Loading...
HomeMy WebLinkAboutAQ_F_1000067_20190509_ST_ProtRvw (5) ROY COOPER NORTH CAROLINA Governor Environmental Quality MICHAEL S.REGAN Secretary MICHAEL ABRACZINSKAS Director May 9, 2019 Ms. Ginny Grace Senior Advisor,Environment Capital Power Corporation 1281 Powerhouse Drive SE Southport,NC 28461 Subject: CPI USA North Carolina—Southport Plant Southport,Brunswick County,North Carolina Facility ID 1000067,Air Permit No. 05884T21 Proposed Particulate Matter,Hydrogen Chloride,and Mercury Emissions Testing Of Unit 1 and Unit 2 Boilers By Grace Consulting,Inc, Proposed week of June 24,2019 DAQ Tracking No. 2019-134ST Dear Ms. Grace: The North Carolina Division of Air Quality(DAQ)has reviewed the protocol submittal form(PSF)for particulate matter PM),hydrogen chloride(HCl),and mercury(Hg)emissions testing of ES-1 (Unit 1) and ES-2 (Unit 2). Grace Consulting,Inc. (GCI)proposes EPA Method 5 for filterable PM,EPA Method 26A for HCl, and EPA Method 30B for Hg. The proposed testing is acceptable to demonstrate compliance with the applicable regulations. ES-1 (ES-14A throughlC)and ES-2(ES-2-2A through 2C)are two electricity generating units consisting of six identical watertube design coal/natural gas/No.2 and No.4 fuel oil/tire derived fuel/pelletized paper fuel/flyash briquette/unadulterated wood/unadulterated biomass/adulterated resinated wood/creosote treated wood-fired steam,electric generating boilers. Each boiler is controlled by a bagfilter,rotating overfire air, furnace sorbent injection, and selective non-catalytic reduction systems. The permitted nominal heat input is 223 million Btu per hour(mmBtu/hr)for each boiler. The following regulations apply: • 40 CFR 60 Subpart Db Standards of Performance for Industrial-Commercial-Institutional Steam Generating Units(PM-filterable only) • 15A NCAC 2D .0501(c) Compliance with Emissions Control Standards(PMio) • 15A NCAC 2D .0530 Prevention of Significant Deterioration (PSD) [PM] • 15A NCAC 02D .0530(u)PSD Projected Actual Emissions(PM/PMIo) • 15A NCAC 02D .0614 Compliance Assurance Monitoring • 15A NCAC 2D .1109, 1120)Case-by-Case MACT(PM,Hg,HCl)through May 19,2019 North Carolina Department of Environmental Quality I Division of Air Quality 217 West Jones Street 11641 Mail Service Center I Raleigh,North Carolina 27699-1641 919.707,8400 Ms. Ginny Grace Page 2 DAQ Tracking No. 2019-134ST • 40 CFR 63 Subpart DDDDD National Emission Standards for Hazardous Air Pollutants for Major Sources:Industrial, Commercial, and Institutional Boilers and Process Heaters starting May 20, 2019 • NCGS 62-133.8(g)Senate Bill 3(SB3)State Best Available Control Technology(BACT) [PMIo/PM2.5,Hg] A summary of the test methods and emission limits is shown in the table below. Pollutant Test Method Emission Limit Regulation 0.051 lb/mmBtul 60 Subpart Db 6.02 lb/hr' 2D .0501 c 0.027 lb/mmBtu' 2D .0530 Filterable PM EPA Method 5 0.0184 lb/mmBtu 2D .053 u 0.18 lb/mmBtu2 1120)Case-by-Case MACT 0.0371b/mmBtu3 HCl EPA Method 26A 0.022 lb/mmBtu 63 Subpart DDDDD Hg EPA Method 30B 5.7E-06 lb/mmBtu I Emission limit is per boiler 2 Limit is in effect through May 19,2019 3 Limit starts May 20,2019 The PSF indicates"normal operating load"as target process operating rate. Based on the previous test conducted August 2018, ES-1 averaged 194.5 mmBtu/hr heat input per boiler and ES-2 averaged 198.5 mmBtu/hr per boiler. The final test report should indicate similar operating rates. An HCl audit sample is required for the EPA Method 26A testing and the sample should be available for inspection. The proposed testing is acceptable to demonstrate compliance with the applicable regulations. Approval of the protocol does not exempt the tester from the minimum requirements of the test methods. Any deviations from the methods remain subject to approval by DAQ. If you have any questions regarding this review,please contact me at(919)707-8427 or Brent.Hall ncdenr. ov. Sincerely, Brent W.Hall Special Projects Engineer Cc: Darryl Christy,P.E., GCI Brad Newland,WIRO Central Files,Brunswick County IBEAM Documents- 1000067