Loading...
HomeMy WebLinkAboutAQ_F_0400056_20221028_ST_RvwMemo_2021-313st DIVISION OF AIR QUALITY October 28, 2022 MEMORANDUM To: Heather Carter,Fayetteville Regional Office Supervisor From: James Hammond, Stationary Source Compliance Branch(SSCB) Subject: Piedmont Natural Gas Company—Wadesboro Compressor Station Wadesboro,Anson County,North Carolina Facility ID 0400056,Air Permit No. 10097T02 Nitrogen Oxides, Carbon Monoxide,and Volatile Organic Compounds Emissions Testing of Natural Gas-Fired Spark Ignition(SI)Emergency Generator EGO 1 By Mostardi Platt,May 10,2022 DAQ Tracking No. 2021-313st Mostardi Platt performed EPA Method 320 for nitrogen oxides(NOX),carbon monoxide(CO), and volatile organic compounds(VOC) emissions from emergency generator EGO1. The emissions test results demonstrate compliance with the applicable regulations. EGO is a four-stroke lean burn natural gas-fired emergency generator rated at a maximum of 880 horsepower(hp)/600 kW. 40 CFR 60 Subpart JJJJ Standards of Performance for Stationary Spark Ignition Internal Combustion Engines and 40 CFR 63 Subpart ZZZZ National Emission Standards for Hazardous Air Pollutants for Reciprocating Internal Combustion Engines (RICE) applies. 60 Subpart JJJJ establishes NO, CO, and VOC limits in parts per million by volume dry corrected to 15%oxygen (ppmvd@15%02). 60 Subpart JJJJ Table 1 specifies the limits for emergency engines>130 hp. The emissions test results and limits are shown in the following table. Pollutant Test Result Emission Limit Regulation Compliance NOX 93 mvd 15%O2 160 ppmvd@ 15%02 CO 179 mvd 15%O2 540 ppmvd@ 15%02 60 Subpart JJJJ VOC as Propane 9 ppmvd@15%02 86 ppmvd@15%02 63 Subpart ZZZZ Yes C3Hg The generator is rated at 600 kW,maximum output. During testing the generator averaged 563 kW, or 94% of maximum. The test results demonstrate compliance with the applicable regulations. If there are questions regarding this review,please contact me at james.hammond@ncdenr.gov or(919)707-8412. cc: Laserfiche documents 0400056