate Matter and Carbon Monoxide Emissions Test Protocol for Boiler B-4
Submitted by TRC Environmental Corporation(TRC)
Proposed Test Date: March 9,2022
Tracking No. 2022-012st
Dear Ms.Hill:
The North Carolina Division of Air Quality(DAQ)has reviewed the protocol submittal form(PSF)for
the filterable particulate matter(PM)and carbon monoxide(CO)emissions testing of Boiler B-4. The
proposed test methods are acceptable as discussed below.
Emissions Source B-4 is a wood fuel-fired boiler controlled by two multiclones and an electrostatic
precipitator ESP-4. The maximum permitted heat input for B-4 is 57.6 million Btu per hour(mmBtu/hr).
The proposed heat input rate for testing is 51.8 mmBtu/hr.40 CFR 63 Subpart DDDDD National
Emissions Standards for Hazardous Air Pollutants for Major Sources:Industrial, Commercial and
Institutional Boilers and Process Heaters applies and limits filterable PM to 0.037 pounds per million Btu
(lb/mmBtu)and limits CO emissions to 15 parts per million corrected to 3%oxygen(ppm@3%02).
40 CFR 60 Subpart Dc Standards of Performance for Small Industrial-Commercial-Institutional Steam
Generating Units applies and limits filterable PM to 0.03 lb/mmBtu.
TRC proposes three 120-minute runs of EPA Method 5 for filterable PM and EPA Method 10 for CO.
The PSF indicates boiler/control parameters(such as steam flow/pressure,pressure drop,and continuous
opacity monitoring system opacity)will be monitored every 15 minutes throughout sampling. The
parametric data shall be averaged and reported with the final emissions results.
Approval of this protocol does not exempt the tester from the minimum requirements of the methods. Any
deviations remain subject to approval by DAQ.If you have any questions,please contact me at
shannon.vogel@ncdenr.gov or 919-707-8416.
Sincerely, y
U
Shannon Vogel,Environmental Engineer
kA4
Division of Air Quality,NCDEQ
cc: Ray Stewart,P.E. Winston Salem Regional Office IBEAM Documents- 0100237
Tyler Mills, TRC Environmental Corporation
D E
Q
'- North Carolina Department of Environmental Quality I Division of Air Quality
�J/}� 217 West Jones Street 1 1641 Mail Service Center I Raleigh,North Carolina 27699-1641
NORD!CAROLINA P
oepnM�ent of EnuMonmematQwhty� /'� 919.707.8400