HomeMy WebLinkAboutAQ_F_1000067_20180723_ST_ProtRvw 74 1
ROY COOPER NORTH CAROLINA
Governor Environmental Quality
MICHAEL S.REGAN
Secretory
MICHAEL ABRACZINSKAS July 23,2018
Director
Virginia Grace
Capital Power Corporation
1281 Powerhouse Drive SE
Southport,North Carolina 28461
Subject: CPI USA North Carolina—Southport Plant
Southport, Brunswick County,North Carolina
Facility ID 1000067, Permit No. 05884T21
112j Case-by-Case MACT Emissions Testing for Boilers Unit 1 and Unit 2
Submitted by Grace Consulting, Inc.
Proposed Test Date: Week of August 13, 2018
Tracking No. 2018-173st
Dear Ms. Grace:
The North Carolina Division of Air Quality(DAQ)has reviewed the protocol submittal form
(PSF) for the testing of the ES-1 and ES-2 boilers. The proposed testing is acceptable to
determine the particulate (PM),particulate matter less than 10 microns(PM10),hydrogen
chloride(HCl), and mercury(Hg) emissions for 112j Case-by-Case Maximum Achievable
Control Technology(MACT) compliance purposes.
The sources to be tested are ES-1 (Unit 1) and ES-2 (Unit 2). Unit 1 and Unit 2 are two
electricity generating units each consisting of three coal/natural gas/No. 2 and No. 4 fuel oil/tire
derived fuel (TDF)/pelletized paper fuel/flyash briquette/unadulterated wood/unadulterated
biomass/adulterated resinated woo&creosote treated wood-fired steam, electric generating
boilers, ES-14A, ES-14B and ES-14C (Unit 1) and ES-24A, ES-24B and ES-24C (Unit 2).
The permitted nominal boiler heat input is 223 million Btu per hour, each. Each boiler is
controlled by a bagfilter, a rotating overfire air system, a furnace sorbent injection system, and a
selective non-catalytic reduction system.
Grace Consulting has proposed the test methods as outlined in Table 1 to demonstrate
compliance with the applicable emissions standards and limitations as detailed in Table 2.
Table 1: Unit 1 Boilers and Unit 2 Boilers-Tracking No. 2018-173st
Pollutant Methods Run Duration #of Sampling Runs
Filterable PM EPA 5 60 minutes 3
HCl EPA 26A 120 minutes 3
Hg EPA 30B 60 minutes 3 spiked/3 uns iked
PM10 EPA 201A/202 90 minutes 3
Filterable&Condensible
Ngarnl�oLi�1� 10)
arFmW
North Carolina Department of Environmental Quality I Division of Air Quality
217 West Jones Street 11641 Mail Service Center I Raleigh,North Carolina 27699-1641
919.707.8400
Virginia Grace
July 23, 2018
Tracking No. 2018-173st
Page 2
Table 2: Applicable Regulations and Emissions Limits
A licable Regulation Pollutant Limits
40 CFR 60 Subpart Db Standards of Performance
for Industrial-Commercial-Institutional Steam PM(filterable only) 0.051 lb/mmBtu
Generating Units
15A NCAC 2D .0501(c) Compliance with PMIO 6.02 lb/hr per boiler
Emissions Control Standards
15A NCAC 2D .0530 Prevention of Significant PM 0.0271b/mmBtu
Deterioration PSD
15A NCAC 02D .0530(u)PSD Projected Actual PM 0.0184 lb/mmBtu
Emissions PMIo 0.0184 lb/mmBtu
PM filterable only) 0.18 lb/million Btu
15A NCAC 2D.1109 Mercury: 0.0000051b/million Btu
112(j) Case-by-Case MACT Hydrogen Chloride 0.021b/million Btu
NCGS 62-133.8(g)Senate Bill 3 (SB3)State PMI0/PM2.5 0.027 lb/mmBtu
Best Available Control Technology(BACT) Mercury 5.00 E-6 Ib/mmBtu
CPI proposes operating the six boilers at"normal operating load" during testing. Current
operation is 360,000 to 500,000 pounds of steam per hour. The proposed fuel mix for testing is
coal (10%-15%), TDF (35%-40%) and wood(45%-50%). The proposed test methods and
conditions are acceptable. The PSF indicates that the required audit sample analyses will be
performed in conjunction with the proposed testing. The audit sample must be on-site and
available for inspection by the DAQ observer. For additional audit information see
www.epa.gov/emc/emc-technical-supportftaudit.
Approval of this sampling protocol does not exempt the tester from minimum requirements of
the test methods. Any deviations remain subject to approval by DAQ. If you have any
questions,please contact me at 919-707-8416 or shannon.vo el ncdenr.�g�ov.
Sincerely, Yrom-nental
ShannonVogel, Engineer
Division of Air Quality,NC DEQ
cc: Central Files, Brunswick County
IBEAM Documents- 1000067
Darryl Christy, P.E., Q.I., Grace Consulting
Brad Newland,Wilmington Regional Office