Loading...
HomeMy WebLinkAboutAQ_F_0100237_20211213_ST_RvwMemo (4) DIVISION OF AIR QUALITY December 13, 2021 MEMORANDUM To: Ray Stewart,P.E.,Winston Salem Regional Office Supervisor From: Brent W. Hall, Stationary Source Compliance Branch(SSCB)XWX Subject: Canfor Southern Pine—Graham Plant Graham,Alamance County,North Carolina Facility ID 01-00237,Permit No. 06740T22 Filterable Particulate Matter Emissions Testing of Boiler B-3 By TRC Environmental Corporation on August 25,2021 DAQ Tracking No. 2021-206ST TRC Environmental Corporation(TRC)performed EPA Method 5 for filterable particulate matter(PM) emissions from boiler B-3. The emissions test results demonstrate compliance with the applicable regulations. Emission source B-3 is a wood fuel-fired boiler(28.7 million Btu per hour [mmBtu/hr] maximum heat input capacity controlled by two multicyclones(MC-3 and MC-3A) and an electrostatic precipitator(ESP-3). 40 CFR 63 Subpart DDDDD National Emissions Standards for Hazardous Air Pollutants for Industrial, Commercial, and Institutional Boilers and Process Heaters and 15A NCAC 2D .0504 Particulates from Woodburning Indirect Heat Exchangers apply. The emissions test results are shown in the table below. Pollutant Test Result' Emissions Limit Regulation Compliance 0.037 lb/mmBtu 63 Subpart DDDDD Filterable PM 0.0042 lb/mmBtu Yes 0.45 lb/mmBtu 2D .0504 ' lb/mmBtu=pounds per million Btu Boiler B-3 averaged 19.7 mmBtu/hr(69%of maximum)heat input during testing. The emissions test results demonstrate compliance with the applicable regulations. If there are any questions regarding this review, please contact me at(919)707-8427 or Brent.Hall anncdenr.gov. Cc: IBEAM Documents- 0100237