HomeMy WebLinkAboutAQ_F_0100010_20160106_CEM_RptRvwLtr (3) PAT MCCRORY
Governor
DONALD R. VAN DER VAART
KI-C Secretary
Air Quality SHEILA C. HOLMAN
ENVIRONMENTAL QUALITY Director
January 6, 2016
Mr. Alan Skrzypczak
Facility Manager
Stericycle, Inc.
Post Office Box 310
Haw River, North Carolina 27258
SUBJECT: Review of 2015 CO/02 CEMS RATA
Stericycle, Inc.
Haw River, Alamance County, North Carolina
Facility ID No. 0100010
Air Permit No. 05896T24
Dear Mr. Skrzypczak:
Thank you for the timely submittal of the subject report received, December 15, 2015, for
Stericycle's Haw River facility. The Division of Air Quality (DAQ)has completed its review of
the relative accuracy test audit(RATA)conducted by TRC Environmental Corp.(TRC)on
November 16-17, 2015. Test results for the carbon monoxide(CO) continuous emission
monitoring systems (CEMS) operating on hospital,medical and infectious waste incinerator
(HMIWI) ESO1 and HMIWI ES02 were reported as follows:
Emission Source Parameter Relative Accuracy Specification
CO 3.1%* < 5% of standard*
ESO1
02 0.51% < 1.0%mean difference
CO 0.7%* < 5% of standard*
ES02
02 0.20% < 1.0%mean difference
*Alternative demonstration:RA<5%when using emission standard.
Based on our review, the CO/02 CEMS operating on the incinerators appear to have met the
relative accuracy (RA) requirements of 40 CFR Part 60, Appendix B, Performance
Specification 4A.
State of North Carolina I Environmental Quality Air Quality
1641 Mail Service Center 1 217 W.Jones Street,Suite 4000 1 Raleigh,NC 27699-1641
919 707 8400 T
Mr. Alan Skrzypczak
January 6, 2016
Page 2
A RATA was also performed on the backup CO CEMS (Mfg/model: Thermo Scientific/48i;
Serial#: CM 09080034). Test results indicate the backup analyzer met the requirements for
relative accuracy as set forth in PS-4A. Should the backup CEMS be pressed into service, please
refer to our letter of December 12, 2012, for conditions of its use.
40 CFR Part 60, Appendix F requires that quarterly audits must be conducted,with a RATA
being conducted at least once every four calendar quarters. The next RATA for ESO1 and ES02
should be completed by December 31, 2016.
If you should have any questions,please contact me at(919) 707-8493 or alan.drake@ncdenr.gov.
Sincerely,
Alan Drake, Environmental Engineer
Division of Air Quality, NCDEQ
cc: Lisa Edwards, WSRO
Michael Pjetraj, RCO
IBEAM, 0100010
Central Files,Alamance County