HomeMy WebLinkAboutAQ_F_1800419_20170224_ST_RvwMemo Catawba County DIVISION OF AIR QUALITY Technical Services Section February 24, 2017 MEMORANDUM To: Bruce Ingle,Mooresville Regional Office From: Gary L. Saunders, Stationary Source Compliance Branch(SSCB) Subject: Prysmian Cables and Systems USA, LLC Claremont, Catawba County,North Carolina,Air Permit No. 07334T36 Facility ID 1800419,Tracking No. 2015-049ST Emissions Testing of Dry Scrubber ID No. 2DS Performed April 15, 2015 by Montrose Air Quality Services(Montrose) Montrose conducted performance testing at the inlet and outlet of the dry scrubber(ID No. 2DS on April 15, 2015. The purpose of this testing was to demonstrate compliance with Prevention of Significant Deterioration avoidance conditions contained in the permit. Method 7E was used to measure nitrogen oxides(NOX) concentrations and emission rates at the inlet and outlet of the dry scrubber and to determine removal efficiency of the scrubber. The measured NO,,concentration at the dry scrubber outlet was 315.6 parts per million by volume on a dry basis(ppmvd) and outlet emission rate of 41.68 pounds per hour(lb/hr). This projects to an outlet annual emission rate of 182.55 tons/year. The inlet NO,concentration was measured at 340.9 ppmvd with an inlet emission rate of 46.65 lb/hr. The NO,,emissions reduction rate was computed at 10.65 percent. The production rate was described in terms of"pre-forms"and during the testing the production rate was 14 pre-forms per 24-hour period. The test results are deemed acceptable. If there are any questions concerning this matter,please contact me at(919) 707-8413 or gary.saunders@ncdenr.gov. cc: Central Files, Catawba County IBEAM Documents- 1800419