HomeMy WebLinkAboutAQ_F_0400056_20140207_ST_ProtRvw YA
iA
FqC®EN
North Carolina Department of Environment and Natural Resources
Division of Air Quality
Pat McCrory Sheila C. Holman John E. Skvarla, III
Governor Director Secretary
February 7, 2014 Anson County
Mr. Gil Vinzani
Piedmont Natural Gas, Inc.
150 Fayetteville Street, Suite 2810
Raleigh,North Carolina 27601
Subject: Piedmont Natural Gas, Wadesboro
Air Permit No.I0097R00, Facility ID 0400056
Proposed Performance Test for ID COM1101-COMP04,NG-fired engines
Proposed Test Date: February 7, 2014
DAQ Tracking No. 2014-007ST
Dear Mr. V 1 nzani:
North Carolina Division of Air Quality(DAQ)has reviewed the protocol submittal form(PSF)
for the subject testing and deemed it acceptable. The sources are 4-stroke lean burn natural gas
engine compressor engines rated at 4735 horsepower(hp). The proposed testing is the initial
performance testing required by applicable regulations for new sources.
Applicable regulations:
• 40 CFR 63 Subpart ZZZZ National Emissions Standards for Hazardous Air Pollutants
for Stationary Reciprocating Internal Combustion Engines (RICE NESHAP)
• Permit including Section 3.0 General Conditions Section JJ General Emissions Testing
and Reporting Requirements
• 15A NCAC 2D .2600 Source Testing
• 40 CFR 60 Subpart JJJJ,Standards of Performance for Stationary Spark Ignition Internal
Combustion Engines
The primary purpose for testing is to demonstrate compliance with 40 CFR 60 Subpart JJJJ.
Compliance with 40 CFR 63 Subpart ZZZZ is met by complying with the emission limits in 40
CFR 60 Subpart JJJJ.
The following emission standards apply to new spark ignition, lean burn burn gas-fired non-
emergency engines constructed after July 1, 2010.
1641 Mail Service Center,Raleigh,North Carolina 27699-1641
217 West Jones Street,Raleigh,North Carolina 27603
Phone:919-707-84011 Fax:919-715-0718
Internet:www.ncair.om
An Equal Opportunity 1 Affirmative Action Employer—Made in part by Recycled Paper
Mr. Gil Vinzani
February 7, 2014
Page 2
Table 1: NSPS,40 CFR Part 60, Subpart JJJJ Standards for 4-stroke lean burn natural gas-fired
non-emergency engines> 500 hp
Pollutant Emission Standard(g/hp-hr) -or- Emission Standard(ppmvd at 15% 02)
NO, 1.0 g/hp-hr 82 ppmvd at 15% 02
CO 2.0 p-hr 270 ppmvd at 15% 02
VOC 1 0.7 g/hp-hr 60 ppmvd at 15% 02
g/hp-hr=gram/horsepower—hour;ppmvd=parts per million by volume, dry basis
Table 2: Approved Test Methods for Feb 10, 2014:
Number Test Number of
Target Proposed Test of Test Run Sampling
Pollutant Method Runs Duration Points Comments
CO I EPA Method 10 3 60
02 EPA Method 3A 3 60 No. of sampling points
NO,, EPA Method 7E 3 60 1-3 is per
VOC EPA Method 3 60 WE stratification test
25A
For moisture
Moisture EPA Method 4 3 60 1-3 calculations, correction
to dry standard
CIL EPA Method 18 3 60 1-3 Correction of THC to
report NMHC
THC=total hydrocarbon;NMHC=non-methane hydrocarbons
The proposed test methods are acceptable for the specified pollutants. Approval of the protocol
does not exempt the tester from the minimum requirements p q ements of the applicable methods and 60
Subpart JJJJ requirements. Since no deviations from the applicable testing methodology were
addressed in the test protocol, the testing should be conducted in strict accordance with the
requirements of EPA Methods 3A, 4, 7E, 10, 18, and 25A.
Testing must be conducted at full load f 10%. Testing proposed operating process rate of 4735 hp
is acceptable. If you have questions,please contact me at(919) 707-8413 or
gary.saunders@ncdenr.gov.
Sincerely,
FL �aunder_s
C _
a
Environmental Engineer
cc: Steven Vozzo,Fayetteville Regional Office
Central Files,Anson County
IBEAM Documents