HomeMy WebLinkAboutAQ_F_0400050_20130919_CEM_RptRvwLtr NCDENR
North Carolina Department of Environment and Natural Resources
Division of Air Quality
Pat McCrory Sheila C. Holman John E. Skvarla, III
Governor Director Secretary
September 19, 2013
Mr. S. Lee Ragsdale
Vice President, Asset Management
North Carolina Electric Membership Corporation—Hamlet Plant
3400 Summer Boulevard
Raleigh,North Carolina 27616
SUBJECT: Review of 2013 First Semester Excess Emissions Report
North Carolina Electric Membership Corporation—Anson Plant
Lilesville, Anson County,North Carolina
Air Quality Permit No. 09492T07
Facility ID: 0400050
Dear Mr. Ragsdale:
Thank you for the timely submittal of the subject report dated, July 29, 2013. The
Division of Air Quality has completed its review of the continuous monitoring system
summary results for peaking turbines (ID Nos. ES 1-A, ES1-B, ES2-A, ES2-B, ES3-A,
ES3-B, ES4-A, ES4-B, ES5-A, ES5-B, ES6-A and ES6-B)that operated at the Hamlet
Plant during the first and second quarters of 2013. The turbines are subject to 40 CFR
Part 60, Subpart KKKK. NOx emissions from the turbines are controlled by water
injection and monitored for compliance using water to fuel ratios. Monitoring
summaries of the water to fuel ratios were reviewed in order to determine compliance
with NOx emission limits stated in Air Quality Permit No. 09492T07, Section 2.1.A.3.
All excess emissions were attributed to either startup, shut down, malfunction (SSM), or
other exempt emissions. These emissions were reviewed and allowed in accordance with
the applicable subpart.
In addition, quarterly percent excess emissions (%EE) and percent monitor downtime
(%MD) were reviewed for compliance with proper operation and maintenance (O&M)
practices pursuant to 40 CFR 60.11(d) and Air Quality Permit No. 09492T07,Section 3,
General Condition F. For each quarter, the facility-wide sum of%EE and%MD was
greater than the target criteria of 24%; therefore, a secondary evaluation was necessary.
Since the average number of operating hours for each peaking turbine was less than 150
hours each quarter, and the SSM ratio was less than 15%, it appears the peaking turbines
were operated with proper O&M.
Technical Services Section
1641 Mail Service Center, Raleigh, North Carolina 27699-1641
217 West Jones Street,Raleigh,North Carolina 27603
Phone:919-707-8407/Fax:919-715-0718
Internet:www.ncair.org
An Eoual ODDortunity 1 Affirmative Action EmDlover-Made in Dart by Recvcled Pacer
Mr. S. Lee Ragsdale
September 19, 2013
Page 2
If you should have any questions, please contact me at 919-707-8493 or alan.drake@ncdenr.gov.
Sincerely,
Alan Drake
Environmental Engineer
cc: Steven Vozzo, FRO
Michael Pjetraj, RCO
Central Files, Anson County