HomeMy WebLinkAboutAQ_F_1000067_20150807_CEM_RptRvwLtr AT
A+��
WDERR
North Carolina Department of Environment and Natural Resources
Pat McCrory Donald R. van der Vaart
Governor
Secretary
August 7, 2015
Mr. David H. Groves
Plant Manager
Capital Power Corporation
P.O. Box 10836
1281 Powerhouse Drive SE
Southport,North Carolina 28461
SUBJECT: Certification report for NOx Continuous Emission Monitoring System (CEMS)on
Unit 1 and Unit 2
Air Permit No. 05884T17
Facility ID: 1000067
Dear Mr. Groves,
The Division of Air Quality(DAQ) has reviewed the subject report submitted by The Capital
Power Corporation in a letter dated June 22,2015. The reports were submitted for the
Continuous Emission Monitoring System(CEMS) on Unit 1 and Unit 2, each consisting of three
Boilers with the common stack.
The purpose of the report was to request a certification of the following NOx, and CO2 CEMS
operating on Unit 1 and Unit 2.
Source ID Parameter Model Serial No. Manufacturer
Unit 1 NOx 42C 71812369 Thermo Environmental Scientific
CO2 41 CHL 71589369 Thermo Environmental Scientific
Unit 2 NOx 42C 71830369 Thermo Environmental Scientific
CO2 41CHL 71588369 Thermo Environmental Scientific
The certification report included a relative accuracy test audit(RATA) conducted on May 21 and
22, 2015 and the 7-day drift test performed from May 28, 2015 through June 3, 2015. Since the
NOx, and CO2 CEMS appear to have met the requirements of 40 CFR 60, Appendix B,
Performance Specification(PS) 2, and 3 respectively, the NOx CEMS on Unit 1 and Unit 2 are
certified effectively June 3, 2015.
The reports also indicated that the relative accuracy values for the SO2, CO CEMS and flow
monitor on Unit 1 and Unit 2 are within the specifications given in 40 CFR 60 Appendix F, and
therefore the test(RATA)results are acceptable.
1641 Mail Service Center,Raleigh,North Carolina 27699-1641
Phone:919-707-8400 4 Internet:www.ncdenr.gov
An Equal Opportunity l Affirmative Action Employer-Made in part by recycled paper
Mr. David H. Groves
August 7, 2015
Page 2
The next annual RATA for the CEMS and flow monitor on Unit 1 and Unit 2 should be
conducted by June 30, 2016.
If you have any questions, please contact me at (919) 707-8409 or samir.parekh ymcdenr.g_ov.
Sincerely,
Samir Parekh, P.E., Environmental Engineer
Division of Air Quality, NCDENR
cc: Michael Pjetraj
Brad Newland—WiRO
Central File—Brunswick Co.
IBEAM—Documents— 1000067