HomeMy WebLinkAboutAQ_F_1100542_20201006_ST_RvwLtr ' L
ROY COOPER dwa s 11JDSyZ- 7 41,4v
Governor
MICHAEL S.REGAN
Secretary
MICHAEL A.ABRACZINSKAS NORTH CAROLINA
Director Environmental Quality
October 6,2020
Mr. Dane Pederson
Buncombe County Solid Waste Director
Buncombe County Landfill IT
81 Panther Branch Road
Alexander,NC 28701
SUBJECT: Stack Test Report
Buncombe County Landfill II
Alexander,North Carolina
Buncombe County
Air Permit Number 10398T02
Facility ID: 01/11/00542
Fee Class: Title V
Tracking No.: 2019-021 ST
Dear Mr. Pederson:
The Division of Air Quality has reviewed and deemed acceptable the results from the EPA
Method 25A for VOC, Method M7E for NOx, and Method 10 for CO emissions testing recently
performed on the landfill gas-fired engine/generator set ES-G1 (SN: 1021619). GEL Engineering,
LLC performed these tests on March 26, 2020. These tests satisfy the testing requirements as
stated in the subject permit. If you have any questions regarding this matter,please do not hesitate
to contact Mr. Chris Scott or me at(828)296-4500.
Sincerely,
Richard Morris
Environmental Specialist
Enclosure
North Carolina Department of Environmental Quality I Division of Air Quality
D E Q."Asheville Regional Office [2090 U.S.Highway 70 1 Swannanoa,NC 28778
or.�mvca fflbru
mmrt,.m.umm� 828.298.4500 T 1 828.299.7043 F
Buncombe County
DIVISION OF AIR QUALITY
Technical Services Section
October 1, 2020
MEMORANDUM
To: Brendan Davey, RE, Asheville Regional Office
From: Gregg O'Neal, P.E., Stationary Source Compliance Branch (SSCB)
Subject: Buncombe County Landfill II
Alexander, Buncombe County, North Carolina
Facility ID 1100542, Air Permit No. 10398T02
Nitrogen Oxides, Carbon Monoxide, and Volatile Organic Compounds
Emissions Testing of Landfill Gas-fired Engine/Generator Set ES-GI (SN: 1021619)
Performed March 26, 2020, by GEL Engineering, LLC
Tracking No. 2020-021ST
GEL Engineering performed the subject testing on the Jenbacher (Model J-420 GS-B82,
Manufactured 2011) landfill gas-fired spark ignition generator unit (1,466 kW,
1,966 horsepower), ES-G1. SSCB has reviewed the testing and the results are acceptable.
40 CFR 63 Subpart ZZZZ National Emission Standards for Hazardous Air Pollutants for
Reciprocating Internal Combustion Engines (RICE) requires that the facility comply with
40 CFR 60 Subpart JJJJ Standards of Performance for Stationary Spark Ignition Internal
Combustion Engines.
Permit condition 2.1.B.5.a establishes State BACT, as defined in North Carolina General Statute
62-133.8(g) Renewable Energy and Energy Efficiency Portfolio Standard(REPS). According to
the current permit the State BACT emission limits for CO and NO. resulting from biomass
combustion are the same as the 40 CFR 60 Subpart JJJJ limits.
Im.mismim I=
0.96 g/HP-hr 2.0 g/HP-hr State BACT
NO, M7E 75.7 ppmvd@15%02 (or 150 ppmvd@15% 02) 60 Subpart JJJJ Indicated
1,351 kW - State BACT
(92%of c0 M10 2.3 g/HP-hr 5.0 g/HP-hr Indicated
Maximum) 303 ppmvd@15%02 (or 610 ppmvd@15% 02) 60 Subpart JJJJ
voc* M25A 0.07 g/HP-hr 1.0 g/HP-hro 60 Subpart JJJJ Indicated
5.7 ppmvd@15% 02 (or 80 ppmvd@15/o 02)
*VOC as non-methane organic compounds as propane(NMOC as C31-1e).
Compliance was indicated. Subsequent performance tests must be conducted every 8,760
hours or 3 years, whichever comes first. If there are any questions concerning this matter,
please contact me at (919) 707-8415 or gregg.oneal(a ricdenr.gov.
cc: Central Files, Buncombe County
IBEAM Documents - 1100542