HomeMy WebLinkAboutAQ_F_0100010_20160825_CEM_RptRvwLtr (3) PAT MCCRORY
Governor
1C_
DONALD R. VAN DER VAART
Secretary
Air Quality SHEILA C. HOLMAN
ENVIRONMENTAL QUALITY Director
August 25, 2016
Mr. Alan Skrzypczak
Facility Manager
Stericycle, Inc.
Post Office Box 310
Haw River,North Carolina 27258
SUBJECT: Review of 2016 First Semester CO/02 CEMS Report
Stericycle, Inc. —Haw River Facility
Haw River, Alamance County,North Carolina
Air Permit No. 05896T24
Facility ID# 0100010
Dear Mr. Skrzypczak:
Thank you for your timely submittal of the subject report, dated July 27, 2016. The excess
emissions report assessed the carbon monoxide (CO)/oxygen(02) continuous emissions
monitoring systems (CEMS) operating at the Haw River Facility during the first half of 2016.
The CEMS was installed pursuant to 15A NCAC 02D .1206—Hospital, Medical, and Infectious
Waste Incinerators. The Division of Air Quality(DAQ)has completed its review and has the
following comments:
1. Hospital, medical, and infectious waste incinerators (HMIWI) ESO1 &ES02 were reviewed
for compliance with the state-only CO emissions limit of 11 parts per million by volume
(ppmv, 7% 02, 12-hour rolling average) as stated in Air Permit No. 05896, Specific
Condition 2.1.A.La. There were no exceedances reported during this time period.
2. Quarterly summary reports were reviewed for compliance with good operation and
maintenance (O&M)practices pursuant to 15A NCAC 02D .0611(d), General Condition 3.F,
and summarized as follows:
Unit Quarter %EE %MD
HMIWI ESO1 1st 0.0 0.1
2nd 0.0 0.0
HMIWI ES02 1st 0.0 0.2
2nd 0.0 0.1
The incinerators, along with associated CEMS units, appear to have operated using proper
O&M practices for minimizing emissions since quarterly percent excess emissions (%EE)
State of North Carolina I Environmental Quality I Air Quality
1641 Mail Service Center 1 217 W.Jones Street,Suite 4000 1 Raleigh,NC 27609-1641
919 707 8400 T
Mr. Alan Skrzypczak
August 25, 2016
Page 2
and percent monitor downtime (%MD) were less than 6% for any single calendar quarter and
less than 3% for two consecutive quarters.
3. Quarterly CO/02 CEMS cylinder gas audits (CGA)were reviewed for each incinerator. The
quality assurance (QA)results appear to have met the 15% accuracy requirement of 40 CFR
Part 60, Appendix F— Quality Assurance Procedures, referenced in Specific Condition
2.1.A.Lh.
If you should have any questions,please contact me at 919-707-8493 or alan.drake@ncdenr.gov.
Sincerely,
w
sZ
Alan Drake, Environmental Engineer
Division of Air Quality,NCDEQ
c: Lisa Edwards, WSRO
Michael Pjetraj, RCO
IBEAM Documents, 0100010
Central Files, Alamance County