HomeMy WebLinkAboutAQ_F_1000067_20131125_PRMT_Permit i
i
w�
CCDEENR
North Carolina Department of Environment and Natural Resources
Division of Air Quality j
Pat McCrory Sheila C. Holman John E. Skvarla, III
Governor Director Secretary
November 25, 2013
Mr. David H. Groves
I
Plant Manager
CPI USA North Carolina—Southport Plant
1281 Powerhouse Drive j
Southport,NC 28461
SUBJECT: Air Quality Permit No. 05884T14
i
Facility ID: 1000067
CPI USA North Carolina—Southport Plant
Southport, North Carolina
Brunswick County
Fee Class: Title V
Dear Mr. Groves:
In accordance with your completed Air Quality Permit Application for a minor modification
of your Title V permit received September 19, 2013, we are forwarding herewith Air Quality Permit
No. 05884T14 to CPI USA North Carolina — Southport Plant, 1281 Powerhouse Drive SE,
Southport, North Carolina, authorizing the construction and operation of the emission source(s) and
associated air pollution control device(s) specified herein. Additionally, any emissions activities
determined from your Air Quality Permit Application as being insignificant per 15A North Carolina
Administrative Code 2Q .0503(8) have been listed for informational purposes as an
"ATTACHMENT." Please note the requirements for the annual compliance certification are
contained in General Condition P in Section 3. The current owner is responsible for submitting a
compliance certification for the entire year regardless of who owned the facility during the year.
As the designated responsible official it is your responsibility to review, understand, and
abide by all of the terms and conditions of the attached permit. It is also your responsibility to
ensure that any person who operates any emission source and associated air pollution control device
subject to any term or condition of the attached permit reviews, understands, and abides by the
conditions of the attached permit that are applicable to that particular emission source.
The changes noted in the 1120) case-by-case MACT section of the air permit are listed as a
minor modification per 15A NCAC 2Q .0515. The compliance certification as described in General
Condition P is required. Unless otherwise notified by NC DAQ, the affected terms of this permit
(excluding the permit shield as described General Condition R) for this source shall become final on
Permitting Section
1641 Mail Service Center,Raleigh,North Carolina 27699-1641
217 West Jones Street,Raleigh,North Carolina 27603
Phone:919-707-8405/Fax:919-715-0717
Internet:www.ncair.org
An Equal Opportunity\Affirmative Action Employer—Made in part by Recycled Paper
Mr. David H. Groves
November 25, 2013
Page 2
January 24, 2014. Until this date, the affected permit terms herein reflect the proposed operating
language that the Permitee shall operate this source under pursuant to 15A NCAC 2Q .0515(f).
If any parts, requirements, or limitations contained in this Air Quality Permit are
unacceptable to you, you have the right to request a formal adjudicatory hearing within 30 days
following receipt of this permit, identifying the specific issues to be contested. This hearing request
must be in the form of a written petition, conforming to NCGS (North Carolina General Statutes)
150B-23, and filed with both the Office of Administrative Hearings, 6714 Mail Service Center,
Raleigh,North Carolina 27699-6714 and the Division of Air Quality, Permitting Section, 1641 Mail
Service Center, Raleigh, North Carolina 27699-1641. The form for requesting a formal
adjudicatory hearing may be obtained upon request from the Office of Administrative Hearings.
Please note that this permit will be stayed in its entirety upon receipt of the request for a hearing.
Unless a request for a hearing is made pursuant to NCGS 150B-23, this Air Quality Permit shall be
final and binding 30 days after issuance.
You may request modification of your Air Quality Permit through informal means pursuant
to NCGS 150B-22. This request must be submitted in writing to the Director and must identify the
specific provisions or issues for which the modification is sought. Please note that this Air Quality
Permit will become final and binding regardless of a request for informal modification unless a
request for a hearing is also made under NCGS 150B-23.
The construction of new air pollution emission source(s) and associated air pollution control
device(s), or modifications to the emission source(s) and air pollution control device(s) described in
this permit must be covered under an Air Quality Permit issued by the Division of Air Quality prior
to construction unless the Permittee has fulfilled the requirements of GS 143-215-108A(b) and
received written approval from the Director of the Division of Air Quality to commence
construction. Failure to receive an Air Quality Permit or written approval prior to commencing
construction is a violation of GS 143-215.108A and may subject the Permiee to civil or criminal
penalties as described in GS 143-215.114A and 143-215.114B.
This Air Quality Permit shall be effective from November 25, 2013 until June 30, 2016, is
nontransferable to future owners and operators, and shall be subject to the conditions and limitations
as specified therein.
Should.you have any questions coZDo
this contact Brian Bland, at (919)
707-8732.
van der Vaart, Ph.D., J.D.,P.E.
Chief
Enclosure
cc: Heather Ceron,EPA Region 4 (electronic copy only)
Wilmington Regional Office
Central Files
ATTACHMENT
CPI USA North Carolina—Southport Plant
Insignificant Activities under 15A NCAC 2Q.0503(8)
Emission Source ID Emission Source Description
I-EFP One diesel fired 340 hp emergency fire pump
I-FOSTI One diesel fuel oil storage tank
I-FOST2 One fire pump fuel oil storage tank
I-SPC One solvent parts cleaner using hot water solution
containing no reportable HAPs
I-TLOT1 and I-TLOT2 Two turbine lube oil tanks
I-TS One tire shredder
I-1 Haul Roads
I-WHS Wood handling and storage
I-TDFHS TDF handling and storage
I-UREA S TK1 One urea storage tank
I-UREA D TK1 One urea dilution tank
I-10A and I-10B Two submerged drag chain systems for removal and
transport of bottom ash to storage pits
1. Because an activity is insignificant does not mean that the activity is exempted from an applicable requirement or
that the owner or operator of the source is exempted from demonstrating compliance with any applicable
requirement.
2. When applicable,emissions from stationary source activities identified above shall be included in determining
compliance with the permit requirements for toxic air pollutants under 15A NCAC 2D.1100"Control of Toxic
Air Pollutants"or 2Q.0711 "Emission Rates Requiring a Permit".
3. For additional information regarding the applicability of GACT see the DAQ page titled"The Regulatory Guide for
Insignificant Activities/Permits Exempt Activities".The link to this site is as follows:
hU:Hdag.state.nc.us/permits/insi�/
I
• I
i
II
ATTACHMENT
CPI USA North Carolina—Southport Plant
The following changes were made to the CPI USA North Carolina—Southport Plant Air Quality Permit No. 05884T13:
Page(s) Section Desc 1ption of Changes
1 Cover Page • Update permit revision numbers and permit/application dates
3 -end All,Header • Update permit revision number
6 2.1 A.Table • Replace individual fuel 1120)case-by-case MACT emission
standards with a single blended fuel standard in Limits/Standard
table
16 2.1 A.7.b • Replace individual fuel 1120)case-by-case MACT emission
standards with a single blended fuel standard
17 2.1 A.7.h • Change initial testing requirements to reflect a single blended fuel
emission standard
20 2.1 A.7.j • Clarify that this item applies only to mercury,hydrogen chloride
and particulate matter(filterable only)
• Add language to clarify testing requirements with regards to units
versus individual boilers
21-22 2.1 A.71 • Add language describing alternate monitoring method
• Change language to clarify that monitoring location is at the unit
level,not at each individual boiler
• Add statement that the 30-day rolling average for CO will begin
on November 29,2013,and the CO CEMS must be certified and
operable by that date
• Add Percent Monitor Downtime(%MD)requirement
25 2.1 A.7.x • Add January 31,2014 start date for semi-annual reports
25 2.1 A.7 • Add 15A NCAC 2Q.0515 language
i
i
State of North Carolina
Department of Environment • •
and Natural Resources
Division of Air Quality
NCDENR
AIR QUALITY PERMIT
Permit No. Re laces Permit No.(s) Effective Date Expiration Date
05884T14 05884TE November 25,2013 June 30, 2016
i
Until such time as this permit expires or is modified or revoked,the below named Permittee is permitted to construct and
operate the emission source(s)and associated air pollution control device(s)specified herein,in accordance with the terms,
conditions, and limitations within this permit. This permit is issued under the provisions of Article 21B of Chapter 143,
General Statutes of North Carolina as amended, and Title 15A North Carolina Administrative Codes (15A NCAC),
Subchapters 21)and 2Q,and other applicable Laws.
Pursuant to Title 15A NCAC,Subchapter 2Q, the Permittee shall not construct, operate,or modify any emission source(s)
or air pollution control device(s) without having first submitted a complete Air Quality Permit Application to the
permitting authority and received an Air Quality Permit,except as provided in this permit.
Permittee: CPI USA North Carolina - Southport Plant
Facility ID: 1000067
Facility Site Location: 1281 Powerhouse Drive SE
City, County, State, Zip: Southport,Brunswick County,North Carolina 28461
Mailing Address: P. O. Box 10836
City,State, Zip: Southport,North Carolina 28461
Application Number: 1000067.13D
Complete Application Date: November 20,2013
Primary SIC Codes: 4911
Division of Air Quality, Wilmington Regional Office
Regional Office Address: 127 Cardinal Drive Extension
Wilmington,North Carolina 28405
Pe t issued this the 25t ay of November, 2013.
ona R. van de aart, Ph.D., J.D., P.E., Chief, Air Permits Section
Autho ' the Environmental Management Commission
Table Of Contents
SECTION 1: PERMITTED EMISSION SOURCE(S)AND ASSOCIATED AIR POLLUTION
CONTROL DEVICE(S)AND APPURTENANCES
SECTION 2: SPECIFIC LIMITATIONS AND CONDITIONS
2.1 -Emission Sources Specific Limitations and Conditions
(Including specific requirements,testing, monitoring,record keeping, and
reporting requirements)
2.2 -Multiple Emissions Source(s) Specific Limitations and Conditions
(Including specific requirements,testing,monitoring,recordkeeping, and
reporting requirements)
2.3 -Clean Air Interstate Rule(CAIR)Permit Requirements
SECTION 3: GENERAL PERMIT CONDITIONS
ATTACHMENT
List of Acronyms
Clean Air Interstate Rule(CAIR)Application dated April 26,2011
I
i
i
i
Air Quality Permit No. 05884T14
Page 3
SECTION 1 - PERMITTED EMISSION SOURCE(S) AND ASSOCIATED
AIR POLLUTION CONTROL DEVICE(S) AND
APPURTENANCES
The following table contains a summary of all permitted emission sources and associated air pollution control devices
and appurtenances:
Emission Source ID Emission Source Description Control Device ID Control Device Description
No. No.
ES-1 (Unit 1)and Two electricity generating units CD-14A Six bagfilters(16,800 square
ES-2(Unit 2) consisting of: CD-14B feet of filter area,each)
(PSD;PSD CD-14C
Avoidance; Six watertube design coal/natural CD-24A
NSPS,Subpart Db; gas/No.2 and No.4 fuel oil/tire CD-24B
2D.1109 Case-by- derived fuel/pelletized paper CD-24C
Case MACT) fuel/flyash briquette/unadulterated
wood'/unadulterated CD-1-5A* Six rotating overfire air
biomass/adulterated resinated wood2- CD-1-5B* (ROFA)systems
fired steam,electric generating, CD-1-5C*
boilers(223 million Btu per hour heat CD-2-5A*
input capacity,each;ID Nos.ES-1- CD-2-5B*
1A,ES-1-113,ES-14C,ES-2-1A,ES- CD-2-5C*
2-113 and ES-2-1C)+
CD-1-6A* Six furnace sorbent injection
CD-1-6B* (FSI)systems
CD-1-6C*
CD-2-6A*
CD-2-6B*
CD-2-6C*
CD-1-7A* Six selective non-catalytic
CD-1-7B* reduction(SNCR)systems3
CD-1-7C*
CD-2-7A*
CD-2-7B*
CD-2-7C*
i
ES-2A through ES- Six coal bunkers CD-2A through Six bagfilters(161 square
2F CD-2F feet of filter area each,
(PSD) respectively)
ES-3A** and ES- Two flyash silos with dedicated wet CD-3A and CD-3B Two silo binvents(100
3B** slurry pugmills for unloading square feet of filter area,
(PSD) each),one located on each
silo
i
i
1 Unadulterated wood as defined per 15A NCAC 2Q .0703(23).
2 Resinated wood includes plywood,oriented-strand board,and manufactured word products such as laminated
beams,untreated wood pellets and lumber scraps that are not part of any construction and demolition.
3 The installation of selective non-catalytic reduction systems on each boiler is optional.
Air Quality Permit No.05884T14
Page 4
Emission Source ID Emission Source Description Control Device ID Control Device Description
No. No.
ES-4A through ES- Four ash system vacuum transport CD-4G and CD-4H Two simple cyclones(42
4D pumps inches in diameter)
(PSD)
CD-4E and CD-4F Two bagfilters(528 square
feet of filter area,each)
CD-4A through Four in-line filters(one per
CD-4D pump,respectively)
ES-5 One coal unloading/storage and Wetsup One wet
(PSD) transfer operation -suppression/chemical binder
system
ES-8A and ES-8B Two cooling towers(32,400 gallons None per minute recirculating water flow
rate each)
ES-9A*and ES-9B* Two alkaline sorbent(limestone,lime CD-9A* and Vent fabric filters(3.9:1 air-
or trona)silos(12,554 ft3 maximum CD-9B* to-cloth ratio each)
storage capacity each)
*The Permittee shall file a Title V Air Quality Permit Application pursuant to 15A NCAC 2Q.0504 for alkaline sorbent silos(ID Nos.ES-9A and
ES-913),vent fabric filters(ID Nos.CD-9A and CD-913),rotating overfire air(ROFA)systems(ID Nos.CD-1-5A,CD-1-513,CD-1-5C,CD-2-5A,
CD-2-5B and CD-2-5C),furnace sorbent injection(FSI)systems(ID Nos. CD-1-6A,CD-1-613,CD-1-6C,CD-2-6A,CD-2-6B and CD-2-6C),and
selective non-catalytic reduction (SNCR) systems (ID Nos. CD-1-7A, CD-1-7B, CD-14C, CD-2=7A, CD-2-713 and CD-2-7C) on or before 12
months after commencing operation.These emission sources (ID Nos.ES-SIL08,ES-PBTS1,ES-PBTS2,ES-PBTS3,and ES-DBA Load)and
control devices(ID Nos.CD-BF9,CD-BF-10,CD-BFll,and CD-131712)are listed as a 15A NCAC 2Q.0501(c)(2)modification. The Permittee
shall file a Title V Air Quality Permit Application on or before 12 months after commencing operation in accordance with General Condition NN.1.
The permit shield described in General Condition R does not apply and compliance certification as described in General Condition P is not required.
** These emissions sources (two wet slurry pugmills for flyash silos, ID Nos.ES-3A and ES-3B)are listed as a minor modification per 15A
NCAC 2Q .0515. The compliance certification as described in General Condition P is required. Unless otherwise notified by NC DAQ, the
affected terms of this permit(excluding the permit shield as described General Condition R)for this source shall become final on July 9,2012.
Until this date,the affected permit terms herein reflect the proposed operating language that the Permittee shall operate this source under pursuant
to 15A NCAC 2Q.0515(t).
'Burning of adulterated resinated wood in boilers(ID Nos.ES-1-1A,ES-1-113,ES-1-IC,ES-2-1A,ES-24B,and ES-24C)is listed as a 15A NCAC
2Q .0501(c)(2)modification. The Permittee shall file a Tide V Air Quality Permit Application on or before 12 months after commencement of
burning adulterated resinated wood in these boilers in accordance with General Condition NN.1. The permit shield described in General Condition
R does not apply and compliance certification as described in General Condition P is not required.
I
I
I
Air Quality Permit No. 05884T14
Page 5
SECTION 2 - SPECIFIC LIMITATIONS AND CONDITIONS
2.1 - Emission Source(s) and Control Devices(s) Specific Limitations and
Conditions
The emission source(s) and associated air pollution control device(s) and appurtenances listed below are subject to
the following specific terms, conditions, and limitations, including the testing, monitoring, record keeping, and
reporting requirements as specified herein:
A. Two electricity generating units consisting of-
-Six watertube design coal/natural gas/No.2 and No. 4 fuel oil/tire derived fuel/pelletized paper fuel/fiyash
briquette/unadulterated wood/unadulterated biomass/adulterated resinated wood-fired boilers (ID Nos.
ES-14A,ES-1-113,ES-14C,ES-24A,ES-2-113 and ES-2-1C),and associated bagfilters(iD Nos.CD-1-1A,
CD-1-113,CD-1-1C,CD-24A,CD-2-11]and CD-24C),rotating overfire air(ROFA)systems(ID Nos.CD-
MA, CD-1-513, CD-1-5C, CD-2-5A, CD-2-513 and CD-2-5C), furnace sorbent injection (FSI) systems (ID
Nos. CD-1-6A, CD-1-613, CD-1-6C, CD-2-6A, CD-2-613 and CD-2-6C) and selective non-catalytic
reduction(SNCR)systems(ID Nos.CD-1-7A,CD-1-713,CD-1-7C,CD-2-7A,CD-2-713 and CD-2-7C)
The following table provides a summary of limits and/or standards for the emission source(s)described above.
Regulated Pollutant Limits/Standards Applicable Regulation
Sulfur dioxide 2.3 pounds per million Btu heat input per boiler* 15A NCAC 2D .0516
Clean Air Interstate Rule(CAIR)Permit Requirements 15A NCAC 2D.2404
See Section 2.3
Particulate matter 0.05 pounds per million Btu heat input per boiler* 15A NCAC 2D .0524
(40 CFR 60, Subpart Db)
(60.43b(a)(1))
Opacity 20 percent(6-minute average)per common stack* 15A NCAC 2D .0524
(40 CFR 60, Subpart Db)
(60.43b(f))
Nitrogen oxide Coal-firing only 15A NCAC 213.0524
0.60 pounds per million Btu heat input per boiler* (40 CFR 60, Subpart Db)
(60.44b(a))
Nitrogen oxide Simultaneously burning coal with fuel oil or a mixture of 15A NCAC 213.0524
these fuels with natural gas or any other fuel(per boiler*): (40 CFR 60, Subpart Db)
(60.44b(c))
En=(0.1H90+0.311r0+0.6HJ/(Hgo+Ho+Ha)
Where:
En= nitrogen oxide emission limit(lbs/mmBtu)
Hgo= heat input from the combustion of natural gas or
distillate oil(mmBtu)
HIo= heat input from the combustion of residual oil
(mmBtu)
He= heat input from the combustion of coal(mmBtu)
Clean Air Interstate Rule(CAIR)Permit Requirements 15A NCAC 2D.2403 and
See Section 2.3 .2405
PMI0 6.02 pounds per hour per boiler* 15A NCAC 2D.050l(e)
Sulfur dioxide 327.8 pounds per hour per boiler* 15A NCAC 2D.0501(e)
Nitrogen oxide 120.4 pounds per hour per boiler* 15A NCAC 2D.0501(e)
Carbon monoxide 120.4 pounds per hour per boiler* 15A NCAC 2D .0501(e)
Particulate matter 0.027 pounds per million Btu heat input per boiler* 15A NCAC 2D .0530
Sulfur dioxide 1.47 pounds per million Btu heat input per boiler* 15A NCAC 2D .0530
Nitrogen oxide 0.54 pounds per million Btu heat input per boiler* 15A NCAC 2D .0530
Carbon monoxide 0.54 pounds per million Btu heat input per boiler* 15A NCAC 213.0530
i
Air Quality Permit No. 05884T14
Page 6
Regulated Pollutant Limits/Standards Applicable Regulation
Sulfuric acid mist 0.019 pounds per million Btu heat input per boiler* 15A NCAC 213.0530
PM,PMIo,NOx, As defined in specific conditions 15A NCAC 2D.0530(u)
SO2i CO,and VOC
Particulate matter Compliance Assurance Monitoring 15A NCAC 213.0614
Toxic air pollutants State-enforceable only 15A NCAC 2Q .0700
See Section 2.2 A.1.
Toxic air pollutants State-enforceable only 15A NCAC 2D.1100
See Section 2.2 A.2.
HAPs All fuel combinations,based on each of these boilers being 15A NCAC 2D.1109
a"unit designed to burn biomass/bio-based solid
subcategory"as defined in 40 CFR 63.7575:
Particulate Matter(filterable only): 0.18 lb/million Btu
• Mercury: 0.000005 lb/million Btu
• Hydrogen Chloride: 0.02 lb/million Btu
• Carbon Monoxide: 508 ppmvd,corrected to 7%02,30-
day rolling average
* Stack measured or calculated emissions represent the collective emissions for the six boilers(ID Nos.ES-1-1A,
ES-1-111,ES-1-IC,ES-24A,ES-2-111 and ES-24C)in the power units. "Per boiler"emissions are derived by
dividing the measured emissions by the boilers in operation during the timeframe specified. Compliance certification
on a per boiler basis is based on the common stack emissions performance divided by the boilers in operation at the
time of measurement per power unit.
1. 15A NCAC 2D.0516: SULFUR DIOXIDE EMISSIONS FROM COMBUSTION SOURCES
a. Emissions of sulfur dioxide from these sources(ID Nos.ES-1-IA,ES-14B,ES-1-IC,ES-24A,ES-2-111
and ES-2-IC)shall not exceed 2.3 pounds per million Btu heat input. Sulfur dioxide formed by the
combustion of sulfur in fuels,wastes,ores,and other substances shall be included when determining
compliance with this standard. [15A NCAC 2D.0516]
Testing[I5A NCAC 2Q .0508(f)]
b. If emissions testing is required,the testing shall be performed in accordance with General Condition JJ. If
the results of this test are above the limit given in Section 2.1 A.La above,the Permittee shall be deemed in
noncompliance with 15A NCAC 2D.0516.
Monitoring/Recordkeeping[15A NCAC 2Q .0508(f)]
c. To assure compliance,the Permittee shall monitor the sulfur content of the coal by using coal supplier
certification per total shipment received. The coal supplier certification shall be recorded in a logbook
(written or electronic format)per total shipment and include the following information:
i. the name of the coal supplier;
ii. the maximum sulfur content of the coal received per total shipment;
iii. a statement verifying that the methods used to determine the maximum sulfur content of the coal was in
accordance with the following:
A. sampling—ASTM Method D 2234;
B. preparation—ASTM Method D 2013;
C. gross calorific value(Btu)—ASTM Method D 5865;
D. moisture content—ASTM Method D 3173;and
E. sulfur content—ASTM Method D 3177 or ASTM Method D 4239.
The Permittee shall be deemed in noncompliance with 15A NCAC 2D.0516 if the sulfur content of the
coal is not monitored and recorded.
Upon certification of SO2 continuous emission monitoring(CEM)systems,the Permittee shall determine
Air Quality Permit No.05884T14
Page 7
compliance with S02 emission limit in Section 2.1 A.La. above,using S02 CEM instead of using coal
supplier certification. Monitoring and record keeping for S02 CEM shall be in accordance with 2.1 A.4.cc
below. If any 24-hour block average of S02 exceeds the emission limit per Section 2.1 A.La. above or the
records are not maintained,the Permittee shall be deemed in noncompliance with 15A NCAC 2D .0516.
Reporting[15A NCAC 2Q.0508(f)]
d. The Permittee shall submit a summary report of the coal supplier certifications postmarked on or before
January 30 of each calendar year for the preceding six-month period between July and December and July
30 of each calendar year for the preceding six-month period between January and June. Also,the Permittee
shall submit a certified statement signed by the responsible official that the records of coal supplier
certification submitted represent all of the coal fired during the reporting period. All instances of deviations
from the requirements of this permit must be clearly identified.
Upon certification of S02 CEM,the Permittee shall submit reports for S02 in pounds per million Btu in
accordance with Section 2.1 A.4.dd.and CC.
2. 15A NCAC 2D.0524: NEW SOURCE PERFORMANCE STANDARDS
a. The Permittee shall comply with all applicable provisions,including the testing,reporting,recordkeeping,
and monitoring requirements contained in Environmental Management Commission Standard 15A NCAC
2D .0524"New Source Performance Standards(NSPS)"as promulgated in 40 CFR Part 60 Subpart Db,
including Subpart A"General Provisions." [15A NCAC 2D.0524] ID Nos.ID Nos.ES-1-IA,ES-1-lB,
ES-1-1C,ES-2-1A,ES-2-1B and ES-2-1C
b. Testing[15A NCAC 2Q .0508(f)]
i. Before Modifyin or r Replacing Existing induced Draft Fans on Boilers (ID Nos. ID Nos. ES-1-IA,
ES-14B,ES-1-IC,ES-2-1A,ES-2-1B and ES-2-IC)
The Permittee shall conduct a performance test for particulate matter within 60 days of achieving the
maximum production rate at which the affected facility(ID Nos. ES-1-1A, ES-1-1B, ES-1-IC, ES-2-
1A,ES-2-1B and ES-2-IC)will be operated but no later than 180 days after the startup of the furnace
sorbent injection (FSI) systems on boilers (ID Nos. ID Nos. ES-1-IA, ES-1-1B, ES-1-IC, ES-2-1A,
ES-2-1B and ES-2-1C) in accordance with General Condition JJ found in Section 3. This testing shall
be used consistent with 40 CFR 60 Appendix C when the facility performs stack testing pursuant to
Section 2.1 A.2.b.ii.below.
Prior to modifying/replacing the induced draft fans on boilers (ID Nos. ES-1-IA, ES-1-1B, ES-14C,
ES-2-1A,ES-2-1B and ES-2-1C),the Permittee shall perform an engineering evaluation demonstrating
that the increase in flue gas flow rate will not increase the boiler's potential heat input rate when firing
100% coal, 50% coal/50% TDF, and 25% coal/50% TDF/25%wood, to greater than 250 million
Btu/hr. The Permittee shall submit the results of this engineering evaluation 60 days prior to
modification/replacement of the induced draft fans on these boilers.
ii. After Modifying or Replacing Existing Induced Draft Fans on Boilers(ID Nos.ES-1-IA,ES-1-1B,
ES-1-IC,ES-2-1A,ES-2-1B and ES-2-IC)
The Permittee shall conduct a performance test for particulate matter within 60 days of achieving the
maximum production rate at which the affected facility (ID Nos. ES-1-IA, ES-1-1B, ES-1-IC, ES-2-
1A, ES-2-1B and ES-2-1C) will be operated but no later than 180 days after the startup of the
modified/replaced induced draft fans on boilers(ID Nos.ES-14A,ES-1-1B,ES-1-IC,ES-2-1A,ES-2-
1B and ES-2-1C) in accordance with General Condition JJ found in Section 3. If the results of this
performance test, consistent with 40 CFR 60 Appendix C, demonstrate that increase in particulate
matter has occurred at boilers(ID Nos. ES-1-IA,ES-1-1B,ES-1-1 C,ES-2-1A,ES-2-1B and ES-2-IC)
or the above performance test is not conducted,the modified boilers(ID Nos. ID Nos.ES-1-1A,ES-1-
1B, ES-1-IC, ES-2-IA, ES-24B and ES-2-1C) are subject to the applicable requirements for
I
Air Quality Permit No. 05884T14
Page 8
particulate matter (category: boilers modified after February 28, 2005) in accordance with 40 CFR 60
Subpart Db.
Within 60 days of achieving the maximum production rate at which the affected facility(ID Nos.ES-1-
IA, ES-1-113, ES-14C, ES-24A, ES-2-113 and ES-24C) will be operated but no later than 180 days
after the startup of the modified/replaced induced draft fans on boilers (ID Nos. ES-1-IA, ES-1-113,
ES-1-IC, ES-24A,ES-2-113 and ES-2-IC),the Permittee shall determine, in accordance with General
Condition JJ found in Section 3,maximum heat input capacity for each boiler(ID Nos.ES-1-IA,ES-1-
113, ES-1-IC,ES-24A, ES-2-113 and ES-24C) when firing 100% coal, 50% coal/50%TDF and 25%
coal/50% TDF/25%wood, based upon a 4-hour averaging period at a maximum fan capacity. If this
demonstration indicates that the maximum heat input capacity exceeds 250 million But/hr for any
boiler, the boilers (ID Nos. ES-1-IA, ES-1-113, ES-1-IC, ES-2-IA, ES-2-113 and ES-2-IC) shall
become subject to the requirements in 40 CFR 60 Subpart Da.
Emission Limitations [15A NCAC 2D.0524]
c. Particulate matter—Particulate emissions from these sources(ID Nos.ES-14A,ES-14B,ES-14C,ES-
2-1A,ES-24B and ES-24C)shall not exceed 0.05 pounds per million Btu heat input when firing coal
with other fuels.
d. Nitrogen oxides—
i. Nitrogen oxides emissions when firing coal shall not exceed 0.60 pounds per million Btu heat input.
ii. Nitrogen oxides emissions from the simultaneous combustion of coal with fuel oil or a mixture of these
fuels with natural gas or any other fuel shall not be in excess of the rate calculated by the following
formula[40 CFR Part 60, Subpart 60.44b(c)]:
E„_(0.1Hg,,+0.3Hro+0.6H,)/(Hg,,+Hro+H,)
Where: E„=nitrogen oxide emission limit(lb/million Btu)
Hgo=heat input from combustion of natural gas or distillate oil(million Btu)
Hr.=heat input from the combustion of residual oil(million Btu)
H,=heat input from the combustion of coal(million Btu)
iii. Compliance with the nitrogen oxide emission limits is determined on a 30-day rolling average basis [40
CFR Part 60,Subpart 60.44b(i)].
e. Opacity—These sources(ID Nos.ES-14A,ES-1-113,ES-14C,ES-2-1A,ES-2-113 and ES-24C)shall
not cause to be discharged into the atmosphere any gases that exhibit greater than 20 percent opacity(six-
minute average)each,except for one six-minute period per hour of not more that 27 percent opacity.
Monitoring [15A NCAC 2Q.0508(f)]
f. 40 CFR 60.48b(a)—The Permittee shall calibrate,maintain,and operate a continuous monitoring system for
measuring the opacity of emissions discharged to the atmosphere and record the output of the system.
g. 40 CFR 60.48b(b)—The Permittee shall calibrate,maintain,and operate a continuous monitoring system for
measuring nitrogen oxide emissions discharged to the atmosphere and record the output of the system.
h. 40 CFR 60.48b(c)—operation of nitrogen oxide continuous monitoring systems and data recording.
i. 40 CFR 60.48b(d)—measurement of nitrogen oxide 1-hour averages.
j. 40 CFR 60.48b(e)—installation,evaluation,and operation of continuous monitoring systems.
k. 40 CFR 60.48b(f)-continuous monitoring systems breakdowns,repairs,calibration checks and zero and
span adjustments.
Recordkeeping[15A NCAC 2Q.0508(f)]
1. 40 CFR 60.49b(d)—recordkeeping of the amounts of each fuel fired each day.
in. 40 CFR 60.49b(e)—quarterly recordkeeping of the nitrogen content of the residual oil if burned.
n. 40 CFR 60.49b(f)—recordkeeping of the opacity.
o. 40 CFR 60.49b(g)—daily recordkeeping of the nitrogen oxide emission rates and supporting data.
p. 40 CFR 60.49b(h)—reporting of excess emissions.
Reporting[15A NCAC 2Q.0508(f)]
Air Quality Permit No. 05884T14
Page 9
q. The Permittee shall submit a summary report of the monitoring and recordkeeping activities,including the
requirements of 40 CFR 60.49b(i)and(h),postmarked on or before January 30 of each calendar year for the
preceding six-month period between July and December and July 30 of each calendar year for the preceding
six-month period between January and June. All instances of deviations from the requirements of this
permit must be clearly identified.
3. 15A NCAC 2D.0501(e): COMPLIANCE WITH NATIONAL AMBIENT AIR QUALITY STANDARDS
a. Particulate matter(PM10)emissions from each source(ID Nos.ES-14A,ES-1-111,ES-14C,ES-24A,
ES-2-113 and ES-24C)shall not exceed 6.02 pounds per hour.
b. Sulfur dioxide emissions from each source(ID Nos.ES-1-IA,ES-1-111,ES-14C,ES-24A,ES-2-113 and
ES-24C)shall not exceed 327.8 pounds per hour.
c. Nitrogen oxide emissions from each source(ID Nos.ES-14A,ES-1-111,ES-14C,ES-24A,ES-2-113 and
ES-24C)shall not exceed 120.4 pounds per hour.
d. Carbon monoxide emissions from each source(ID Nos.ES-14A,ES-1-111,ES-14C,ES-24A,ES-2-111
and ES-24C)shall not exceed 120.4 pounds per hour.
e. The maximum sulfur content of any coal received and burned in these sources(ID Nos.ES-14A,ES-1-113,
ES-1-IC,ES-24A,ES-2-113 and ES-24C)shall not exceed 1.0 percent by weight.
Testin [15A NCAC 2Q.0508(f)]
f. If emissions testing is required,the testing shall be performed in accordance with General Condition JJ. If
the results of this test are above any limit given in Section 2.1 A.3.a through d above,the Permittee shall be
deemed in noncompliance with 15A NCAC 2D .0501(e).
MonitorinE/Recordkeeping[15A NCAC 2Q .0508(f)]
g. Particulate matter emissions from these sources(ID Nos.ES-14A,ES-1-113,ES-14C,ES-24A,ES-2-113
and ES-24C)shall be controlled by six bagfilters(ID Nos.CD-14A,CD-1-113,CD-14C,CD-24A,CD-
2-1B and CD-24C),one each. To assure compliance,the Permittee shall perform inspections and
maintenance as recommended by the manufacturer. In addition to the manufacturer's inspection and
maintenance recommendations,or if there are no manufacturer's inspection and maintenance
recommendations,as a minimum,the inspection and maintenance requirement shall include an annual
internal inspection of the bagfilters(ID Nos. CD-14A,CD-1-113,CD-1-IC,CD-24A,CD-2-111 and CD-
24C)for structural and fabric filter integrity. The Permittee shall be deemed in noncompliance with 15A
NCAC 2D.0501(e)if the bagfilters(ID Nos. CD-14A,CD-1-113,CD-1-IC,CD-24A,CD-2-111 and CD-
24C)are not inspected and maintained.
h. The Permittee shall install,operate,and maintain a pressure drop indicator on each bagfilter(ID Nos. CD-
1-IA,CD-1-111,CD-14C,CD-24A,CD-2-111 and CD-24C). The pressure drop across each bagfilter
(ID Nos. CD-14A,CD-1-113,CD-14C,CD-24A,CD-2-1B and CD-24C)shall not exceed 10 inches of
water. The Permittee shall be deemed in noncompliance with 15A NCAC 2D .0501(e)if the pressure drop
is not maintained within the prescribed limits.
i. The results of inspection and maintenance shall be maintained in a logbook(written or electronic format)
on-site and made available to an authorized representative upon request. The logbook shall record the
following:
i. the date and time of each recorded action;
ii. the pressure drop once weekly at a minimum when the source(ID Nos.ES-14A,ES-1-111,ES-14C,
ES-24A,ES-2-111 and ES-24C)is operating;.
iii. the results of each inspection;
iv. a report of any maintenance performed on the bagfilters(ID Nos.CD-14A,CD-1-113,CD-14C,CD-
2-1A,CD-2-1B and CD-24C);and
v. any variance from manufacturer's recommendations, if any, and corrections made.
The Permittee shall be deemed in noncompliance with 15A NCAC 2D .0501(e)if these records are not
maintained.
j. The Permittee shall follow the monitoring and recordkeeping requirements in Sections 2.1 A.I.c,2.1 A.2.f-j
and 2.1 A.2.n above. The Permittee shall be deemed in noncompliance with 15A NCAC 2D.0501(e)if this
monitoring and recordkeeping is not performed.
Air Quality Permit No. 05884T14
Page 10
Reporting[15A NCAC 2Q.0508(f)]
k. Within 30 days of a written request from DAQ,the Permittee shall submit a report of any maintenance
performed on the bagfilters(ID Nos.CD-1-1A,CD-14B,CD-14C,CD-24A,CD-24B and CD-24C).
1. The Permittee shall submit a summary report of monitoring and recordkeeping activities postmarked on or
before January 30 of each calendar year for the preceding six-month period between July and December and
July 30 of each calendar.year for the preceding six-month period between January and June. All instances
of deviations from the requirements of this permit must be clearly identified.
Alternative Operating Scenario for Emissions of Sulfur Dioxide Only - While operating FSI SOZ
reduction technology with limestone/lime/trona
aa. Sulfur dioxide emissions from each boiler(ID Nos.ES-14A,ES-14B,ES-1-1C, ES-2-1A,ES-2-113 and
ES-24C)shall not exceed 327.8 pounds per hour. [15A NCAC 2D.0501(e)]
Testing[15A NCAC 2Q.0508(f)]
bb. If emissions testing is required, the testing shall be performed in accordance with General
Condition JJ found in Section 3. If the results of this test are above any limit given in Section 2.1 A. 3. aa.
above,the Permittee shall be deemed in noncompliance with 15A NCAC 2D.0501(e).
MonitorinL,/Recordkeeping[15A NCAC 2Q.0508(f)]
cc. The Permittee shall assure compliance with 2.1 A. 3.aa. above by determining sulfur dioxide emissions in
pounds per hour using a continuous emissions monitoring(CEM)system meeting the requirements of 40
CFR Part 75 except that unbiased values may be used(missing data shall be filled in accordance with 40
CFR Part 75,except that the lookback periods per 40 CFR 75.33 (Tables 1 and 2)shall consist of the
available data up to the appropriate quality-assured hours.Also,the replacement procedures for monitor
data availability between 80 and 90 percent may be used at values below 80 percent). Compliance with
sulfur dioxide emission standards shall be determined by averaging hourly continuous emission monitoring
system values over a 24-hour block period beginning at midnight. To compute the 24-hour block average,
the average hourly values(missing data shall be filled in accordance with 40 CFR Part 75,except that the
lookback periods per 40 CFR 75.33 (Tables 1 and 2)shall consist of the available data up to the appropriate
quality-assured hours. Also,the replacement procedures for monitor data availability between 80 and 90
percent may be used at values below 80 percent)shall be summed,and the sum shall be divided by 24. The
minimum number of data points,equally spaced,required to determine a valid hour value shall be
determined by 40 CFR Part 75.If any 24-hour block average exceeds the limits per Section 2.1 A.3.aa.
above or the records are not maintained,the Permittee shall be deemed in noncompliance with 15A NCAC
2D.0501(e).
Reporting[15A NCAC 2Q.0508(f)]
dd. The Permittee shall submit the continuous emissions monitoring data showing the 24-hour daily block
values in pounds per hour for sulfur dioxide emissions for each 24-hour daily block averaging period
during the reporting period no later than January 30 of each calendar year for the preceding three-month
period between October and December, April 30 of each calendar year for the preceding three-month
period between January and March, July 30 of each calendar year for the preceding three-month period
between April and June, and October 30 of each calendar year for_the preceding three-month period
between July and September. All instances of deviations from the requirements of this permit must be
clearly identified.
ee. CEMs Monitor Availability-The Permittee shall submit sulfur dioxide CEM system monitor downtime
reports,including monitor availability values(as calculated for 40 CFR Part 75)for the last hour of the
reporting period,no later than January 30 of each calendar year for the preceding three-month period
between October and December,April 30 of each calendar year for the preceding three-month period
between January and March,July 30 of each calendar year for the preceding three-month period between
April and June,and October 30 of each calendar year for the preceding three-month period between July
and September.
4. 15A NCAC 2D.0530: PREVENTION OF SIGNIFICANT DETERIORATION
Air Quality Permit No.05884T14
Page 11
a. Particulate matter(PMIo)emissions from each source(ID Nos.ES-1-1A,ES-14B,ES-1-1C,ES-2-1A,
ES-2-113 and ES-24C)shall not exceed 0.027 pounds per million Btu heat input.
b. Sulfur dioxide emissions from each source(ID Nos.ES-14A,ES-14B,ES-14C,ES-2-1A,ES-24B and
ES-2-1C)shall not exceed 1.47 pounds per million Btu heat input.
c. Nitrogen oxide emissions from each source(ID Nos.ES-14A,ES-14B,ES-14C,ES-24A,ES-24B and
ES-2-1C)shall not exceed 0.54 pounds per million Btu heat input.
d. Carbon monoxide emissions from each source(ID Nos.ES-14A,ES-14B,ES-14C,ES-24A,ES-24B
and ES-2-1C)shall not exceed 0.54 pounds per million Btu heat input.
e. Sulfuric acid mist emissions from each source(ID Nos.ES-14A,ES-14B,ES-14C,ES-24A,ES-24B
and ES-2-1C)shall not exceed 0.019 pounds per million Btu heat input.
f. The maximum sulfur content of any coal received and burned in these sources(ID Nos.ES-14A,ES-1-113,
ES-14C,ES-24A,ES-2-1B and ES-2-1C)shall not exceed 1.0 percent by weight.
Testing[15A NCAC 2Q.0508(t)]
g. If emissions testing is required,the testing shall be performed in accordance with General Condition JJ. If
the results of this test are above any limit given in Section 2.1 A.4.a-e above,the Permittee shall be deemed
in noncompliance with 15A NCAC 21) .0530.
h. Under the provisions of NCGS 143-215.108,the Permittee shall conduct an emission stack test for
particulate matter(PMIo)on each source stack(Unit 1-ID Nos.ES-14A,ES-14B,and ES-14C; or
Unit 2—ID Nos.ES-24A,ES-24B and ES-2-1C)once per permit term to determine the emission rate in
pounds per hour and pounds per million Btu for particulate matter(PMIo)as follows:
i. the emissions stack test shall include the following operating scenarios:
A. 10%unadulterated wood,70%coal,and 20%tire-derived fuels;and
B. 16%tire-derived fuels and 84%coal.
If physical design limitations exist which prevent the Permittee from achieving either of the above feed
compositions,the Permittee shall conduct the tests with the maximum feasible feed rated of wood,in
the first scenario,and maximum feasible feed rates of tire-derived fuels,in the second scenario.
ii. all testing shall be conducted in accordance with a testing protocol approved by the DAQ, as provided
in Section 3,General Condition JJ of this permit.
iii. the Permittee shall submit a written report of the test results to the DAQ Regional Supervisor within 60
days of completion of each test.
If the required stack test is not conducted or if the results of this test are above the limits given in Section
2.1 A.4.a above,the Permittee shall be deemed in noncompliance with 15A NCAC 213 .0530.
Monitoring/Recordkeeping[15A NCAC 2Q .0508(f)]
i. The Permittee shall follow the monitoring and recordkeeping requirements in Section 2.1 A.Lc,A.21--j and
n,and A.3.g-i. The Permittee shall be deemed in noncompliance with 15A NCAC 2D .0530 if this
monitoring and recordkeeping is not performed.
Reporting[15A NCAC 2Q.0508(f)]
j. The Permittee shall follow the reporting requirements in Section 2.1 A.l.d,2.1 A.2.p,and 2.1 A.314 above.
Alternative Operating Scenario for Emissions of Sulfur Dioxide Only - While operating FSI SOZ
reduction technology with limestone/lime/trona
aa. Sulfur dioxide emissions from each boiler(ID Nos.ES-1-1A,ES-1-113,ES-1-1C,ES-2-1A,ES-2-1B and
ES-2-1C)shall not exceed 1.47 pounds per million Btu heat input. [15A NCAC 21) .0530]
Testing[15A NCAC 2Q.0508(f)]
bb. If emissions testing is required, the testing shall be performed in accordance with General
Condition JJ found in Section 3. If the results of this test are above any limit given in Section 2.1 A.4. aa.
above,the Permittee shall be deemed in noncompliance with 15A NCAC 2D.0530.
Monitoring/Recordkeeping[15A NCAC 2Q.0508(f)]
Air Quality Permit No. 05884T14
Page 12
cc. The Permittee shall assure compliance with 2.1 A.4.aa. above by determining sulfur dioxide emissions in
pounds per million Btu using a continuous emissions monitoring(CEM) system meeting the requirements
of 40 CFR Part 75 except that unbiased values may be used(missing data shall be filled in accordance with
40 CFR Part 75, except that the lookback periods per 40 CFR 75.33 (Tables I and 2) shall consist of the
available data up to the appropriate quality-assured hours. Also, the replacement procedures for monitor
data availability between 80 and 90 percent may be used at values below 80 percent). Compliance with
sulfur dioxide emission standards shall be determined by averaging hourly continuous emission monitoring
system values over a 24-hour block period beginning at midnight. To compute the 24-hour block average,
the average hourly values (missing data shall be filled in accordance with 40 CFR Part 75, except that the
lookback periods per 40 CFR 75.33 (Tables 1 and 2)shall consist of the available data up to the appropriate
quality-assured hours. Also,the replacement procedures for monitor data availability between 80 and 90
percent may be used at values below 80 percent)shall be summed,and the sum shall be divided by 24. The
minimum number of data points, equally spaced, required to determine a valid hour value shall be
determined by 40 CFR Part 75. If any 24-hour block average exceeds the limits per Section 2.1 A.4. aa.
above or the records are not maintained,the Permittee shall be deemed in noncompliance with 15A NCAC
2D .0530.
Reporting[15A NCAC 2Q.0508(f)]
dd. The Permittee shall submit the continuous emissions monitoring data showing the 24-hour daily block
values in pounds per hour for sulfur dioxide emissions for each 24-hour daily block averaging period
during the reporting period no later than January 30 of each calendar year for the preceding three-month
period between October and December, April 30 of each calendar year for the preceding three-month
period between January and March, July 30 of each calendar year for the preceding three-month period
between April and June, and October 30 of each calendar year for the preceding three-month period
between July and September. All instances of deviations from the requirements of this permit must be
clearly identified.
ee. CEMs Monitor Availability - The Permittee shall submit sulfur dioxide CEM system monitor downtime
reports, including monitor availability values (as calculated for 40 CFR Part 75) for the last hour of the
reporting period, no later than January 30 of each calendar year for the preceding three-month period
between October and December, April 30 of each calendar year for the preceding three-month period
between January and March, July 30 of each calendar year for the preceding three-month period between
April and June, and October 30 of each calendar year for the preceding three-month period between July
and September.
5. 15A NCAC 2D.0530(u):PREVENTION OF SIGNIFICANT DETERIORATION
a. The Permittee has used projected actual emissions to avoid applicability of prevention of significant
deterioration requirements for a project consisting of increasing the feed rate of tire derived fuel to 50%of
heat input rate of each boiler (ID Nos. ES-14A, ES-1-1B, ES-14C, ES-24A, ES-2-1B and ES-24C),
installing rotating opposed overfire air systems(ID Nos. CD-1-5A through CD-1-5C and CD-2-5A through
CD-2-5C), furnace sorbent injection systems (ID Nos. CD-1-6A through CD-1-6C and CD-2-6A through
CD-2-6C)and selective non-catalytic reduction systems(CD-1-7A through CD-1-7C and CD-2-7A through
CD-2-7C) on boilers(ID Nos. ES-14A, ES-14B, ES-14C, ES-24A, ES-24B and ES-24C), and
installing alkaline sorbent silos(ID Nos.ES-9A and CD-9B)and associated vent fabric filters(ID No. CD-
9A and CD-9B).
In order to verify the assumptions used in the projected actual emissions calculations, the Permittee shall
comply with the testing,record keeping and reporting requirements in Section 2.1 A.5.b.through d.below.
Testing[15A NCAC 2Q.0508(fl]
b. Under the provisions of NCGS 143-215.108, the Permittee shall conduct emissions testing for boilers (ID
Nos. ES-1-1A, ES-1-1B, ES-14C, ES-24A, ES-24B and ES-2-1C)) for PM, PM10,NOx, S02i CO, and
VOC within 180 days of commencement of feeding tire derived fuel at 50%of the heat input rate in each
boiler,installing rotating opposed overfire air systems,furnace sorbent injection systems and selective non-
Air Quality Permit No. 05884T14
Page 13
catalytic reduction systems4 on each boiler, and installing alkaline sorbent silos and associated vent fabric
filters.
Details of the emissions testing and reporting requirements can be found in Section 3 - General Condition
JJ.
The Permittee shall establish emission factors based on the average of all runs performed in the units of
pounds per million Btu heat input for PM,PMIo,NOx, S02i CO, and VOC. These emission factors shall be
used along with the actual fuel input rates to calculate monthly emissions from each boiler (ID Nos.ES-1-
IA,ES-1-113,ES-14C,ES-24A, ES-2-113 and ES-24C). The calculated monthly emissions shall be used
in reporting actual emissions for these pollutants in Section 2.1 A.5.d.below.
Recordkeeping[15A NCAC 2D.0530(u)]
c. The Permittee shall maintain records of actual emissions for PM, PM10,NOx, S02, CO, and VOC in tons
per year on a calendar year basis for five years following the resumption of regular operations after
commencement of tire derived fuel feedrate in each boiler at 50% (ID Nos. ES-14A, ES-1-113, ES-14C,
ES-24A, ES-2-113 and ES-24C), installing rotating opposed overfire air systems (ID Nos. CD-1-5A
through CD-1-5C and CD-2-5A through CD-2-5C), furnace sorbent injection systems (ID Nos. CD-1-6A
through CD-1-6C and CD-2-6A through CD-2-6C)and selective non-catalytic reduction systems(CD-1-7A
through CD-1-7C and CD-2-7A through CD-2-7C)on boilers(ID Nos.ES-14A,ES-1-113,ES-14C,ES-2-
1A, ES-2-113 and ES-24C), and installing alkaline sorbent silos (ID Nos. ES-9A and CD-913) and
associated vent fabric filters(ID No. CD-9A and CD-913).
The Permittee shall make the information, documented and maintained in this Section 2.1 A.5.c., available
to the Director or the general public pursuant to the requirements in 40 CFR 70.4(b)(3)(viii).
Reporting[15A NCAC 2D .0530(u)]
d. The Permittee shall submit a report for PM, PMIo, NOx, S02, CO, and VOC emissions to the Director
within 60 days after the end of each calendar year during which the records in Section 2.1 A.5.c. must be
generated. The report shall contain the items listed in 40 CFR 51.166(r)(6)(v)(a)through(c).
The reported actual emissions for each of the five calendar years for PM,PM10,NOx, S02, CO, and VOC
will be compared to the respective projected actual emissions as included below:
Pollutant Projected Actual Emissions Projected Actual
Emission Factor Emissions**
Lb/Million Btu Tons per Year
PM 0.0184 86.1
PMIo 0.0184 83.2
NOx 0.35 1296
S02 1.37(CoaUTDF) 3700
0.021 (Wood)
CO 0.077(CoaUTDF) 306
0.1 (Wood)
VOC 0.0037 (CoaUTDF) 27
0.017(Wood)
The emission factor is for boiler only.
"The projected actual emissions are not enforceable limitations. If the reported actual emissions exceed
the projected actual emissions, the Permittee shall include in its annual report an explanation as to why
actual emissions exceeded the projected actual emissions.
6. 15A NCAC 2D.0614: COMPLIANCE ASSURANCE MONITORING
i
4 The installation of selective non-catalytic reduction systems on each boiler is optional.
i
Air Quality Permit No. 05884T14
Page 14
a. Per 40 CFR 64 and 15A NCAC 2D .0614,the Permittee shall comply with the following.
b. Background
i. Emission Unit(s).
(A) Description. Six watertube design coal/natural gas/No.2 and No.4 fuel oil/tire derived
fuel/pelletized paper fuel/flyash briquette/unadulterated wood-fired boilers
(B) Identification. ID Nos.ES-1-1A,ES-1-1B,ES-14C,ES-24A,ES-24B and ES-2-1C
ii. Applicable Regulation,Emission Limit,and Monitoring Requirements.
(A) Regulations. 15A NCAC 2D.0524(Subpart Db)
15A NCAC 2D.0501(e)
15A NCAC 2D.0530
(B) Emission limits
1. 0.05 pounds per million Btu heat input(40 CFR 60.43b(a)(1))—[particulate matter]
20 percent opacity[40 CFR 60.43b(f)]
2. 6.02 pounds per hour per boiler[PMIo]
3. 0.027 pounds per million Btu heat input per boiler[PMIo]
(C) Control Technology. Six bagfilters(ID Nos.CD-14A,CD-14B,CD-14C,CD-24A,CD-2-1B
and CD-24C)
c. Monitoring Approach. The key elements of the monitoring approach for particulate matter,including
parameters to be monitored,parameter ranges and performance criteria are presented in the following table.
1 2
I. Indicator Visible emissions Pressure drop
Measurement Approach Visible emissions from the fabric filter Pressure drop across the fabric filter is
will be monitored continuously using measured with a differential pressure gauge
COM system on each common stack
II. Indicator Range An excursion is defined as visible An excursion is defined as a pressure drop
emissions in amounts greater than or greater than 9.5 inches of water. Excursions
equal to 15%(six-minute average). trigger an inspection,corrective action,and
Excursions trigger an inspection, a reporting requirement.
corrective action,and a reporting
requirement.
QIP Threshold None selected
The QIP threshold is six excursions in a
6-month reporting period.
I
I
II
Air Quality Permit No. 05884T14
Page 15
1 2
III. Performance Criteria
A. Data Representativeness Measurements are being made at the Pressure taps are located at the fabric filter
emission point(fabric filter outlet)of inlet and outlet. The gauge has a minimum
each common stack accuracy of 0.5 inches of water.
B. Verification of NA NA
Operational Status
C. QA/QC Practices The COM systems shall be calibrated, The pressure gauge is checked daily for
maintained and operated according to 40 operation.
CFR 60,Appendix B,PSI.
D. Monitoring Frequency Data is collected continuously with COM Pressure drop is monitored daily.
systems.
E. Data Collection Date from the COM systems is collected Pressure gauge readings are manually
Procedures electronically and maintained on the Data recorded daily.
Acquisition and Handling System
computer along with information on the
operating status of the boilers.
NA NA
F. Averaging Periods
d. Justification
i. Background. The pollutant-specific emission units are the six identical stoker boilers used to produce
steam(a portion of which is sold to a nearby industrial facility for use in their process). The remainder
of the steam is used to drive a steam turbine connected to an electrical generator to generate electricity
for wholesale to the connected utility. The particulate matter emissions from each boiler are controlled
by fabric filters with approximately 16,800 square feet of filter area,each.
ii. Rationale for Selection of Performance Indicators. Visible emissions was selected as the performance
indicator because it is a good indicator of the proper operation and maintenance of the filter units.
When the filter units are operating properly,there will not be any visible emissions in the exhaust
outlet.Any increase in visible emissions indicates reduced performance of the filter units,therefore,the
presence of visible emissions in levels exceeding or equal to 15%(six-minute average)is used as a
performance indicator.
In general,filters are designed to operate at a relatively constant pressure drop. Monitoring pressure
drop provides a means of detecting a change in operation that could lead to an increase in emissions.
An increase in pressure drop can indicate that the cleaning cycle is not frequent enough,cleaning
equipment is damaged/broken,the bags are becoming blinded,or the airflow has increased. A decrease
in pressure drop may indicate broken or loose bags,but this is also indicated by the presence of visible
emissions,indicator No. 1. A pressure drop across the filter unit also serves to indicate that there is
airflow through the control device.
iii. Rationale for Section of Indicator Ranges. Per operating knowledge of the systems,the facility has
selected an indicator range of greater than or equal to 15%opacity(six-minute average). When an
excursion occurs, corrective action will be initiated,beginning with an evaluation of the occurrence to
determine the action required to correct the situation. All excursions will be documented and reported.
This indicator range was selected because: (1)an increase in visible emissions is indicative of an
increase in particulate emissions;and(2)a COMB is a well established monitoring technique for these
sources.
The selected QIP threshold for fabric filter visible emissions is six excursions in a 6-month reporting
period. If the QIP threshold is exceeded in a semiannual reporting period,a QIP will be developed and
Air Quality Permit No. 05 884T 14
Page 16
implemented.
The indicator range chosen for the fabric filter pressure drop is greater than 9.5 inches water. An
excursion triggers an inspection,corrective action,and a reporting requirement. The pressure drop is
recorded daily. As the pressure drop approaches 9.5 inches water the bags are scheduled for
replacement.
Reporting[15A NCAC 2Q.0508(f)]
e. The Permittee shall submit a summary report of all monitoring activities postmarked on or before January
30 of each calendar year for the preceding six-month period between July and December and July 30 of
each calendar year for the preceding six-month period between January and June. All instances of
deviations for the requirements of this permit must be clearly identified.
7. 15A NCAC 2D.1109: Case-by-Case MACT*
a. The Permittee shall comply with this CAA§1120)standard until May 22,2019. The initial compliance
date for the applicable CAA§112(d)standard for"National Emission Standards for Hazardous Air
Pollutants for Industrial,Commercial,and Institutional Boilers and Process Heaters"is May 23,2019.
Emissions Standards
b. The following emission standards shall apply to the affected boilers(ID Nos.ES-1-1A,ES-14B,ES-14C,
ES-24A,ES-2-1B and ES-24C):
i. All fuel combinations,based on each of these boilers being a"unit designed to burn biomass/bio-based
solid subcategory"as defined in 40 CFR 63.7575:
(A) Particulate Matter(filterable only): 0.18 lb/million Btu
(B) Mercury: 0.000005 lb/million Btu
(C) Hydrogen Chloride: 0.02 lb/million Btu
(D) Carbon Monoxide: 508 ppmvd,corrected to 7%02,30-day rolling average
The initial compliance date for the emission standards,operating requirements,and associated monitoring,
recordkeeping,and reporting requirements is June 2,2013. These terms need not be included in the annual
compliance certification until after the initial compliance date. These standards shall apply all times,
except for periods of startup,shutdown,and malfunction.The Permittee shall follow the procedures in 15A
NCAC 2D.0535 for any excess emissions that occur during the periods of startup,shutdown,or
malfunction.
Operating Requirements
c. If the facility utilizes a fabric filter to comply with the particululate matter(PM)(filterable only)and
mercury(Hg)emissions standards in Section 2.1 A.7.b.above,the Permittee shall comply with the
following:
i. Install and operate the fabric filter such that the bag leak detection system alarm does not sound more
than 5 percent of the operating time during each 6-month period;or,
ii. Maintain opacity of exhaust from the control device at less than or equal to 20 percent(6-minute
average)except for one 6-minute period per hour of not more than 27 percent.
d. If the facility utilizes a sorbent injection system(such as FSI)to comply with the hydrogen chloride(HCI)
emissions standards listed in Section 2.1 A.7.b.above,the Permittee shall maintain the minimum sorbent
i
injection rate at or above the operating levels,adjusted for variability,established during the performance
test that demonstrated compliance with the applicable emissions standards.
e. If the facility utilizes fuel analysis to comply with the Hg and HCl emissions standards in Section 2.1
A.7.b. above,the Permittee shall maintain the fuel type or fuel mixture such that the Hg and HCl emissions
rates calculated according to the procedures in Section 2.1 A.Ti.below are less than the applicable
emission standards.
I
Testing[15A NCAC 2Q.0508(f)]
f. No initial or subsequent annual testing is required to demonstrate compliance with the emissions standards
associated with burning of No.2 fuel oil and natural gas in the affected boilers.
I
Air Quality Permit No. 05884T14
Page 17
g. No initial or subsequent annual testing is required if a facility can demonstrate compliance with applicable
emissions standards using fuel analysis according to the procedures in Section 2.1 A.71 below.
h. Initial Testing Requirement-The Permittee shall conduct an initial compliance test while burning mixed
fuel of a ratio,by heat input,of approximately 50 percent wood and 50 percent coal/TDF for emissions of
PM(filterable only),Hg,HCl, and CO.
The initial compliance test for these fuels shall be conducted within 180 days of the initial compliance date.
The initial compliance test is not required if the NC DAQ—SSCB approves any previously conducted
performance test as an equivalent compliance demonstration. Testing shall be conducted in accordance
with General Condition JJ found in Section 3.
The Permittee shall establish operating parameters,as applicable,during the initial compliance test in
accordance with the following Table.
Operating Parameters Established by Performance Testing
Control Device Pollutant(s) Requirements for Performance Test
Sorbent Injection HCI 1.Collect sorbent injection rate data every 15 minutes during the
System(such as entire period of the performance test;and,
FSn 2.Determine the average sorbent injection rate for each individual test
run in the 3-run performance test by computing the average of all the
15-minute readings taken during each test run.
The Permittee shall be deemed in non-compliance with 15A NCAC 2D.1109 if the required tests are not
conducted,or if the results of the emissions tests exceed the emission standards in Section 2.1.A.7.b.above,
or if the operating parameters,as applicable,are not established.
i. If the Permittee chooses to demonstrate compliance with the emissions standards in Section 2.1 A.7.b.
above using the fuel analyses,the following procedures shall be complied with.
i. Develop and submit a site-specific fuel analysis plan to the NC DAQ—SSCB for review and approval
no later than 60 days before the date that the Permittee plans to demonstrate compliance. The plan
shall include the following information:
(A) The identification of all fuel types anticipated to be burned in each affected boiler or process
heater.
(B) For each fuel type,identification of whether the fuel analysis will be conducted by the Permittee
or a fuel supplier.
(C)'For each fuel type,a detailed description of the sample location and specific procedures to be used
for collecting and preparing the composite samples if the procedures are different from paragraph
c. or d.below. Samples should be collected at a location that most accurately represents the fuel
type,where possible,at a point prior to mixing with other dissimilar fuel types.
(D) For each fuel type,the analytical methods,with the expected minimum detection levels,to be used
for the measurement of C12 and Hg.
ii. Obtain,at a minimum,three composite fuel samples for each fuel type according to the following
procedures,or according to the procedures in Table in this Section:
(A) If sampling from a belt(or screw)feeder,collect fuel samples as follows:
(1) Stop the belt and withdraw a 6-inch wide sample from the full cross-section of the stopped
belt to obtain a minimum two pounds of sample. Collect all the material(fines and coarse)in
the full cross-section.Transfer the sample to a clean plastic bag.
(2) Each composite sample will consist of a minimum of three samples collected at
approximately equal intervals during the testing period.
(B) If sampling from a fuel pile or truck,collect fuel samples according as follows:
(1) For each composite sample,select a minimum of five sampling locations uniformly spaced
over the surface of the pile.
(2) At each sampling site,dig into the pile to a depth of 18 inches.Insert a clean flat square
shovel into the hole and withdraw a sample,making sure that large pieces do not fall off
during sampling.
(3) Transfer all samples to a clean plastic bag for further processing.
i
I
Air Quality Permit No. 05884T14
Page 18
iii. Prepare each composite sample according to the procedures in paragraphs(A).through(G)below:
(A) Thoroughly mix and pour the entire composite sample over a clean plastic sheet.
(B) Break sample pieces larger than 3 inches into smaller sizes.
(C) Make a pie shape with the entire composite sample and subdivide it into four equal parts.
(D) Separate one of the quarter samples as the first subset.
(E) If this subset is too large for grinding,repeat the procedure in paragraph iii. above with the quarter
sample and obtain a one-quarter subset from this sample.
(F) Grind the sample in a mill.
(G) Use the procedure in paragraph(C)above to obtain a one-quarter subsample for analysis. If the
quarter sample is too large,subdivide it further using the same procedure.
iv. Determine the concentration of Hg and C12 in unit of lb/million Btu of each composite sample for each
fuel type according to the procedures in the following Table:
Pollutant(s) Task Method
Hg and HCl Collect Fuel Samples • Procedure in paragraph c.above;or,
• ASTM D2234-00,D2234M-03(for coal)(IBR,see 40 CFR 63.14(b));or,
• ASTM D6323-98(2003)(for biomass)(IBR,see 40 CFR 63.14(b)).
Prepare Composited Fuel • SW-846-3050B(for solid samples);or,
Samples • SW-846-3020A(for liquid samples);or,
• ASTM D2013-04(for coal)(113R,see 40 CFR 63.14(b));or,
• ASTM D5198-92(2003)(for biomass)(IBR,see 40 CFR 63.14(b)).
Determine Heat Content • ASTM D5865-04(for coal)(113R,see 40 CFR 63.14(b));or,
• ASTM E711-87(for biomass)(113R,see 40 CFR 63.14(b)).
Determine Moisture • ASTM D3137-03(113R,see 40 CFR 63.14(b));or,
Content • ASTM E871-82(1998)(113R,see 40 CFR 63.14(b)).
�Hg Measure Hg Concentration • ASTM D6722-01(for coal)(113R,see 40 CFR 63.14(b));or,
in Sample • SW-846-7471A(for solid samples);or,
• SW-846-7470A(for liquid samples).
Convert Concentration into Method 19 F-factor methodology in 40 CFR 60,Appendix A
Ibs/MMBtu
HCl Measure HCl • SW-846-9250 or ASTM D6721-01(for coal);or,
Concentration in Sample • ASTM E776-87(1996)(for biomass)(113R,see 40 CFR 63.14(b)).
Convert Concentration into Method 19 F-factor methodology in 40 CFR 60,Appendix A
Ibs/MMBtu
v. Establish the maximum chlorine fuel input(Cinput)during the initial performance testing according to
the following procedures:
(A) Determine the permitted fuel type or fuel mixture that has the highest content of chlorine.
(B) During the performance testing for HCl,determine the fraction of the total heat input for each fuel
type burned(Qi)based on the fuel mixture that has the highest content of chlorine, and the average
chlorine concentration of each fuel type burned(Ci).
(C) Establish a maximum chlorine input level using the following equation.
C1;"p"'=E,=t." [Ci/Qil
Where:
Clinput = Maximum amount of chlorine entering the boiler or process heater
through fuels burned in lbs/million Btu.
Ci = Arithmetic average concentration of chlorine in fuel type,i, determined
by fuel analysis,in lbs/million Btu.
Qi = Fraction of total heat input from fuel type,i,based on the fuel mixture
that has the highest content of chlorine. If multiple fuel types are not
fired during the performance testing,insert a value of"1"for Qi.
n = Number of different fuel types burned in your boiler or process heater
for the mixture that has the highest content of chlorine.
Air Quality Permit No. 05884T14
Page 19
vi. Establish the maximum Hg fuel input level(Mercuryinput)during the initial performance testing using
the procedures provided below.
(A) Determine the fuel type or fuel mixture that can be burned in the boiler or process heater with the
highest content of Hg.
(B) During the compliance demonstration for Hg,determine the fraction of total heat input for each
fuel burned(Qi)based on the fuel mixture that has the highest content of mercury,and the average
mercury concentration of each fuel type burned(HGi).
(C) Establish a maximum mercury input level using the following equation:
Mercury;"p"t=Z;=j to" [HG/Q;]
Mercuryinput = Maximum amount of mercury entering the boiler or
process heater through fuels burned in lbs/million Btu.
HGi = Arithmetic average concentration of mercury in fuel type,i,determined
by fuel analysis,in lbs/million Btu.
Qi = Fraction of total heat input from fuel type,i,based on the fuel mixture
that has the highest content of chlorine. If multiple fuel types are not
fired during the performance testing,insert a value of"1"for Qi.
n = Number of different fuel types burned in your boiler
or process heater for the mixture that has the highest content of Hg.
vii. If the affected source can burn more than one fuel type,determine the fuel mixture that would result in
the maximum emission rates of the pollutant(s)for which compliance will be demonstrated by fuel
analysis.
viii.Determine the 90th percentile confidence level fuel pollutant concentration of the composite samples
analyzed for each fuel type using the one-sided z-statistic test described in the following equation.
P90=mean+(SD x t)
Where:
P90 = 90th percentile confidence level pollutant concentration,in lb/million
Btu.
mean = Arithmetic average of the fuel pollutant concentration in the fuel
samples,in lb/million Btu.
SD Standard deviation of the pollutant concentration in the fuel samples,
in lb/million Btu.
t = t distribution critical value for 90th percentile(0.1)probability for
the appropriate degrees of freedom(number of samples minus one)
as obtained from a Distribution Critical Value Table.
ix. To demonstrate compliance with the applicable emission standard for HCI,the calculated HCI
emission rate,using the following equation,for the affected source shall be less than the applicable
emission standard.
HCI =Ei=t ton = [Cwo x Qj x 1.028]
Where:
HCl = HCl emission rate from the boiler or process heater in lbs/million
Btu.
Ci90 = 90th percentile confidence level concentration of chlorine in fuel type,
i,in lbs/MMBtu(calculated using Equation in Section 2.1 A.7.i.viii.
above) '
i
i
i
Air Quality Permit No.05884T14
Page 20
Qi =Fraction of total heat input from fuel type,i,based on the fuel mixture
that has the highest content of chlorine.If the affected source does not
burn multiple fuel types,insert a value of"1"for Qi.
n =Number of different fuel types burned in the affected source for the
mixture that has the highest content of chlorine.
1.028 = Molecular weight ratio of HCl to chlorine.
x. To demonstrate compliance with the applicable emission standard for mercury,the calculated mercury
emission rate,using the following equation,for the affected source shall be less than the applicable
emission standard.
Mercury =Ei=i to" = [HGvox Qi
Where:
Mercury =Mercury emission rate from the boiler or process heater in
lbs/million Btu.
HGi90 = 90th percentile confidence level concentration of mercury in fuel type,
i,in lbs/N vMtu (calculated using Equation in Section 2.1 A.7.i.viii.
above)
Qi =Fraction of total heat input from fuel type,i,based on the fuel mixture
that has the highest content of mercury.If the affected source does not
bum multiple fuel types,insert a value of"1"for Qi.
n =Number of different fuel types burned in the affected source for the
mixture that has the highest mercury content.
The Permittee shall be deemed in non-compliance with 15A NCAC 2D .1109 if the requirements of
this Section 2.1 A.7.i.are not complied with or the calculated emission rates of Hg or HCl exceed the
applicable emissions standards in Section 2.1.A.7.b. above.
j. Annual Testing Requirement-The Permittee shall conduct subsequent performance tests for mercury,
hydrogen chloride and particulate matter(filterable only)on an annual basis to comply with the emissions
standards in Section 2.1 A.7.b. above,when firing coal or tire derived fuel or pelletized paper fuel or
flyash briquette,No.4 fuel oil,and green wood,unless it meets the requirements listed in i.through iii.
below. Annual performance tests,if required,shall be completed between 10 and 12 months after the
previous performance test.
i. The Permittee may conduct performance tests less often for a given pollutant if the performance tests
for at least 3 consecutive years show compliance with the emission limit.In this case,the Permittee
need not conduct a performance test for that unit,consisting of three boilers,for that pollutant for the
next 2 years,but shall conduct a performance test during the third year and no more than 36 months
after the previous performance test. If any unit shows noncompliance with an emission standard,this
shall be considered a separate compliance issue with each individual boiler.
ii. If the affected unit continues to meet the emission limit,the Permittee may conduct performance tests
every third year,but each such performance test shall be conducted no more than 36 months after the
previous performance test.
iii. If a performance test shows noncompliance with an emission limit,the Permittee shall conduct annual
performance tests for that pollutant until all performance tests over a consecutive 3-year period show
compliance.
iv. If the Permittee uses fuel analysis to demonstrate compliance with the emissions standards in Section
2.1 A.7.b. above,the Permittee shall conduct a fuel analysis for each type of fuel burned no later than 5
years after the previous fuel analysis.
The Permittee shall be deemed in non-compliance with 15A NCAC 2D .1109 if any subsequent annual tests
or fuel analysis are not conducted,or if the results of the emissions tests exceed the applicable emissions
standards in Section 2.1.A.7.b. above.
j
Air Quality Permit No.05884T14
Page 21
Monitoring[15A NCAC 2Q.0508(f)]
k. For complying with the emission standards associated with coal/tire derived fuel/pelletized paper fuel/flyash
briquette,No.4 fuel oil,dry wood,and green wood burning,the Permittee shall install,operate,and
maintain a continuous emission monitoring system(CEMS)for carbon monoxide and oxygen or carbon
dioxide according to the procedures listed in i.through iv,below. The carbon monoxide and oxygen or
carbon dioxide shall be monitored at the same location at the outlet of the unit.
i. Each CEMS shall be installed,operated,and maintained according to the applicable procedures under
Performance Specification(PS)3 or 4A of 40 CFR 60,Appendix B,and according to the site-specific
monitoring plan(See Section 7).
I Conduct a performance evaluation of each CEMS according to the requirements in 40 CFR 63.8 and
according to PS 4A of 40 CFR 60,Appendix B.
iii. Each CEMS shall complete a minimum of one cycle of operation(sampling,analyzing,and data
recording)for each successive 15-minute period.
iv. The CEMS data shall be reduced as specified in 40 CFR 63.8(g)(2).
V. An alternate monitoring method may be used by substituting carbon dioxide instead of oxygen to
calculate carbon monoxide for purposes of CAA 1120)standard and 15A NCAC 2D. 1109 only. A
carbon dioxide diluent cap of 5.0%can be used if carbon dioxide concentrations fall below 5.0%.
Based on 40 CFR Part 60 Appendix A Method 19 Equations 19-1 and 19-7,the following formula can
be used as an alternate approach to calculate carbon monoxide corrected to 7%oxygen:
Fc 100 (20.9—%02 correction)
Cd— CW X Fd X %CO2w X 20.9
Where:
Cd =pollutant concentration,dry basis
CW =pollutant concentration,wet basis
Fe=Method 19 carbon F-factor for wood
Fd=Method 19 wet F-factor for wood
%02 correction=7%
vi. The Permittee shall calculate and record a 30-day rolling average emission rate on a daily basis. A
new 30-day rolling average emission rate is calculated as the average of all of the hourly CO emission
data for the preceding 30 operating days. This 30-day rolling average for CO will begin on November
29,2013,and the CO CEMS must be certified and operable by that date.
vii. Except for monitor malfunctions,associated repairs,and required quality assurance or control activities
(including,as applicable,calibration checks and required zero and span adjustments),the monitor shall
continuously record(or collect data at all required intervals)at all times that the affected source is
operating.
viii. For purposes of calculating data averages,the Permittee may not use data recorded during periods of
monitoring malfunctions,associated repairs,out-of-control periods,required quality assurance or
control activities,or when the boiler or process heater is operating at less than 50 percent of its rated
capacity. The Permittee shall use all the data collected during all other periods in assessing
compliance. Any period for which the monitoring system is out-of-control and data are not available
for required calculations constitutes a deviation from the monitoring requirements.
ix. A 30-day rolling average emission rate above the applicable emission limitation shall constitute a
violation of the standard.
X. The CEMS monitor downtime(MD)shall not exceed 5.0 percent.
Percent Monitor Downtime MMD)Calculation:
/oMD o Total Monitor Downtime
= x100
Total Source Operating Time"
* Total Monitor Downtime includes Quality Assurance(QA)activities unless exempted by regulation or defined in
it
Air Quality Permit No. 05884T14
Page 22
an agency approved QA Manual. The amount of exempt QA Time will be reported in the quarterly report as such.
** If a source operates less than 2200 hours during any quarter, the source may calculate the %MD using all
operating data for the current quarter and the preceding quarters until 2200 hours of data are obtained. [N.C.G.S. 143-
215.110]
The Permittee shall be deemed in non-compliance with 15A NCAC 2D .1109 if the requirements of this
Section 2.1 A.71. are not complied with or any 30-day rolling average emission rate of CO is above the
applicable CO emissions standards in Section 2.1 A.7.b. above when burning coal,tire derived fuel,
pelletized paper fuel,flyash briquette,No.4 fuel oil,dry wood,and green wood.
1. If the option to comply with the opacity operating requirement is selected in Section 2.1 A.7.c.above,the
Permittee shall install, operate,certify and maintain each continuous opacity monitoring system(COMS)
according to the procedures listed below.
i. Each COMS shall be installed,operated,and maintained according to PS 1 of 40 CFR 60,Appendix B.
ii. Conduct a performance evaluation of each COMS according to the requirements in 40 CFR 63.8 and
according to PS 1 of 40 CFR 60,Appendix B.
iii. As specified in 40 CFR 63.8(c)(4)(i),each COMS shall complete a minimum of one cycle of sampling
and analyzing for each successive 10-second period and one cycle of data recording for each
successive 6-minute period.
iv. The COMS data shall be reduced as specified in 40 CFR 63.8(g)(2).
v. Except for monitor malfunctions,associated repairs,and required quality assurance or control activities
(including,as applicable,calibration checks and required zero and span adjustments),monitor
continuously(or collect data at all required intervals)at all times that the affected source is operating.
vi. Include in the site-specific monitoring plan(See Section 7)procedures and acceptance criteria for
operating and maintaining each COMS according to the requirements in 40 CFR 63.8(d). At a
minimum,the monitoring plan shall include a daily calibration drift assessment,a quarterly
performance audit,and an annual zero alignment audit of each COMS.
vii. Operate and maintain each COMS according to the requirements in the monitoring plan and the
requirements of 40 CFR 63.8(e). Identify periods the COMS is out-of-control including any periods
that the COMS fails to pass a daily calibration drift assessment,a quarterly performance audit,or an
annual zero alignment audit.
viii.Determine and record all the 6-minute averages(and 1-hour block averages as applicable)collected for
periods during which the COMS is not out of control.
The Permittee shall be deemed in non-compliance with 15A NCAC 2D .1109 if the requirements of this
Section 2.1 A.71 are not complied with or any 6-minute average of opacity exceeds the operating
` requirement in Section 2.1 A.7.c.ii.above.
in. For each operating limit that requires the use of a CMS,the Permittee must install,operate,and maintain
each continuous parameter monitoring system(CPMS)according to the procedures listed below.
i. The CPMS must complete a minimum of one cycle of operation for each successive 15-minute period.
A valid hour of data must have a minimum of four successive cycles of operation.
ii. Except for monitoring malfunctions,associated repairs,and required quality assurance or control
activities(including,as applicable,calibration checks and required zero and span adjustments),
conduct all monitoring in continuous operation at all times that the affected unit is operating. A
monitoring malfunction is any sudden,infrequent,not reasonably preventable failure of the monitoring
to provide valid data. Monitoring failures that are caused in part by poor maintenance or careless
operation are not malfunctions.
iii. For purposes of calculating data averages,the Permittee may not use data recorded during monitoring
malfunctions,associated repairs,out-of-control periods,or required quality assurance or control
activities.The Permittee must use all the data collected during all other periods in assessing
compliance. Any period for which the monitoring system is out-of-control and data are not available
for required calculations constitutes a deviation from the monitoring requirements.
iv. Determine the 3-hour block average of all recorded readings,except as provided in paragraph iii. i
above.
v. Record the results of each inspection,calibration,and validation check.
vi. Operation above the established maximum or below the established minimum operating limits shall
constitute a violation of established operating limits.
I
I
Air Quality Permit No.05884T14
Page 23
The Permittee shall be deemed in non-compliance with 15A NCAC 2D.1109 if the requirements of this
Section 2.1 A.7.m. are not complied with.
n. If the option to comply with the fabric filter bag leak detection system operating requirement in Section 2.1
E.7.c. above is selected,the Permittee shall install,calibrate,maintain,and continuously operate a bag leak
detection system as specified below:
i. Install and operate a bag leak detection system for each exhaust stack of the fabric filter.
ii. Each bag leak detection system shall be installed,operated,calibrated,and maintained in a manner
consistent with the manufacturer's written specifications and recommendations and in accordance with
the guidance provided in EPA-454/R 98-015,September 1997.
iii. The bag leak detection system shall be certified by the manufacturer to be capable of detecting PM
emissions at concentrations of 10 milligrams per actual cubic meter or less.
iv. The bag leak detection system sensor shall provide output of relative or absolute particulate matter
loadings.
v. The bag leak detection system shall be equipped with a device to continuously record the output signal
from the sensor.
vi. The bag leak detection system shall be equipped with an alarm system that will sound automatically
when an increase in relative particulate matter emissions over a preset level is detected. The alarm
shall be located where it is easily heard by plant operating personnel.
vii. For positive pressure fabric filter systems that do not duct all compartments of cells to a common
stack,a bag leak detection system shall be installed in each baghouse compartment or cell.
viii.Where multiple bag leak detectors are required,the system's instrumentation and alarm may be shared
among detectors.
The Permittee shall be deemed in non-compliance with 15A NCAC 2D .1109 if the requirements of this
Section 2.1 E.7.n.are not conducted with.
o. If an affected source unit is controlled with a fabric filter and the facility demonstrates continuous
compliance using a bag leak detection system,the Permittee shall:
i. Initiate corrective action within I hour of a bag leak detection system alarm and complete corrective
actions as soon as practical,and operate and maintain the fabric filter system such that the alarm does
not sound more than 5 percent of the operating time during a 6—month period.
ii. Maintain records of the date,time,and duration of each alarm,the time corrective action was initiated
and completed,and a brief description of the cause of the alarm and the corrective action taken.
iii. Record the percent of the operating time during each 6-month period that the alarm sounds.
(A) If inspection of the fabric filter demonstrates that no corrective action is required,no alarm time is
counted.
(B) If corrective action is required,each alarm shall be counted as a minimum of 1 hour.
(C) If it takes longer than 1 hour to initiate corrective action,the alarm time shall be counted as the
actual amount of time taken to initiate corrective action.
The Permittee shall be deemed in non-compliance with 15A NCAC 2D .1109 if the requirements of this
Section 2.1 A.7.o. are not complied with or if the alarm on the fabric filter leak detection system sounds
more than 5 percent of the operating time during any 6—month period.
p. For each operating requirement that requires the use of equipment to monitor sorbent injection rate(e.g.,
weigh belt,weigh hopper,or hopper flow measurement device),the Permittee shall meet the requirements
in Section 2.1 A.7.m.above,in addition to the following requirements:
i. Locate the device in a position(s)that provides a representative measurement of the total sorbent
injection rate.
ii. Install and calibrate the device in accordance with manufacturer's procedures and specifications.
iii. At least annually,calibrate the device in accordance with the manufacturer's procedures and
specifications.
The Permittee shall be deemed in non-compliance with 15A NCAC 2D.1109 if the requirements of this
Section 2.1 A.7.p. are not complied with.
Recordkeepin¢Requirements [15A NCAC 2Q.0508(f)]
q. The Permittee shall maintain a copy of each notification and report required by this standard,including all
documentation supporting any Notification of Compliance Status.
r. The Permittee shall maintain records of performance tests,fuel analyses,or other compliance
demonstrations,CMS performance evaluations,and opacity observations.
I
Air Quality Permit No.05884T14
Page 24
s. For each required CEMS and COMS,the Permittee shall maintain the following records:
i. All required measurements needed to demonstrate compliance with a relevant standard(including,but
not limited to, 15-minute averages of CMS data,raw performance testing measurements, and raw
performance evaluation measurements,that support data that the source is required to report);
ii. A record of each period during which a CMS is malfunctioning or inoperative(including out-of-
control periods);
iii. All CMS calibration checks;and,
iv. All adjustments and maintenance performed on CMS;
t. The Permittee shall maintain records of all monitoring data and calculated averages for applicable
operating requirements such as opacity,fabric filter leak detection system alarm sounding, and sorbent
injection rate,used to demonstrate compliance with the standard.
u. For the affected boiler,the Permittee shall maintain the following records:
i. Records of monthly fuel use by each affected source,including the type(s)of fuel and amount(s)used.
ii. A copy of all calculations and supporting documentation of maximum C12,and Hg fuel input that were
conducted to demonstrate compliance with and associated emissions standards through performance
testing. Supporting documentation should include results of any fuel analyses and basis for the
estimates of maximum C12,and Hg fuel input.The Permittee may use the results from one fuel analysis
for multiple boilers and process heaters provided they are all burning the same fuel type. However,the
Permittee shall calculate C12 and Hg fuel input for each boiler and process heater.
iii. A copy of all calculations and supporting documentation of HCl and Hg emission rates that were
conducted to demonstrate compliance with the associated limits through fuel analysis. Supporting
documentation should include results of any fuel analyses and basis for the estimate of emission rate.
The Permittee may use the results from one fuel analysis for multiple boilers and process heaters
provided they are all burning the same fuel type. However,the Permittee shall calculate the emission
rate for each boiler and process heater.
The Permittee shall be deemed in noncompliance with 15A NCAC 2D .1109 if the records required in
Section 2.1 A.7. q.through u. are not kept.
Reporting Requirements [15A NCAC 2Q .0508(f)]
V. Performance Testing and Fuel Anal. For each required performance test or fuel analyses,the
Permittee shall comply with the notification and reporting requirements in General Condition JJ of
its Title V air quality permit. The Permittee shall report the results of each performance test or fuel
analyses within 60 days after such event.These reports should also include the verification that the
operating requirements for the affected boilers have not changed or provide documentation of revised
operating requirements.
w. Notification of Compliance Status. The Permittee shall submit a Notification of Compliance Status that
meets the requirements of§63.9(h)(2)(ii)before the close of business on the 60th day following the
completion of the final required performance test and/or other initial compliance demonstration. The
Notification of Compliance Status report shall contain the following information,as applicable:
i. A description of the affected source(s)including identification of which subcategory the source is in,
the capacity of the source,a description of the add-on controls used on the source description of the
fuel(s)burned,and justification for the fuel(s)burned during the performance test.
ii. Summary of the results of all performance tests,fuel analyses,and calculations conducted to
demonstrate initial compliance including all established operating limits.
iii. Identification of whether the facility is complying with the PM emission limit or the alternative TSM
emission limit.
iv. Identification of whether the facility demonstrated compliance with each applicable emission limit
through performance testing or fuel analysis, j
v. Identification of whether the facility plans to demonstrate compliance by emissions averaging.
vi. A certification signed by the Responsible Official that the facility has met all applicable emission
limits and work practice standards.
vii. A summary of the CO emissions monitoring data and the maximum CO emission levels recorded
during the performance test to show that the facility has met any applicable work practice standard in
Section 2.
viii.If the affected source fires only gaseous fuel and/or distillate fuel oil,include a certification of such
that is signed by the Responsible Official.
Air Quality Permit No.05884T14
Page 25
x. Semiannual Summary Report. The Permittee shall submit a summary report by January 30 of each
calendar year for the preceding six-month period between July and December, and July 30 of each calendar
year for the preceding six-month period between January and June. The first summary report shall be
required on January 31,2014. The report shall include the following:
i. Company name, address and facility ID number;
ii. Statement by a responsible official with that official's name,title,and signature,certifying the truth,
accuracy,and completeness of the content of the report;
iii. Date of report and beginning and ending dates of the reporting period;
iv. The total fuel use by each affected source for each calendar month within the semiannual reporting
period,including,'but not limited to,a description of the fuel and the total fuel usage amount with units
of measure;
v. A summary of the results of the annual performance tests and documentation of any operating limits
that were reestablished during this test,if applicable.
vi. A signed statement indicating that no new types of fuels were fired in the affected sources.
*The changes to 15A NCAC 213.1109:Case-by-Case MACT section described in Application 1000067.131),Permit No.05884T14)are listed as
a minor modification per 15A NCAC 2Q.0515. The compliance certification as described in General Condition P is required.Unless otherwise
notified by NC DAQ,the affected terms of this permit(excluding the permit shield as described General Condition R)for this source shall become
final on January 24,2014. Until this date,the affected permit terms herein reflect the proposed operating language that the Permittee shall operate
under pursuant to 15A NCAC 2Q.0515(f).
B. Six coal bunkers (ID Nos.ES-2A through ES-2F)and associated bagfilters(ID Nos. CD-2A through CD-
2F)
Two flyash silos with dedicated wet slurry pugmills for unloading(ID Nos.ES-3A and ES-313)and
associated binvents(ID Nos. CD-3A and CD-313)
Four ash system vacuum transport pumps(ID Nos.ES-4A through ES-41))and associated filters(ID Nos.
CD-4A through CD-41)),two bagfilters(ID Nos.CD-4E and CD-4F),and two simple cyclones(ID Nos.
CD-4G and CD-411)
The following table provides a summary of limits and/or standards for the emission source(s)described above.
Regulated Pollutant Limits/Standards Applicable Regulation
Visible emissions 20 percent opacity 15A NCAC 2D.0521
Particulate matter (ID Nos.ES-2A through ES-2F) 15A NCAC 2D .0530
Fuel bunkers for coal,tire-derived fuel,pelletized paper,
and flyash briquette handling, only
2.7x10-5 pounds per hour—each fuel bunker
(ID Nos.ES-3A and ES-313)
Flyash silos
0.032 pounds per hour—each ash silo
(ID Nos.ES-4A through ES-41))
Ash transport
0.032 pounds per hour—each ash silo pump
1. .15A NCAC 2D.0521: CONTROL OF VISIBLE EMISSIONS
I
a. Visible emissions from these sources(ID Nos.ES-2A through ES-2F,ES-3A,ES-313,and ES-4A
through ES-41))shall not be more than 20 percent opacity when averaged over a six-minute period.
However,six-minute averaging periods may exceed 20 percent opacity not more than once in any hour and
not more than four times in any 24-hour period. In no event shall the six-minute average exceed 87 percent
opacity. [15A NCAC 2D .0521(d)]
Testing[15A NCAC 2Q.0508(f)]
b. If emissions testing is required,the testing shall be performed in accordance with General Condition JJ. If
the results of this test are above the limit given in Section 2.1 B.1.a above,the Permittee shall be deemed in
Air Quality Permit No. 05884T14
Page 26
noncompliance with 15A NCAC 2D .0521.
Monitoring [15A NCAC 2Q .0508(t)]
c. To assure compliance,once a week the Permittee shall observe the emission points from these sources(ID
Nos.ES-2A through ES-2F,ES-3A,ES-311,and ES-4A through ES-4D)for any visible emissions above
normal. If visible emissions from these sources(ID Nos.ES-2A through ES-2F,ES-3A,ES-313,and ES-
4A through ES-4D)are observed to be above normal,the Permittee shall:
i. take appropriate action to correct the above-normal emissions within the monitoring period and record
the action taken as provided in the recordkeeping requirements below,or
ii. demonstrate that the percent opacity from the emission points of the emission sources (ID Nos. ES-2A
through ES-2F, ES-3A, ES-311, and ES-4A through ES-4D) in accordance with 15A NCAC 02D
.2610(Method 9)for 12 minutes is below the limit given in Section 2.1 B.La.above.
If the above-normal emissions are not corrected per i.above or if the demonstration in ii.above cannot be
made,the Permittee shall be deemed to be in noncompliance with 15A NCAC 2D.0521.
Recordkeeping [15A NCAC 2Q.0508(t)]
d. The results of the monitoring shall be maintained in a logbook(written or electronic format)on site and
made available to an authorized DAQ representative upon request. The logbook shall record the following:
i. the date and time of each recorded action;
ii. the results of each observation and/or test noting those sources with emissions that were observed to be
in noncompliance along with any corrective actions taken to reduce visible emissions;and
iii. the results of any corrective actions performed.
The Permittee shall be deemed in noncompliance with 15A NCAC 2D .0521 if these records are not
maintained.
Reporting[15A NCAC 2Q.0508(t)]
e. The Permittee shall submit a summary report of the observations postmarked on or before January 30 of
each calendar year for the preceding six-month period between July and December and July 30 of each
calendar year for the preceding six-month period between January and June. All instances of deviations
from the requirements of this permit must be clearly identified.
2. 15A NCAC 2D.0530: PREVENTION OF SIGNIFICANT DETERIORATION
a. When handling coal,tire-derived fuel,pelletized paper,and/or flyash briquettes,particulate matter
emissions from each source(ID Nos.ES-2A through ES-2F)shall not exceed 2.7x10-5 pounds per hour.
b. Particulate matter emissions from each source(ID Nos.ES-3A and ES-313)shall not exceed 0.032 pounds
per hour.
c. Particulate matter emissions from each source(ID Nos.ES-4A through ES-4D)shall not exceed 0.032
pounds per hour.
Monitoring/Recordkeeping[15ANCAC 2Q .0508(t)]
d. Particulate matter emissions from these emission sources(ID Nos.ES-2A through ES-2F,ES-3A,ES-313,
and ES-4A through ES-41))shall be controlled by eight bagfilters(ID Nos.CD-2A through CD-2F,CD-
4E and CD-4F),two simple cyclones(ID Nos.CD-4G and CD-411),two binvents(ID Nos.CD-3A and
CD-311),and four in-line filters(ID Nos. CD-4A through CD-4D)as described above. To assure
compliance,the Permittee shall perform inspections and maintenance as recommended by the
manufacturers. In addition to the manufacturer's inspection and maintenance recommendations or if there
are no manufacturer's inspection and maintenance recommendations,as a minimum,the inspection and
maintenance requirement shall include the following:
i. an annual(for each 12 month period following the initial inspection)internal inspection of the simple
cyclones structural integrity;and
ii. an annual(for each 12 month period following the initial inspection)internal inspection of the
bagfdters/binvents/in-line filters for structural and fabric filter integrity.
The Permittee shall be deemed in noncompliance with 15A NCAC 2D .0530 if the binvents,cyclones,in-
line filters,and bagfilters are not inspected and maintained.
e. The results of inspection and maintenance shall be maintained in a logbook(written or electronic format)on
Air Quality Permit No.05884T14
Page 27
site and made available to an authorized DAQ representative upon request. The logbook shall record the
following:
i. the date and time of each recorded action;
ii. the results of each inspection;
iii. the results of any maintenance performed on the control devices;and
iv. any variance from manufacturer's recommendations,if any,and corrections made.
The Permittee shall be deemed in noncompliance with 15A NCAC 2D .0530 if these records are not
maintained.
Reporting[15A NCAC 2Q .0508(f)]
f. Upon request from the DAQ,the Permittee shall submit,within 30 days of such request,a report of any j
maintenance performed on a control device.
g. The Permittee shall submit a summary report of the monitoring and recordkeeping postmarked on or before
January 30 of each calendar year for the preceding six-month period between July and December and July
30 of each calendar year for the preceding six-month period between January and June. All instances of
deviations from the requirements of this permit must be clearly identified.
C. Coal unloading/storage and transfer operations(ID No.ES-5)and associated wet suppression system(ID
No.Wetsup)
The following table provides a summary of limits and/or standards for the emission source(s)described above.
Regulated Pollutant Limits/Standards Applicable Regulation
Visible emissions 20 percent opacity 15A NCAC 2D .0521
Particulate matter Wet suppression shall be used on the following: 15A NCAC 2D .0530
-rail car unloading
-coal pile load-in/out
-wind erosion coal piles
1. 15A NCAC 2D.0521: CONTROL OF VISIBLE EMISSIONS
a. Visible emissions from this source(ID No.ES-5)shall not be more than 20 percent opacity when averaged
over a six-minute period. However,six-minute averaging periods may exceed 20 percent opacity not more
than once in any hour and not more than four times in any 24-hour period. In no event shall the six-minute
average exceed 87 percent opacity. [15A NCAC 2D .0521(d)]
Testing[15A NCAC 2Q.0508(f)]
b. If emissions testing is required,the testing shall be performed in accordance with General Condition JJ. If
the results of this test are above the limit given in Section 2.1 C.1.a above,the Permittee shall be deemed in
noncompliance with 15A NCAC 2D .0521.
Monitoring [15A NCAC 2Q.0508(f)]
c. To assure compliance, once a week the Permittee shall observe this source(ID No.ES-5)for any visible
emissions above normal. If visible emissions from this source(ID No.ES-5)are observed to be above
normal,the Permittee shall:
i. take appropriate action to correct the above-normal emissions within the monitoring period and record
the action taken as provided in the recordkeeping requirements below,or
ii. demonstrate that the percent opacity from the emission points of the emission source (ID No. ES-5)in
accordance with 15A NCAC 02D .2610 (Method 9)for 12 minutes is below the limit given in Section
2.1 C.La.above.
If the above-normal emissions are not corrected per i. above or if the demonstration in ii. above cannot be
made,the Permittee shall be deemed to be in noncompliance with 15A NCAC 2D .0521.
Recordkeeping[15A NCAC 2Q.0508(f)]
d. The results of the monitoring shall be maintained in a logbook(written or electronic format)on site and
made available to an authorized DAQ representative upon request. The logbook shall record the following:
Air Quality Permit No. 05884T14
Page 28
i. the date and time of each recorded action;
ii. the results of each observation and/or test noting those sources with emissions that were observed to be
in noncompliance along with any corrective actions taken to reduce visible emissions;and
iii. the results of any corrective actions performed.
The Permittee shall be deemed in noncompliance with 15A NCAC 2D .0521 if these records are not
maintained.
Reporting[15A NCAC 2Q.0508(f)]
e. The Permittee shall submit a summary report of the observations postmarked on or before January 30 of
each calendar year for the preceding six-month period between July and December and July 30 of each
calendar year for the preceding six-month period between January and June. All instances of deviations
from the requirements of this permit must be clearly identified.
2. 15A NCAC 2D.0530: PREVENTION OF SIGNIFICANT DETERIORATION
a. The Permittee shall employ wet suppression on the rail car unloading,the coal pile load-in/out,and the
wind erosion coal piles. [15A NCAC 2D .0530]
Monitoring[15A NCAC 2Q .0508(f)]
b. Particulate matter emissions from this emission source(ID Nos.ES-5)shall be controlled by wet
suppression(ID No.Wetsup). To assure compliance,the Permittee shall perform inspections and
maintenance on the wet suppression system(ID No.Wetsup)as recommended by the manufacturer. In
addition to the manufacturer's inspection and maintenance recommendations,or if there are no
manufacturer's inspection and maintenance recommendations,as a.minimum,the inspection and
maintenance requirement shall include a monthly external inspection of the system for integrity of piping
and nozzles. The Permittee shall be deemed in noncompliance with 15A NCAC 2D.0530 if the system is
not inspected and maintained.
Recordkeeping [15A NCAC 2Q .0508(f)]
c. A wet suppression log shall be maintained indicating areas and dates wet suppression was applied. No
reporting is required-but the log shall be made available to a DAQ representative upon request. The
Permittee shall be deemed in noncompliance with 15A NCAC 2D .0530 if the wet suppression log is not
maintained.
d. The results of inspection and maintenance activities shall be maintained in a logbook(written or electronic
format)onsite and made available to an authorized representative upon request. The logbook shall record
the following:
i. the date and time of each recorded action;
ii. the results of each action or inspection;
iii. a report of any maintenance performed on the wet suppression system(ID No.Wetsup);and
iv. any variance from manufacturer's recommendations,if any,and corrections made.
The Permittee shall be deemed in noncompliance with 15A NCAC 2D .0530 if these records are not
maintained.
Reporting[15A NCAC 2Q .0508(f)]
e. Within 30 days of a written request from the DAQ,the Permittee shall submit a report of any maintenance
performed on the wet suppression system(ID No.Wetsup).
f. The Permittee shall submit a summary report of monitoring and recordkeeping activities postmarked on or
before January 30 of each calendar year for the preceding six-month period between July and December and
July 30 of each calendar year for the preceding six-month period between January and June. All instances
of deviations from the requirements of this permit must be clearly identified.
D. Two cooling towers(ID Nos.ES-8A and ES-8B)
The following table provides a summary of limits and standards for the emission source(s)described above:
Air Quality Permit No.05884T14
Page 29
-Regulated Pollutant Limits/Standards Applicable Regulation
particulate matter E=4.10 x P ' for P <30 15A NCAC 2D .0515
tons/hr
or
E=55.0 x P 0-"-40 for P>30 tons/hr
where:
E= allowable emission rate in pounds per hour
P= process weight rate in tons per hour
1. 15A NCAC 2D.0515: PARTICULATES FROM MISCELLANEOUS INDUSTRIAL PROCESSES
a.. Emissions of particulate matter from these sources (ID Nos. ES-8A and ES-813) shall not exceed an
allowable emission rate as calculated by the following equation: [15A NCAC 2D.0515(a)]
E=4.10 x P 0.61 for P 530 tons per hour
or
E=55.0 x Po-"_40 for P>30 tons per hour
where E=allowable emission rate in pounds per hour
P=process weight in tons per hour
Liquid and gaseous fuels and combustion air are not considered as part of the process weight.
Testing[15ANCAC 2Q.0508(f)]
b. If emissions testing is required,the testing shall be performed in accordance with General Condition JJ. If
the results of this test are above the limit given in 2.1 D.1.a. above, the Permittee shall be deemed in
noncompliance with 15A NCAC 2D .0515.
Monitoring/Recordkeeoing/Reporting[15A NCAC 2Q.0508(f)]
C. No monitoringtrecordkeepingtreporting is required for particulate matter emissions from these
sources.
E.
E. Two alkaline sorbent (limestone/lime/trona) silos (ID Nos. ES-9A and ES-911) and associated vent
fabric filters(ID Nos. CD-9A and CD-9B)
The following table 2rovides a surninary of limits and standards for the emission source(s)described above:
Regulated Limits/Standards Applicable Regulation'
Pollutant
particulate E=4.10 P.6 15A NCAC 2D.0515
matter where:
E=allowable particulate emission rate in pounds per hour
P=process weight rate in tons per hour
visible 20 percent opacity(except during startups,shutdowns,and 15A NCAC 2D .0521
emissions malfunctions)when averaged over a six-minute period
except that six-minute periods averaging not more than 87
percent opacity may occur not more than once in any hour
nor more than four times in any 24-hour period.
1. 15A NCAC 2D.0515: PARTICULATES FROM MISCELLANEOUS INDUSTRIAL PROCESSES
a. Emissions of particulate matter from these sources. (ID Nos. ES-9A and ES-913) shall not exceed an
allowable emission rate as calculated by the following equations: [15A NCAC 2D .0515(a)]
I
Air Quality Permit No. 05884T14
Page 30
0.67
E=4.10 x P Where E=allowable emission rate in pounds per hour
P=process weight in tons per hour
Liquid and gaseous fuels and combustion air are not considered as part of the process weight.
Testing[15A NCAC 2Q.0508(f)]
b. If emissions testing is required,the testing shall be performed in accordance with General Condition JJ. If
the results of this test are above the limit given in Section 2.1 E. 1. a. above,the Permittee shall be deemed
in noncompliance with 15A NCAC 2D .0515.
Monitoring/Recordkeeping[15A NCAC 2Q.0508(f)]
c. Particulate matter emissions from the silos(ID Nos.ES-9A and ES-913)shall be controlled by the bagfilters
(ID Nos. CD-9A and CD-913). To assure compliance, the Permittee shall perform inspections and
maintenance as recommended by the manufacturer. In addition to the manufacturer's inspection and
maintenance recommendations, or if there is no manufacturer's inspection and maintenance
recommendations,as a minimum,the inspection and maintenance requirement shall include the following:
i. a monthly visual inspection of the system ductwork and material collection unit for leaks;and
ii. an annual (for each 12 month period following the initial inspection) internal inspection of the
bagfilter's structural integrity.
The Permittee shall be deemed in noncompliance with 15A NCAC 2D .0515 if the ductwork and bagfilters
are not inspected and maintained.
d. The results of inspection and maintenance shall be maintained in a logbook(written or electronic format)
on-site and made available to an authorized representative upon request. The logbook shall record the
following:
i. the date and time of each recorded action;
ii. the results of each inspection;
iii. the results of any maintenance performed on the bagfilters;and
iv. any variance from manufacturer's recommendations,if any,and corrections made.
The Permittee shall be deemed in noncompliance with 15A NCAC 2D .0515 if these records are not
maintained.
Reporting[15A NCAC 2Q.0508(f)]
e. The Permittee shall submit the results of any maintenance performed on the bagfilters within 30 days of a
written request by the DAQ.
f. The Permittee shall submit a summary report of monitoring and recordkeeping activities postmarked on or
before January 30 of each calendar year for the preceding six-month period between July and December
and July 30 of each calendar year for the preceding six-month period between January and June. All
instances of deviations from the requirements of this permit must be clearly identified.
2. 15A NCAC 2D.0521: CONTROL OF VISIBLE EMISSIONS
a. Visible emissions from these sources (ID Nos. ES-9A and ES-913) shall not be more than 20 percent
opacity when averaged over a six-minute period. However, six-minute averaging periods may exceed 20
percent not more than once in any hour and not more than four times in any 24-hour period. In no event
shall the six-minute average exceed 87 percent opacity. [15A NCAC 2D .0521 (d)]
Testing[15A NCAC 2Q .0508(f)]
b. If emissions testing is required,the testing shall be performed in accordance with General Condition JJ. If
the results of this test are above the limit given in Section 2.1 E.2.a. above,the Permittee shall be deemed in
noncompliance with 15A NCAC 2D .0521.
Monitoring [15A NCAC 2Q .0508(f)]
c. To assure compliance, once a month the Permittee shall observe the emission point of these sources (ID
Nos. ES-9A and ES-913) for any visible emissions above normal when these source are operating. The
Permittee shall establish"normal" for these sources in the first 30 days following the start-up. If visible
emissions from these sources are observed to be above normal,the Permittee shall either:
Air Quality Permit No. 05884T14
Page 31
i. take appropriate action to correct the above-normal emissions as soon as practicable and within the
monitoring period and record the action taken as provided in the recordkeeping requirements below,or
ii. demonstrate that the percent opacity from the emission points of the emission sources in accordance
with 15A NCAC 2D .2610 (Method 9) for 12 minutes is below the limit given in Section 2.1 E.2.a.
above.
If the above-normal emissions are not corrected per(i)above or if the demonstration in(ii)above cannot be
made,the Permittee shall be deemed to be in noncompliance with 15A NCAC 2D.0521.
2.2- Multiple Emission Sources
A. Facility Wide
The following table provides a summary of limits and standards for the emission source(s)described above:
Regulated Limits/Standards Applicable Regulation
Pollutant
toxic air pollutants See Section 2.2 A.1. -State Only Requirement 15A NCAC 2Q.0700
toxic air pollutants See Section 2.2 A.2.-State Only Requirement 15A NCAC 2D .1100
State Only Requirement
1. 15A NCAC 2Q.0700: TOXIC AIR POLLUTANT PROCEDURES
a. The Permittee is allowed to burn the following as supplemental fuels in these sources(El)Nos.ES-14A,
ES-1-1111,ES-14C,ES-24A,ES-2-111 and ES-2-1C)provided that the wastes are generated at this plant-
site and are combusted under conditions of high fire producing high steam demand:
i. waste water basin/evaporation pit sludge of a maximum feed rate of 1%by weight not to exceed 20
tons per year,
ii. spent demineralizer resin;
iii. activated carbon filters from the water treatment process not to exceed 10 tons per year,and
iv. EDTA boiler cleaning solution with a maximum injection rate of 10 gallons per minute of the solution
per 100,000 pounds of steam flow not to exceed 35,000 gallons per year.
b. The Permittee may use the following for normal start-up of these sources(ID Nos.ES-14A,ES-1-1111,ES-
14C,ES-24A,ES-2-111 and ES-2-1C)provided that the oil is generated at this plant-site:
i. unadulterated oil soaked rags,
ii. used oil absorbents,
iii. used/fuel oil soaked rags,and
iv. used oil soaked wood chips.
c. The Permittee may burn"regenerated"spent cation/anion resins [spent demineralizer resin] in these sources
(ID Nos.ES-14A,ES-1-111,ES-14C,ES-24A,ES-2-111 and ES-24C)once the following conditions
have been met:
i. testing adequate to determine the quantity and type of any toxic materials listed in 15A NCAC 2Q
.0711 shall be performed. The results shall be forwarded to the Wilmington Regional Office
Supervisor,Division of Air Quality.
ii. the Permittee shall request and obtain written permission from the Wilmington Regional Office
Supervisor,Division of Air Quality,prior to burning the resins.
iii. Combustion of these plant wastes will occur with the following limitations:
A. wastes are generated from this plant-site,
B. wastes are combusted in these sources(11)Nos.ES-14A,ES-1-111,ES-14C,ES-24A,ES-2-111
and ES-2-1C)operating under conditions of high fire producing high steam demand,
d. Combustion of these plant wastes will occur with the following limitations that the maximum amount of
"regenerated"spent cation/anion resins[spent demineralizer resin] shall not exceed 40 tons per year.
e. To comply with this permit and avoid the applicability of 15A NCAC 2Q.0706,"Modifications"as
requested by the Permittee,toxic pollutant emissions from the firing of the alternative fuel flyash briquettes
in these sources(ID Nos.ES-14A,ES-1-1111,ES-14C,ES-24A,ES-2-111 and ES-24C)shall be less
Air Quality Permit No.05884T14
Page 32
than the emissions from the firing of coal in theses sources(ID Nos.ES-1-1A,ES-1-1B,ES-1-1C,ES-2-
1A,ES-2-1B and ES-24C). To ensure enforceability of this limit,flyash briquettes will be fired only
during low steam demand conditions defined to be:
i, when the plant is dispatched off-line(no electrical generation produced for the utility),and
ii. steam production limit of 80,000 pounds steam per hour.
f. Pursuant to 15A NCAC 2Q .0711, for each of the below listed toxic air pollutants (TAPS), the Permittee has
made a demonstration that facility-wide actual emissions do not exceed the Toxic Permit Emission Rates
(TPERS) listed in 15A NCAC 2Q .0711. The facility shall be operated and maintained in such a manner
that emissions of any listed toxic air pollutant(s) from the facility, including fugitive emissions, will not
exceed the toxic permit emission rate(s)(TPERs)specified in 15A NCAC 2Q.0711.
i. A permit to emit any of the below listed TAPS shall be required for this facility if actual emissions
from all sources will become greater than the corresponding TPER.
ii. PRIOR to exceeding any of these listed TPERs, the Permittee shall be responsible for obtaining a
permit to emit TAPS and for demonstrating compliance with the requirements of 15A NCAC 2D.1100.
iii. In accordance with the approved application,the Permittee shall maintain records of operational
information demonstrating that the toxic air pollutant emissions do not exceed the TPER(s)as
listed below:
TPER
Limitations
Pollutant Creinogens Chronic Toxicants: Acute Systemic Acute
(CAS.Number) (lb/day) Toxicants Irritants
lb/hr) lli/hr
acetaldehyde(75-07-0) 6.8
benzyl chloride(100-44-7) 0.13
di(2-ethylhexyl)phthalate 0.63
(117-81-7
carbon disulfide(75-15-0) 3.9
carbon tetrachloride(56-23-5) 460
chlorobenzene(108-90-7) 46
chloroform(67-66-3) 290
dimethyl sulfate(77-78-1) 0.063
ethylene dibromide(106-93-4) 27
ethylene dichloride(107-06-2) 260
n-hexane(110-54-3) 23
methyl ethyl ketone(78-93-3) 78 22.4
methylene chloride(75-09-2) 1600 0.39
methyl chloroform(71-55-6) 250 64
pentachlorophenol(87-86-5) 0.063 0.0064
phenol(108-95-2) 0.24
styrene(100-42-5) 2.7
tetrachlorodibenzo-p-dioxin 0.00020 i
(1746-01-6)
toluene(108-88-3) 98 14.4
trichloroethylene(79-01 6) 4000
xylene(1330-20-7) 57 16.4
I
Monitorinz/Recordkeepin 15A NCAC 2Q.0508(f)]
g. Prior to using any used oil absorbents the Permittee shall submit an analysis of the oil for an unadulterated
equivalency determination. This equivalency determination need only be submitted and approved once for
each oil type. The Permittee shall maintain records on site of DAQ approved equivalent oils.
h. The Permittee shall maintain a wastewater sludge combustion logbook onsite with the following
information: i
i. date of wastewater sludge combustion;
I
Air Quality Permit No.05884T14
Page 33
ii. feed rate of wastewater sludge to these sources(ID Nos.ES-1-IA,ES-1-1B,ES-1-IC,ES-2-JA,ES-2-
1B and ES-24C);
iii. quantity of wastewater sludge combusted in these sources(ID Nos.ES-14A,ES-14B,ES-1-1C,ES-
2-1A,ES-24B and ES-24C);and
iv. feed rate of coal to these sources(ID Nos.ES-14A,ES-1-1B,ES-14C,ES-24A,ES-24B and ES-2-
1 C).
i. The Permittee shall maintain a plant waste fuel start-up logbook onsite with the following information:
i. date of start-up,
ii. hours of start-up,and
iii. quantity and type of materials used when plant wastes are used to start-up these sources(ID Nos.ES-1-
1A,ES-14B,ES-14C,ES-24A,ES-24B and ES-24C).
j. The Permittee shall maintain a plant waste combustion logbook onsite with the following information:
i. date of plant waste combustion,
ii. type of plant waste combusted,
iii. quantity of waste materials combusted,
iv, feed rate of plant waste to these sources(ID Nos.ES-14A,ES-1-1B,ES-1-1C,ES-2-1A,ES-24B
and ES-24C),
v. feed rate of coal to these sources(ID Nos.ES-1-1A,ES-14B,ES-1-1C,ES-24A,ES-2-1B and ES-2-
1 C), and
vi. documentation of any feed rate limitation, if applicable.
k. The Permittee shall maintain a pelletized paper fuel(PPF)combustion logbook onsite with the following
information:
i. date of PPF combustion,
ii. description of PPF combusted,
iii. quantity of PPF combusted,
iv. feed rate of PPF to these sources(ID Nos.ES-1-1A,ES-14B,ES-1-1C,ES-24A,ES-24B and ES-2-
1 C),
v. feed rate of coal to these sources(ID Nos.ES-1-1A,ES-1-1B,ES-1-IC,ES-24A,ES-2-1B and ES-2-
1C),and
vi. documentation of compliance with any applicable feed rate limitation.
1. The Permittee shall maintain a flyash briquette combustion logbook onsite with the following information:
i. daily quantity of flyash briquettes combusted,
ii. maximum hourly steam demand during the hours of flyash briquettes combustion for that day,and
iii. daily recordkeeping is only required on days in which briquettes are burned.
in. The Permittee shall be deemed in noncompliance with 15A NCAC 2Q.0700 if the monitoring and
recordkeeping requirements of Section 2.1 A.6.a through 2.1 A.6.m. above,are not maintained.
Reporting [15A NCAC 2Q .0508(f)]
n. . Within 30 days after each calendar year,the following shall be reported:
i. the total amount of the flyash briquettes burned,and
ii. the chemical composition datasheet and/or MSDS for each shipment of flyash briquettes received
during that calendar year.
o. Prior to combustion for the first time,the Permittee shall submit an analysis of the used oil and
unadulterated oil equivalency determination for approval.
p. Within 30 days after the end of each calendar year,the Permittee shall submit a report of the number of
gallons of used oil combusted and an analysis of the used oil.
q. Within 30 days after the initial use of each of these permitted alternative fuels and plant wastes,the
Permittee shall submit in writing the type of fuel or plant waste,and the date in which the material was first
used in these sources(ID Nos.ES-14A,ES-14B,ES-14C,ES-24A,ES-2-1B and ES-24C).
State-Only Requirement
2. 15A NCAC 2D.1100: CONTROL OF TOXIC AIR POLLUTANTS
a. Pursuant to 15A NCAC 2D .1100 and in accordance with the approved application for an air toxic
compliance demonstration,the following permit limits shall not be exceeded when burning tire-derived fuel
(TDF)in boilers(ID Nos.ES-14A,ES-1-1B,ES-1-1C,ES-24A,ES-24B and ES-24C):
Air Quality Permit No.05884T14
Page 34
Emission Source Toxic Air Emission Limit
Pollutants
Facility-wide Emission Sources acrolene 101 lbs per hour
ammonia 3,418 lbs per hour
arsenic 122.5 lbs per year
beryllium 2,184.1 lbs per year
benzo(a)pyrene 17,579.2 lbs per year
cadmium 2,929.9 lbs per year
formaldehyde 190 lbs per hour
hydrogen 886 lbs per hour
chloride
hydrogen 316 lbs per hour
fluoride 3,164.91bs per day
manganese 3,270.41bs per day
nickel 633 lbs per day
soluble chromate 65.4 lbs per day
compounds,as
chromium(VI)
equivalent
sulfuric acid mist 127 lbs per hour
1,266.0 lbs per day
vinyl chloride 202,427 lbs per year
Testing[15A NCAC 2Q.0508(f)]
b. No stack testing is required.
Monitoring/Recordkeeping/Reporting 15A NCAC 2D .1105]
C. No monitoring/recordkeeping/reporting is required.
I
Air Quality Permit No.05884T14
Page 35
2.3 - Clean Air Interstate Rule (CAIR) Permit Requirements
ORIS code: 10378
The following sources are affected CAIR units:
CAIR ID No.
ES-14A
ES-1-1B
ES-14 C
ES-24 A
ES-2-1 B
ES-2-1 C
A. 15A NCAC 2D.2403: NITROGEN OXIDE EMISSIONS
1. The total nitrogen oxide (NOx) emissions from the affected CAIR units listed above at the CPI USA North
Carolina-Southport Plant shall not exceed, except as provided in 15A NCAC 2D .2408: [15A NCAC 2D
.2403]
a. 401 tons annually for 2009-2014
b. 341 tons annually for 2015 and later
If any of the CAIR sources listed above is a new source for which allocations have not been included in the
table in 15A NCAC 2D.2403,the CAIR designated representative may submit a request to be allocated CAIR
NOx allowances for those sources using the procedures in 40 CFR 96.142(c)(2)and(3).
2. The affected CAIR NOx sources shall comply with the requirements of 15A NCAC 2D.2400 using the trading
program and banking set out in 40 CFR Part 96.[15A NCAC 2D.2408]
3. The owner or operator of any unit or source covered under 15A NCAC 2D .2403 shall be subject to the
provisions of 40 CFR 96.106(f). [15A NCAC 2D.2403]
Monitoring/Recordkeepin2/Reportin [15A NCAC 2D.2403 and 15A NCAC 2D.2407(a)(1)]
4. The Permittee shall comply with the monitoring, recordkeeping, and reporting requirements in 40 CFR
96.106(b)and(e),and 40 CFR 96 Subpart HH for each CAIR NOx unit.
5. The emissions of nitrogen oxides of a CAIR NOx source shall not exceed the number of allowances that it
has in its compliance account established and administered under 15A NCAC 2D.2408.
6. The emissions measurements recorded and reported according to 40 CFR Part 96 Subpart HH shall be used to
determine compliance by each CAIRNOx source with its emissions limitation according to 40 CFR 96.106(c)
including 96.106(c)(5)and(6).
7. The provisions of 40 CFR 96.106(d)shall be used for excess emissions.
B. 15A NCAC 2D.2405: NITROGEN OXIDE EMISSIONS DURING OZONE SEASON I
I
1. Ozone season NOx emissions from the affected CAIR units listed above at the CPI USA North Carolina-
Southport Plant shall not exceed, except as provided in 15A NCAC 2D .2408: [15A NCAC 2D .2405(a)(1)
and(b)]
a. 213 tons during the ozone season for 2009-2014;and
b. 181 tons during the ozone season for 2015 and later
The ozone season shall be defined as the period of time extending from May I"to September 300' of each
calendar year. If any of the CAIR sources listed above is a new source for which allocations have not been
included in the table in 15A NCAC 2D.2405,the CAIR designated representative may submit a request to be
allocated CAIR NOx ozone season allowances for those sources using the procedures in 40 CFR 96.342(c)(2)
and(3).
I
I
Air Quality Permit No.05884T14
Page 36
2. The affected CAIR NOx Ozone Season sources shall comply with the requirements of 15A NCAC 2D .2400
using the trading program and banking set out in 40 CFR Part 96.[15A NCAC 2D.2408]
3. The owner or operator of any unit or source covered under 15A NCAC 2D .2405 shall be subject to the
provisions of 40 CFR 96.306(f). [15A NCAC 2D.2405]
Monitoring/Recordkeeping/Reporting[15A NCAC 2D.2405 and 15A NCAC 2D.2407(a)(3)]
4. The Permittee shall comply with the monitoring, recordkeeping, and reporting requirements in 40 CFR
96.306(b)and(e),and 40 CFR 96 Subpart HHHH for each CAIR Ozone Season NOx unit.
5. The nitrogen oxide ozone season emissions of a CAIR NOx Ozone Season source shall not exceed the
number of allowances that it has in its compliance account established and administered under 15A NCAC 2D
.2408.
6. The emissions measurements recorded and reported according to 40 CFR Part 96 Subpart HHHH shall be
used to determine compliance by each CAIR NOx Ozone Season source with its emissions limitation
according to 40 CFR 96.306(c) including 96.306(c)(5)and(6).
7. The provisions of 40 CFR 96.306(d)shall be used for excess emissions.
C. 15A NCAC 2D.2404: SULFUR DIOXIDE EMISSIONS
1. The annual allocation of sulfur dioxide allowances shall be determined by EPA.The allocations for
CAIR SO2 units are listed in the table below (these allocations are from 40 CFR 73.10 except where none is
given):
ALLOCATION
CAIR ID No. FOR
2010 AND LATER
ES-14A none
ES-14 B none
ES-1-1C none
ES-2-1 A none
ES-2-1 B none
ES-2-1 C none
2. The affected CAIR SO2 sources shall comply with the requirements of 15A NCAC 2D.2400 using the trading
program and banking set out in 40 CFR Part 96. [15A NCAC 2D.2408]
3. The owner or operator of any unit or source covered under 15A NCAC 2D .2404 shall be subject to the
provisions of 40 CFR 96.206(1). [15A NCAC 2D.2404]
Monitoring/Recordkeeping/Reporting[15A NCAC 2D.2404 and 15A NCAC 2D.2407(a)(2)]
4. The Permittee shall comply with the monitoring, recordkeeping, and reporting requirements in 40 CFR
96.206(b)and(e),and 40 CFR 96 Subpart HHH for each CAIR SO2 unit.
5. The emissions of sulfur dioxides of each CAIR SO2 source shall not exceed the number of allowances that it
has in its compliance account established and administered under Rule 15A NCAC 2D.2408.
6. The emissions measurements recorded and reported according to 40 CFR Part 96 Subpart HHH shall be used to
determine compliance by each CAIR SO2 source with its emissions limitation according to 40 CFR 96.206(c)
including 96.206(c)(5)and(6).
7. The provisions of 40 CFR 96.206(d)shall be used for excess emissions.
D. CAIR Permit Application
I
The permit application submitted for this facility, as approved by the Department of Environment and Natural
Resources,Division of Air Quality, is part of this permit. The owner and operator of these CAIR NOx and SO2
sources must comply with the standard requirements and special provisions set forth in the following attached
application:
Air Quality Permit No.05884T14
Page 37
CAIR Permit Application dated April 26,2011
I
I
- I
I
I
i
Air Quality Permit No. 05884T14
Page 38
SECTION 3 - GENERAL CONDITIONS (version 3.6)
This section describes terms and conditions applicable to this Title V facility.
A. General Provisions[NCGS 143-215 and 15A NCAC 2Q.0508(i)(16)]
1. Terms not otherwise defined in this permit shall have the meaning assigned to such terms as defined in 15A
NCAC 2D and 2Q.
2. The terms, conditions, requirements, limitations, and restrictions set forth in this permit are binding and
enforceable pursuant to NCGS 143-215.114A and 143-215.114B, including assessment of civil and/or
criminal penalties.Any unauthorized deviation from the conditions of this permit may constitute grounds for
revocation and/or enforcement action by the DAQ.
3. This permit is not a waiver of or approval of any other Department permits that may be required for other
aspects of the facility which are not addressed in this permit.
4. This permit does not relieve the Permittee from liability for harm or injury to human health or welfare,animal
or plant life, or property caused by the construction or operation of this permitted facility, or from penalties
therefore, nor does it allow the Permittee to cause pollution in contravention of state laws or rules, unless
specifically authorized by an order from the North Carolina Environmental Management Commission.
5. Except as identified as state-only requirements in this permit, all terms and conditions contained herein shall
be enforceable by the DAQ, the EPA, and citizens of the United States as defined in the Federal Clean Air
Act.
6. Any stationary source of air pollution shall not be operated,maintained, or modified without the appropriate
and valid permits issued by the DAQ,unless the source is exempted by rule. The DAQ may issue a permit
only after it receives reasonable assurance that the installation will not cause air pollution in violation of any
of the applicable requirements. A permitted installation may only be operated, maintained, constructed,
expanded,or modified in a manner that is consistent with the terms of this permit.
B. Permit Availability[15A NCAC 2Q.0507(k)and.0508(i)(9)(B)]
The Permittee shall have available at the facility a copy of this permit and shall retain for the duration of the permit
term one complete copy of the application and any information submitted in support of the application package. -
The permit and application shall be made available to an authorized representative of Department of Environment
and Natural Resources upon request.
C. Severability Clause[15A NCAC 2Q.0508(i)(2)]
In the event of an administrative challenge to a final and binding permit in which a condition is held to be invalid,
the provisions in this permit are severable so that all requirements contained in the permit,except those held to be
invalid,shall remain valid and must be complied with.
D. Submissions[15A NCAC 2Q.0507(e)and 2Q .0508(i)(16)]
Except as otherwise specified herein,two copies of all documents,reports,test data,monitoring data,notifications,
request for renewal, and any other information required by this permit shall be submitted to the appropriate j
Regional Office. Refer to the Regional Office address on the cover page of this permit. For continuous emissions
monitoring systems (CEMS)reports, continuous opacity monitoring systems (COMS)reports, quality assurance
(QA)/quality control(QC)reports,acid rain CEM certification reports,and NOx budget CEM certification reports,
one copy shall be sent to the appropriate Regional Office and one copy shall be sent to:
i
Supervisor,Stationary Source Compliance
North Carolina Division of Air Quality
1641 Mail Service Center
Raleigh,NC 27699-1641
All submittals shall include the facility name and Facility ID number(refer to the cover page of this permit).
I
E. Duty to Comply[15A NCAC 2Q.0508(i)(2)]
j
Air Quality Permit No. 05884T14
Page 39
The Permittee shall comply with all terms, conditions, requirements, limitations and restrictions set forth in this
permit. Noncompliance with any permit condition except conditions identified as state-only requirements
constitutes a violation of the Federal Clean Air Act. Noncompliance with any permit condition is grounds for
enforcement action, for permit termination, revocation and reissuance, or modification, or for denial of a permit
renewal application.
F. Circumvention-STATE ENFORCEABLE ONLY
The facility shall be properly operated and maintained at all times in a manner that will effect an overall reduction
in air pollution. Unless otherwise specified by this permit, no emission source may be operated without the
concurrent operation of its associated air pollution control device(s)and appurtenances.
G. Permit Modifications
1. Administrative Permit Amendments[I 5A NCAC 2Q.0514]
The Permittee shall submit an application for an administrative permit amendment in accordance with 15A
NCAC 2Q.0514.
2. Transfer in Ownership or Operation and Application Submittal Content [15A NCAC 2Q.0524 and 2Q.0505]
The Permittee shall submit an application for an ownership change in accordance with 15A NCAC 2Q.0524
and 2Q.0505.
3. Minor Permit Modifications[15A NCAC 2Q.0515]
The Permittee shall submit an application for a minor permit modification in accordance with 15A NCAC 2Q
.0515.
4. Significant Permit Modifications[15A NCAC 2Q.0516]
The Permittee shall submit an application for a significant permit modification in accordance with 15A NCAC
2Q.0516.
5. Reopening for Cause[15A NCAC 2Q.0517]
The Permittee shall submit an application for reopening for cause in accordance with 15A NCAC 2Q.0517.
H. Changes Not Requiring Permit Modifications
1. Reporting Requirements
Any of the following that would result in new or increased emissions from the emission source(s) listed in
Section 1 must be reported to the Regional Supervisor,DAQ:
a. changes in the information submitted in the application;
b. changes that modify equipment or processes;or
c. changes in the quantity or quality of materials processed.
If appropriate, modifications to the permit may then be made by the DAQ to reflect any necessary changes in the
permit conditions. In no case are any new or increased emissions allowed that will cause a violation of the
emission limitations specified herein.
2. Section 502(b)(10)Changes[15A NCAC 2Q.0523(a)]
a. "Section 502(b)(10) changes" means changes that contravene an express permit term or condition. Such
changes do not include changes that would violate applicable requirements or contravene federally
enforceable permit terms and conditions that are monitoring (including test methods), recordkeeping,
reporting,or compliance certification requirements.
b. The Permittee may make Section 502(b)(10)changes without having the permit revised if:
i. the changes are not a modification under Title I of the Federal Clean Air Act;
ii. the changes do not cause the allowable emissions under the permit to be exceeded;
iii. the Permittee notifies the Director and EPA with written notification at least seven days before the
change is made;and
iv. the Permittee shall attach the notice to the relevant permit.
c. The written notification shall include:
i. a description of the change;
ii. the date on which the change will occur;
iii. any change in emissions;and
Air Quality Permit No.05884T14
Page 40
iv. any permit term or condition that is no longer applicable as a result of the change.
d. Section 502(b)(10) changes shall be made in the permit the next time that the permit is revised or
renewed,whichever comes first.
3. Off Permit Changes[15A NCAC 2Q.0523(b)]
The Permittee may make changes in the operation or emissions without revising the permit if:
a. the change affects only insignificant activities and the activities remain insignificant after the change;or
b. the change is not covered under any applicable requirement.
4. Emissions Trading[15A NCAC 2Q.0523(c)]
To the extent that emissions trading is allowed under 15A NCAC 2D, including subsequently adopted
maximum achievable control technology standards, emissions trading shall be allowed without permit
revision pursuant to 15A NCAC 2Q.0523(c).
I.A. Reporting Requirements for Excess Emissions and Permit Deviations
[15A NCAC 2D.0535(f)and 2Q.0508(f)(2)]
"Excess Emissions"-means an emission rate that exceeds any applicable emission limitation or standard allowed
by any rule in Sections .0500, .0900, .1200, or.1400 of Subchapter 2D; or by a permit condition; or that exceeds
an emission limit established in a permit issued under 15A NCAC 2Q .0700. (Note: Definitions of excess
emissions under 2D.1110 and 2D.1111 shall apply where defined by rule)
"Deviations" - for the purposes of this condition, any action or condition not in accordance with the terms and
conditions of this permit including those attributable to upset conditions as well as excess emissions as defined
above lasting less than four hours.
Excess Emissions
1. If a source is required to report excess emissions under NSPS (15A NCAC 2D .0524), NESHAPS (15A
NCAC 2D .1110 or .1111), or the operating permit provides for periodic(e.g., quarterly)reporting of excess
emissions,reporting shall be performed as prescribed therein.
2. If the source is not subject to NSPS (15A NCAC 2D .0524),NESHAPS (15A NCAC 2D .1110 or .1111), or
these rules do NOT define "excess emissions,"the Permittee shall report excess emissions in accordance with
15A NCAC 2D.0535 as follows:
a. Pursuant to 15A NCAC 2D .0535, if excess emissions last for more than four hours resulting from a
malfunction,a breakdown of process or control equipment,or any other abnormal condition,the owner or
operator shall:
i. notify the Regional Supervisor or Director of any such occurrence by 9:00 a.m.Eastern Time of the
Division's next business day of becoming aware of the occurrence and provide:
• name and location of the facility;
• nature and cause of the malfunction or breakdown;
• time when the malfunction or breakdown is first observed;
• expected duration;and
• estimated rate of emissions;
ii. notify the Regional Supervisor or Director immediately when corrective measures have been
accomplished;and
iii. submit to the Regional Supervisor or Director within 15 days a written report as described in 15A
NCAC 213.0535(f)(3).
Permit Deviations
3. Pursuant to 15A NCAC 2Q .0508(f)(2),the Permittee shall report deviations from permit requirements(terms
and conditions)as follows:
a. Notify the Regional Supervisor or Director of all other deviations from permit requirements not covered
under 15A NCAC 2D .0535 quarterly. A written report to the Regional Supervisor shall include the
probable cause of such deviation and any corrective actions or preventative actions taken. The
responsible official shall certify all deviations from permit requirements.
I.B. Other Requirements under 15A NCAC 2D.0535
The Permittee shall comply with all other applicable requirements contained in 15A NCAC 2D .0535, including
Air Quality Permit No.05884T14
Page 41
15A NCAC 2D.0535(c)as follows:
1. Any excess emissions that do not occur during start-up and shut-down shall be considered a violation of the
appropriate rule unless the owner or operator of the sources demonstrates to the Director, that the excess
emissions are a result of a malfunction. The Director shall consider, along with any other pertinent
information,the criteria contained in 15A NCAC 2D.0535(c)(1)through(7).
2. 15A NCAC 2D.0535(g). Excess emissions during start-up and shut-down shall be considered a violation of
the appropriate rule if the owner or operator cannot demonstrate that excess emissions are unavoidable.
I Emergency Provisions[40 CFR 70.6(g)]
The Permittee shall be subject to the following provisions with respect to emergencies:
1. An emergency means any situation arising from sudden and reasonably unforeseeable events beyond the
control of the facility, including acts of God, which situation requires immediate corrective action to restore
normal operation, and that causes the facility to exceed a technology-based emission limitation under the
permit, due to unavoidable increases in emissions attributable to the emergency. An emergency shall not
include noncompliance to the extent caused by improperly designed equipment, lack of preventive
maintenance,careless or improper operation,or operator error.
2. An emergency constitutes an affirmative defense to an action brought for noncompliance with such
technology-based emission limitations if the conditions specified in 3.below are met.
3. The affirmative defense of emergency shall be demonstrated through properly signed contemporaneous
operating logs or other relevant evidence that include information as follows:
a. an emergency occurred and the Permittee can identify the cause(s)of the emergency;
b. the permitted facility was at the time being properly operated;
c. during the period of the emergency the Permittee took all reasonable steps to minimize levels of
emissions that exceeded the standards or other requirements in the permit;and
d. the Permittee submitted notice of the emergency to the DAQ within two working days of the time when
emission limitations were exceeded due to the emergency. This notice must contain a description of the
emergency,steps taken to mitigate emissions,and corrective actions taken.
4. In any enforcement proceeding, the Permittee seeking to establish the occurrence of an emergency has the
burden of proof.
5. This provision is in addition to any emergency or upset provision contained in any applicable requirement
specified elsewhere herein.
K. Permit Renewal[15A NCAC 2Q.0508(e)and 2Q.0513(b)]
This 15A NCAC 2Q.0500 permit is issued for a fixed term not to exceed five years and shall expire at the end of
its term and shall expire at the end of its term. Permit expiration terminates the facility's right to operate unless a
complete 15A NCAC 2Q .0500 renewal application is submitted at least nine months before the date of permit
expiration. If the Permittee or applicant has complied with 15A NCAC 2Q.0512(b)(1),this 15A NCAC 2Q.0500
permit shall not expire until the renewal permit has been issued or denied. Permit expiration under 15A NCAC 2Q
.0400 terminates the facility's right to operate unless a complete 15A NCAC 2Q .0400 renewal application is
submitted at least six months before the date of permit expiration for facilities subject to 15A NCAC 2Q .0400
requirements. In either of these events, all terms and conditions of these permits shall remain in effect until the
renewal permits have been issued or denied.
L. Need to Halt or Reduce Activity Not a Defense[15A NCAC 2Q.0508(i)(4)]
It shall not be a defense for a Permittee in an enforcement action that it would have been necessary to halt or
reduce the permitted activity in order to maintain compliance with the conditions of this permit.
M. Duty to Provide Information (submittal of information)[15A NCAC 2Q.0508(i)(9)]
1. The Permittee shall furnish to the DAQ,in a timely manner,any reasonable information that the Director may
request in writin to determine whether cause exists for modifying,revoking and reissuing,or terminating the
permit or to determine compliance with the permit.
2. The Permittee shall furnish the DAQ copies of records required to be kept by the permit when such copies are
requested by the Director.For information claimed to be confidential,the Permittee may furnish such records
directly to the EPA upon request along with a claim of confidentiality.
i
Air Quality Permit No.05884T14
Page 42
N. Duty to Supplement[15A NCAC 2Q.0507(f)]
The Permittee,upon becoming aware that any relevant facts were omitted or incorrect information was submitted
in the permit application, shall promptly submit such supplementary facts or corrected information to the DAQ.
The Permittee shall also provide additional information as necessary to address any requirement that becomes
applicable to the facility after the date a complete permit application was submitted but prior to the release of the
draft permit.
O. Retention of Records[15A NCAC 2Q.0508(f)and 2Q.0508(1)]
The Permittee shall retain records of all required monitoring data and supporting information for a period of at
least five years from the date of the monitoring sample, measurement, report, or application. Supporting
information includes all calibration and maintenance records and all original strip-chart recordings for continuous
monitoring information,and copies of all reports required by the permit. These records shall be maintained in a
form suitable and readily available for expeditious inspection and review. Any records required by the conditions
of this permit shall be kept on site and made available to DAQ personnel for inspection upon request.
P. Compliance Certification [15A NCAC 2Q.0508(n)]
The Permittee shall submit to the DAQ and the EPA(Air and EPCRA Enforcement Branch,EPA,Region 4, 61
Forsyth Street,Atlanta,GA 30303)postmarked on or before March 1 a compliance certification(for the preceding
calendar year)by a responsible official with all federally-enforceable terms and conditions in the permit,including
emissions limitations, standards,or work practices. It shall be the responsibility of the current owner to submit a
compliance certification for the entire year regardless of who owned the facility during the year. The compliance
certification
shall comply with additional requirements as may be specified under Sections 114(a)(3) or 504(b) of the Federal
Clean Air Act. The compliance certification shall specify:
1. the identification of each term or condition of the permit that is the basis of the certification;
2. the compliance status(with the terms and conditions of the permit for the period covered by the certification);
3. whether compliance was continuous or intermittent;and
4. the method(s)used for determining the compliance status of the source during the certification period.
Q. Certification by Responsible Official[15A NCAC 2Q.0520]
A responsible official shall certify the truth, accuracy, and completeness of any application form, report, or
compliance certification required by this permit. All certifications shall state that based on information and belief
formed after reasonable inquiry,the statements and information in the document are true,accurate,and complete.
R. Permit Shield for Applicable Requirements[15A NCAC 2Q.0512]
1. Compliance with the terms and conditions of this permit shall be deemed compliance with applicable
requirements, where such applicable requirements are included and specifically identified in the permit as of
the date of permit issuance.
2. A permit shield shall not alter or affect:
a. the power of the Commission,Secretary of the Department,or Governor under NCGS 143-215.3(a)(12),
or EPA under Section 303 of the Federal Clean Air Act;
b. the liability of an owner or operator of a facility for any violation of applicable requirements prior to the
effective date of the permit or at the time of permit issuance;
c. the applicable requirements under Title IV;or
d. the ability of the Director or the EPA under Section 114 of the Federal Clean Air Act to obtain
information to determine compliance of the facility with its permit.
3. A permit shield does not apply to any change made at a facility that does not require a permit or permit
revision made under 15A NCAC 2Q.0523.
4. A permit shield does not extend to minor permit modifications made under 15A NCAC 2Q.0515. ,
S. Termination,Modification,and Revocation of the Permit[15A NCAC 2Q.0519]
The Director may terminate,modify,or revoke and reissue this permit if:
1. the information contained in the application or presented in support thereof is determined to be incorrect;
I
Air Quality Permit No. 05884T14
Page 43
2. the conditions under which the permit or permit renewal was granted have changed;
3. violations of conditions contained in the permit have occurred;
4. the EPA requests that the permit be revoked under 40 CFR 70.7(g)or 70.8(d);or
5. the Director finds that termination, modification, or revocation and reissuance of the permit is necessary to
carry out the purpose ofNCGS Chapter 143,Article 21B.
T. Insignificant Activities[15A NCAC 2Q.0503]
Because an emission source or activity is insignificant does not mean that the emission source or activity is
exempted from any applicable requirement or that the owner or operator of the source is exempted from
demonstrating compliance with any applicable requirement. The Permittee shall have available at the facility at all
times and made available to an authorized representative upon request, documentation, including calculations, if
necessary,to demonstrate that an emission source or activity is insignificant.
U. Property Rights [15A NCAC 2Q.0508(i)(8)]
This permit does not convey any property rights in either real or personal property or any exclusive privileges.
V. Inspection and Entry[15A NCAC 2Q.0508(1)and NCGS 143-215.3(a)(2)]
1. Upon presentation of credentials and other documents as may be required by law,the Permittee shall allow the
DAQ,or an authorized representative,to perform the following:
a. enter the Permittee's premises where the permitted facility is located or emissions-related activity is
conducted,or where records are kept under the conditions of the permit;
b. have access to and copy,at reasonable times,any records that are required to be kept under the conditions
of the permit;
c. inspect at reasonable times and using reasonable safety practices any source, equipment (including
monitoring and air pollution control equipment),practices, or operations regulated or required under the
permit;and
d. sample or monitor substances or parameters,using reasonable safety practices,for the purpose of assuring
compliance with the permit or applicable requirements at reasonable times.
Nothing in this condition shall limit the ability of the EPA to inspect or enter the premises of the Permittee
under Section 114 or other provisions of the Federal Clean Air Act.
2. No person shall refuse entry or access to any authorized representative of the DAQ who requests entry for
purposes of inspection, and who presents appropriate credentials, nor shall any person obstruct, hamper, or
interfere with any such authorized representative while in the process of carrying out his official duties.
Refusal of entry or access may constitute grounds for permit revocation and assessment of civil penalties.
W. Annual Fee Payment[15A NCAC 2Q.0508(i)(10)]
1. The Permittee shall pay all fees in accordance with 15A NCAC 2Q.0200.
2. Payment of fees may be by check or money order made payable to the N.C. Department of Environment and
Natural Resources. Annual permit fee payments shall refer to the permit number.
3. If,within 30 days after being billed,the Permittee fails to pay an annual fee,the Director may initiate action to
terminate the permit under 15A NCAC 2Q.0519.
X. Annual Emission Inventory Requirements[15A NCAC 2Q.0207]
The Permittee shall report by June 30 of each year the actual emissions of each air pollutant listed in 15A NCAC
2Q.0207(a)from each emission source within the facility during the previous calendar year. The report shall be in
or on such form as may be established by the Director. The accuracy of the report shall be certified by a
responsible official of the facility.
Y. Confidential Information[15A NCAC 2Q.0107 and 2Q.0508(i)(9)]
Whenever the Permittee submits information under a claim of confidentiality pursuant to 15A NCAC 2Q .0107,
the Permittee may also submit a copy of all such information and claim directly to the EPA upon request. All
requests for confidentiality must be in accordance with 15A NCAC 2Q.0107.
Z. Construction and Operation Permits[15A NCAC 2Q.0100 and.0300]
Air Quality Permit No.05884T14
Page 44
A construction and operating permit shall be obtained by the Permittee for any proposed new or modified facility
or emission source which is not exempted from having a permit prior to the beginning of construction or
modification,in accordance with all applicable provisions of 15A NCAC 2Q.0100 and.0300.
AA.Standard Application Form and Required Information [15A NCAC 2Q.0505 and.0507]
The Permittee shall submit applications and required information in accordance with the provisions of 15A NCAC
2Q.0505 and.0507.
BB.Financial Responsibility and Compliance History[15A NCAC 2Q.0507(d)(4)]
The DAQ may require an applicant to submit a statement of financial qualifications and/or a statement of
substantial compliance history.
CC.Refrigerant Requirements(Stratospheric Ozone and Climate Protection) [15A NCAC 2Q .0501(e)]
1. If the Permittee has appliances or refrigeration equipment, including air conditioning equipment, which use
Class I or H ozone-depleting substances such as chlorofluorocarbons and hydrochlorofluorocarbons listed as
refrigerants in 40 CFR Part 82 Subpart A Appendices A and B, the Permittee shall service, repair, and
maintain such equipment according to the work practices,personnel certification requirements, and certified
recycling and recovery equipment specified in 40 CFR Part 82 Subpart F.
2. The Permittee shall not knowingly vent or otherwise release any Class I or 11 substance into the environment
during the repair,servicing,maintenance,or disposal of any such device except as provided in 40 CFR Part 82
Subpart F.
3. The Permittee shall comply with all reporting and recordkeeping requirements of 40 CFR❑ 82.166. Reports
shall be submitted to the EPA or its designee as required.
DD.Prevention of Accidental Releases-Section 112(r)[15A NCAC 2Q.0508(h)]
If the Permittee is required to develop and register a Risk Management Plan with EPA pursuant to Section 112(r)
of the Clean Air Act,then the Permittee is required to register this plan in accordance with 40 CFR Part 68.
EE. Prevention of Accidental Releases General Duty Clause-Section 112(r)(1)-
FEDERALLY-ENFORCEABLE ONLY
Although a risk management plan may not be required,if the Permittee produces,processes,handles,or stores any
amount of a listed hazardous substance, the Permittee has a general duty to take such steps as are necessary to
prevent the accidental release of such substance and to minimize the consequences of any release.
FF. Title IV Allowances [15A NCAC 2Q.0508(i)(1)]
This permit does not limit the number of Title IV allowances held by the Permittee,but the Permittee may not use
allowances as a defense to noncompliance with any other applicable requirement. The Permittee's emissions may
not exceed any allowances that the facility lawfully holds under Title IV of the Federal Clean Air Act.
GG.Air Pollution Emergency Episode[15A NCAC 2D.0300]
Should the Director of the DAQ declare an Air Pollution Emergency Episode, the Permittee will be required to
operate in accordance with the Permittee's previously approved Emission Reduction Plan or, in the absence of an
approved plan,with the appropriate requirements specified in 15A NCAC 2D.0300.
HH.Registration of Air Pollution Sources[15A NCAC 2D.0200]
The Director of the DAQ may require the Permittee to register a source of air pollution. If the Permittee is
required to register a source of air pollution,this registration and required information will be in accordance with
15A NCAC 2D.0202(b).
H. Ambient Air Quality Standards[15A NCAC 2D.0501(c)]
In addition to any control or manner of operation necessary to meet emission standards specified in this permit,
any source of air pollution shall be operated with such control or in such manner that the source shall not cause the
ambient air quality standards in 15A NCAC 2D .0400 to be exceeded at any point beyond the premises on which
the source is located. When controls more stringent than named in the applicable emission standards in this permit
Air Quality Permit No. 05884T14
Page 45
are required to prevent violation of the ambient air quality standards or are required to create an offset,the permit
shall contain a condition requiring these controls.
JJ. General Emissions Testing and Reporting Requirements[15A NCAC 2Q.0508(i)(16)]
Emission compliance testing shall be by the procedures of Section .2600, except as may be otherwise required
in Rules.0524, .0912, .1110, .1111,or.1415 of Subchapter 2D.
If emissions testing is required by this permit or the DAQ or if the Permittee submits emissions testing to the DAQ
to demonstrate compliance,the Permittee shall perform such testing in accordance with 15A NCAC 2D .2600 and
follow the procedures outlined below:
1. The owner or operator of the source shall arrange for air emission testing protocols to be provided to the
Director prior to air pollution testing. Testing protocols are not required to be pre-approved by the Director
prior to air pollution testing. The Director shall review air emission testing protocols for pre-approval prior
to testing if requested by the owner or operator at least 45 days before conducting the test.
2. Any person proposing to conduct an emissions test to demonstrate compliance with an applicable standard
shall notify the Director at least 15 days before beginning the test so that the Director may at his option
observe the test.
3. The owner or operator of the source shall arrange for controlling and measuring the production rates during
the period of air testing. The owner or operator of the source shall ensure that the equipment or process
being tested is operated at the production rate that best fulfills the purpose of the test. The individual
conducting the emission test shall describe the procedures used to obtain accurate process data and include
in the test report the average production rates determined during each testing period.
4. Two copies of the final air emission test report shall be submitted to the Director not later than 30 days
after sample collection unless otherwise specified in the specific conditions. The owner or operator may
request an extension to submit the final test report. The Director shall approve an extension request if he
finds that the extension request is a result of actions beyond the control of the owner or operator.
a. The Director shall make the final determination regarding any testing procedure deviation and the
validity of the compliance test.The Director may:
(1) Allow deviations from a method specified under a rule in this Section if the owner or operator of
the source being tested demonstrates to the satisfaction of the Director that the specified method is
inappropriate for the source being tested.
(2)Prescribe alternate test procedures on an individual basis when he finds that the alternative method
is necessary to secure more reliable test data.
(3) Prescribe or approve methods on an individual basis for sources or pollutants for which no test
method is specified in this Section if the methods can be demonstrated to determine compliance of
permitted emission sources or pollutants.
b. The Director may authorize the Division of Air Quality to conduct independent tests of any source
subject to a rule in this Subchapter to determine the compliance status of that source or to verify any
test data submitted relating to that source. Any test conducted by the Division of Air Quality using the
appropriate testing procedures described in Section 2D.2600 has precedence over all other tests.
KK.Reopening for Cause [15A NCAC 2Q.0517]
1. A permit shall be reopened and revised under the following circumstances:
a. additional applicable requirements become applicable to a facility with remaining permit term of three or
more years;
b. additional requirements(including excess emission requirements)become applicable to a source covered
by Title IV;
c. the Director or EPA finds that the permit contains a material mistake or that inaccurate statements were
made in establishing the emissions standards or other terms or conditions of the permit;or
d. the Director or EPA determines that the permit must be revised or revoked to assure compliance with the
applicable requirements.
2. Any permit reopening shall be completed or a revised permit issued within 18 months after the applicable
requirement is promulgated. No reopening is required if the effective date of the requirement is after the
expiration of the permit term unless the term of the permit was extended pursuant to 15A NCAC 2Q.0513(c).
3. Except for the state-enforceable only portion of the permit, the procedures set out in 15A NCAC 2Q .0507,
.0521, or .0522 shall be followed to reissue the permit. If the State-enforceable only portion of the permit is
Air Quality Permit No. 05884T14
Page 46
reopened,the procedures in 15A NCAC 2Q .0300 shall be followed. The proceedings shall affect only those
parts of the permit for which cause to reopen exists.
4. The Director shall notify the Permittee at least 60 days in advance of the date that the permit is to be reopened,
except in cases of imminent threat to public health or safety the notification period may be less than 60 days.
5. Within 90 days,or 180 days if the EPA extends the response period,after receiving notification from the EPA
that a permit needs to be terminated,modified, or revoked and reissued,the Director shall send to the EPA a
proposed determination of termination,modification,or revocation and reissuance,as appropriate.
LL. Reporting Requirements for Non-Operating Equipment[15A NCAC 2Q.0508(i)(16)]
The Permittee shall maintain a record of operation for permitted equipment noting whenever the equipment is
taken from and placed into operation. During operation the monitoring recordkeeping and reporting requirements
as prescribed by the permit shall be implemented within the monitoring period.
MM.Fugitive Dust Control Requirement[15A NCAC 2D.0540]-STATE ENFORCEABLE ONLY
As required by 15A NCAC 2D .0540 "Particulates from Fugitive Dust Emission Sources,"the Permittee shall not
cause or allow fugitive dust emissions to cause or contribute to substantive complaints or excess visible emissions
beyond the property boundary. If substantive complaints or excessive fugitive dust emissions from the facility are
observed beyond the property boundaries for six minutes in any one hour(using Reference Method 22 in 40 CFR,
Appendix A),the owner or operator may be required to submit a fugitive dust plan as described in 2D.0540(f).
"Fugitive dust emissions" means particulate matter from process operations that does not pass through a process
stack or vent and that is generated within plant property boundaries from activities such as: unloading and loading
areas,process areas stockpiles, stock pile working,plant parking lots, and plant roads (including access roads and
haul roads).
NN.Specific Permit Modifications [15A NCAC 2Q.0501 and.0523]
1. For modifications made pursuant to 15A NCAC 2Q.0501(c)(2),the Permittee shall file a Title V Air Quality
Permit Application for the air emission source(s) and associated air pollution control device(s)on or before
12 months after commencing operation.
2. For modifications made pursuant to 15A NCAC 2Q .0501(d)(2),the Permittee shall not begin operation of
the air emission source(s) and associated air pollution control device(s)until a Title V Air Quality Permit
Application is filed and a construction and operation permit following the procedures of Section .0500
(except for Rule.0504 of this Section)is obtained.
3. For modifications made pursuant to 502(b)(10), in accordance with 15A NCAC 2Q .0523(a)(1)(C), the
Permittee shall notify the Director and EPA (EPA - Air Planning Branch, 61 Forsyth St., Atlanta, GA
30303)in writing at least seven days before the change is made. The written notification shall include:
a. a description of the change at the facility;
b. the date on which the change will occur;
C. any change in emissions;and
d. any permit term or condition that is no longer applicable as a result of the change.
In addition to this notification requirement, with the next significant modification or Air Quality Permit
renewal,the Permittee shall submit a page "E5" of the application forms signed by the responsible official
verifying that the application for the 502(b)(10) change/modification, is true, accurate, and complete.
Further note that modifications made pursuant to 502(b)(10) do not relieve the Permittee from satisfying
preconstruction requirements.
OO.Third Party Participation and EPA Review[15A NCAC 2Q.0521, .0522 and.0525(7)]
For permit modifications subject to 45-day review by the federal Environment Protection Agency(EPA),EPA's
decision to not object to the proposed permit is considered final and binding on the EPA and absent a third party
petition, the failure to object is the end of EPA's decision-making process with respect to the revisions to the
permit. The time period available to submit a public petition pursuant to 15A NCAC 2Q .0518 begins at the end
of the 45-day EPA review period.
ATTACIE ENT
List of Acronyms
AOS Alternate Operating Scenario
BACT Best Available Control Technology
Btu British thermal unit
CAA Clean Air Act
CAIR Clean Air Interstate Rule
CEM Continuous Emission Monitor
CFR Code of Federal Regulations
DAQ Division of Air Quality
DENR Department of Environment and Natural Resources
EMC Environmental Management Commission
EPA Environmental Protection Agency
FR Federal Register
GACT Generally Available Control Technology
HAP Hazardous Air Pollutant
MACT Maximum Achievable Control Technology
NAA Non-Attainment Area
NCAC North Carolina Administrative Code
NCGS North Carolina General Statutes
NESHAPS National Emission Standards for Hazardous Air Pollutants
NOx Nitrogen Oxides
NSPS New Source Performance Standard-
OAH Office of Administrative Hearings
PM Particulate Matter
PMI0 Particulate Matter with Nominal Aerodynamic Diameter of 10 Micrometers or Less
POS Primary Operating Scenario
PSD Prevention of Significant Deterioration
RACT Reasonably Available Control Technology
SIC Standard Industrial Classification
SIP State Implementation Plan
S02 Sulfur Dioxide
tpy Tons Per Year