Loading...
HomeMy WebLinkAboutAQ_F_2100073_20160523_ST_RvwLtr (4) DIVISION OF AIR QUALITY May 23,2016 MEMORANDUM To: Robert Fisher,Washington Regional Office From: Shannon Vogel, Stationary Source Compliance Branch Subject: Regulator Marine, Inc. Edenton, Chowan County,North Carolina Facility ID 2100073,Permit No. 07132TI I Carbon Monoxide Emissions Testing of Diesel-fired Peak Shaving Generator ES-14 Performed by Integrity Air Monitoring, Inc. on September 24,2015 Tracking No. 2015-177st Integrity Air Monitoring performed EPA Method 10 carbon monoxide(CO) emissions testing of ES-14 to demonstrate compliance with the applicable emissions limits. The test results are acceptable. Emission Source ID ES-14 is a diesel-fired peak shaving generator controlled by diesel oxidation catalyst CD-14. The maximum permitted capacity is 764 horsepower. 40 CFR 63 Subpart ZZZZ National Emission Standards for Hazardous Air Pollutants,for Stationary Reciprocating Internal Combustion Engine(RICE) applies. The engine is classified as new under the regulations. 63 Subpart ZZZZ requires a minimum CO reduction efficiency greater than or equal to 70%. Pollutant Test Results Requirement Standard Compliance Inlet CO 44.3 ppm@15%02 --- --- --- Outlet CO 0.121 ppm 15%02 --- --- Efficiency 99.73% >70% Yes Pressure Drop 5.6 in. H2O f2 in. H2O 63 Subpart ZZZZ --- Inlet Temperature 732.4°F 450OF - 1350OF --- The average reported output during testing was 246.4 kilowatts. This operating rate is acceptable. Compliance was demonstrated. If you have questions regarding the results of this review,please contact me at 919-707-8416 or shannon.vogel@ncdenr.gov. cc: Central Files, Chowan County IBEAM Documents -2100073