HomeMy WebLinkAboutAQ_F_1000067_20201010_CEM_RptRvwLtr �t„c STATE`u�
f�4+.wN�N
ROY COOPER NORTH CAROLINA
Governor Environmental Quality
MICHAEL S.REGAN
Secretary
MICHAEL ABRACZINSKAS
Director
October 20, 2020
Mr. Frank Hayward
Plant Manager
Capital Power Corporation
P.O. Box 10836
1281 Powerhouse Drive SE
Southport,North Carolina 28461
SUBJECT: 2ND Quarter 2020 Annual Relative Accuracy Test Audit (RATA) Report
Air Permit No. 05884T21
Facility I.D. No. 1000067
Dear Mr. Hayward,
The Division of Air Quality(DAQ)has reviewed the subject reports (RATA) submitted by The
Capital Power Corporation in a letter dated August 6, 2020. The reports were submitted for the
Continuous Emission Monitoring System(GEMS) on Unit 1 and Unit 2, each consisting of three
Boilers with the common stack.
DAQ's review of the above-mentioned reports indicated that the relative accuracy values for the
NOX,SOz, CO CEMS and flow monitor on Unit 1 and Unit 2 are within the specifications given in
40 CFR 60 Appendix F, and therefore the test (RATA) results are acceptable.
The review of the report also indicated that the relative accuracy value in lbs/hr was determined
using fuel heat input methodology. Please note, our e-mail dated March 2, 2018 states: To
determine the relative accuracy value in lbs/hr, the gas RATA should be conducted
simultaneously with the corresponding flow RATA. Please ensure that future RATAs meet this
requirement and use volumetric flow rate instead of fuel heat input to calculate the relative
accuracy value in lbs/hr.
The next annual RATA for the CEMS on Unit 1 and Unit 2 for the Part 60 purposes should be
conducted by June 30, 2021.
Due to COVID-19 restrictions on DAQ staff and our office operations, the mailing of this letter
may be delayed. In the meantime, an electronic copy(e-copy) is being provided for your records.
ORROLA
De ,O.MuI F�WrmmeMel OLWTY
North Carolina Department of Environmental Quality 1 Division of Air Quality
217 West Jones Street 1 1641 Mail Service Center 1 Raleigh,North Carolina 27699-1641
919.707.8400
Mr. Francis Hayward
October 20, 2020
Page 2
If you should have any questions, please contact me at (919) 707-8409 or
samir.parekh(&ncdenr.gov.
Sincerely,
Samir Parekh, P.E., Environmental Engineer
Division of Air Quality, NCDENR
cc: Gary Saunders
Brad Newland—WiRO (e-copy)
IBEAM—Documents— 1000067 (e-copy)
Central File—Brunswick Co.