HomeMy WebLinkAboutAQ_F_0100010_20161208_CEM_RptRvwLtr (3) PAT MCCRORY
Governor
DONALD R. VAN DER VAART
N.-C Secretory
Air Quality SHEILA C. HOLMAN
ENVIRONMENTAL QUALITY Director
December 8, 2016
Mr. Alan Skrzypczak
Facility Manager
Stericycle, Inc.
Post Office Box 310
Haw River, North Carolina 27258-0310
SUBJECT: Review of 2016 CO/02 CEMS RATA
Stericycle, Inc.
Haw River,Alamance County,North Carolina
Facility ID No. 0100010
Air Permit No. 05896T24
Dear Mr. Skrzypczak:
Thank you for the timely submittal of the subject report dated, November 28, 2016, for
Stericycle's Haw River facility. The Division of Air Quality(DAQ)has completed its review of
the relative accuracy test audit(RATA) conducted by TRC Environmental Corp. (TRC) on
November 1, 2016. Test results for the carbon monoxide (CO)/ oxygen(02) continuous
emission monitoring systems (CEMS) operating on hospital, medical and infectious waste
incinerator (HMIWI) ES01 and HMIWI ES02 were reported as follows:
Emission Source Parameter Relative Accuracy Specification
CO 0.8%* < 5% of standard*
ES01
02 0.48% < 1.0% (mean difference)
CO 1.3%* < 5% of standard*
ES02
02 0.45% < 1.0% Imean difference)
*Alternative demonstration:RA<5%when using emission standard.
Based on our review, the CO/02 CEMS operating on the incinerators appear to have met the
relative accuracy (RA) requirements of 40 CFR Part 60, Appendix B, Performance
Specification 4A.
State of North Carolina Environmental Quality Air Quality
1641 Mail Service Center 1217 W.Jones Street,Suite 4000 1 Raleigh,NC 27699-1641
919 707 8400 T
Mr. Alan Skrzypczak
December 8, 2016
Page 2
A RATA was also performed on the backup CO CEMS (Mfg/model: Thermo Scientific/48i;
Serialt CM 09080034). Test results indicate the backup analyzer met the requirements for
relative accuracy as set forth in PS-4A. Should the backup CEMS be pressed into service,please
refer to our letter of December 12, 2012, for conditions of its use.
40 CFR Part 60, Appendix F requires that quarterly audits must be conducted,with a RATA
being conducted at least once every four calendar quarters. The next RATA for ESO1 and ES02
should be completed by December 31, 2017.
If you should have any questions,please contact me at (919) 707-8493 or alan.drake*ncdenr.gov.
Sincerely,
Alan Drake, Environmental Engineer
Division of Air Quality, NCDEQ
c: Lisa Edwards, WSRO
Michael Pjetraj, RCO
IBEAM, 0100010
Central Files, Alamance County