HomeMy WebLinkAboutAQ_F_2100073_20160523_ST_RvwLtr (4) DIVISION OF AIR QUALITY
May 23,2016
MEMORANDUM
To: Robert Fisher,Washington Regional Office
From: Shannon Vogel, Stationary Source Compliance Branch
Subject: Regulator Marine, Inc.
Edenton, Chowan County,North Carolina
Facility ID 2100073,Permit No. 07132TI I
Carbon Monoxide Emissions Testing of Diesel-fired Peak Shaving Generator ES-14
Performed by Integrity Air Monitoring, Inc. on September 24,2015
Tracking No. 2015-177st
Integrity Air Monitoring performed EPA Method 10 carbon monoxide(CO) emissions testing of ES-14 to
demonstrate compliance with the applicable emissions limits. The test results are acceptable.
Emission Source ID ES-14 is a diesel-fired peak shaving generator controlled by diesel oxidation catalyst
CD-14. The maximum permitted capacity is 764 horsepower. 40 CFR 63 Subpart ZZZZ National
Emission Standards for Hazardous Air Pollutants,for Stationary Reciprocating Internal Combustion
Engine(RICE) applies. The engine is classified as new under the regulations. 63 Subpart ZZZZ requires
a minimum CO reduction efficiency greater than or equal to 70%.
Pollutant Test Results Requirement Standard Compliance
Inlet CO 44.3 ppm@15%02 --- --- ---
Outlet CO 0.121 ppm 15%02 --- ---
Efficiency 99.73% >70% Yes
Pressure Drop 5.6 in. H2O f2 in. H2O 63 Subpart ZZZZ ---
Inlet Temperature 732.4°F 450OF - 1350OF ---
The average reported output during testing was 246.4 kilowatts. This operating rate is acceptable.
Compliance was demonstrated. If you have questions regarding the results of this review,please contact
me at 919-707-8416 or shannon.vogel@ncdenr.gov.