HomeMy WebLinkAboutAQ_F_1200180_20161215_PRMT_Permit PAT MCCRORY
Governor
DONALD R.VAN DER VAART
w Secretary
Air Quality C LT T HTT
- ENVIRONMENTAL QUALITY- SHEILA C. OLMAN
Director
December 15, 2016
Mr. Koji Kawada
President
Seiren North America, LLC
PO Box 130
Morganton,NC 28680-0130
Subject: Air Permit No. 09231R13
Seiren North America, LLC
Morganton,Burke County,North Carolina
Permit Class: Synthetic Minor
Facility ID# 1200180
Dear Mr. Kawada:
f
In accordance with your completed application received October 13, 2016, we are
forwarding herewith Permit No. 0923IR13 to Seiren North America, LLC, Morganton, Burke
County,North Carolina for the construction and operation of air emissions sources or air cleaning
devices and appurtenances. Additionally, any emissions activities determined from your air permit
application as meeting the exemption requirements contained in 15A NCAC 2Q .0102 have been
listed for information purposes as an "ATTACHMENT" to the enclosed air permit. Please note the
records retention requirements are contained in General Condition 2 of the General Conditions and
Limitations.
If any parts,requirements,or limitations contained in this permit are unacceptable to you,
you have the right to request a formal adjudicatory hearing within 30 days following receipt of this
permit, identifying the specific issues to be contested. Such a request will stay the effectiveness of
the entire permit. This hearing request must be in the form of a written petition, conforming to G.S.
150B-23 of the North Carolina General Statutes, and filed with the Office of Administrative
Hearings, 6714 Mail Service Center, Raleigh,NC 27699-6714. The form for requesting a formal
adjudicatory hearing may be obtained upon request from the Office of Administrative Hearings.
Unless a request for a hearing is made pursuant to G.S. 15013-23,this air permit shall be final and
binding.
You may request modification of your air permit through informal means pursuant to G.S.
15013-22. This request must be submitted in writing to the Director and must identify the specific
provisions or issues for which the modification is sought. Please note that the permit will become
final and binding regardless of a request for informal modification unless a request for a hearing is
also made under G.S. 15013-23.
State of North Carolina I Environmental Quality I Air Quality
Asheville Regional Office 1 2090 U.S.Highway 70 1 Swannanoa,NC 28778
828 296 4500 T 1 828 299 7043 F
Mr. Koji Kawada
December 15, 2016
Page 2
Unless exempted by a condition of this permit or the regulations, construction of new
air pollution sources or air cleaning devices, or modifications to the sources or air cleaning
devices described in this permit must be covered under a permit issued by the Division of Air
Quality prior to construction. Failure to do so is a violation of G.S. 143-215.108 and may
subject the Permittee to civil or criminal penalties as described in G.S. 143-215.114A and 143-
215.114B.
This permit shall be effective from December 15, 2016 until May 31, 2018, is
nontransferable to future owners and operators, and shall be subject to the conditions and limitations
as specified therein.
Changes have been made to the permit stipulations. The Permittee is responsible for
carefully reading the entire permit and evaluating the requirements of each permit
stipulation. The Permittee shall comply with all terms, conditions, requirements, limitations
and restrictions set forth in this permit. Noncompliance with any permit condition is grounds
for enforcement action, for permit termination, revocation and reissuance, or modification, or
for denial of a permit renewal application. Specific changes and additions are summarized
below (note: this list may not include all changes and additions):
• The facility's name is changed from "Viscotec Automotive Products, LLC" to "Seiren
North America,LLC".
• Two electrically-heated embossing operations (ID No. IES-11) are added to the Exempt
Activities List.
Should you have any questions concerning this matter,please contact Harold Brady at 828-296-
45.00.
Sincerely,
Brendan G. Davey, P.E., Regional Supervisor
Division of Air Quality,NC DEQ
BGD:hlb
Enclosures
3
c: Asheville Regional Office
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENTAL QUALITY
DIVISION OF AIR QUALITY
AIR PERMIT NO. 09231R13
Issue Date: December 15, 2016 Effective Date: December 15, 2016
Expiration Date: May 31, 2018 Replaces Permit: 09231R12
To construct and operate air emission source(s) and/or air cleaning device(s), and for the
discharge of the associated air contaminants into the atmosphere in accordance with the provisions
of Article 2 1 B of Chapter 143, General Statutes of North Carolina(NCGS) as amended,and other
applicable Laws, Rules and Regulations,
Seiren North America, LLC
1500 E Union Street
Morganton, Burke County,North Carolina
Permit Class: Synthetic Minor
Facility ID# 1200180
(the Permittee) is hereby authorized to construct and operate the air emissions sources and/or air
cleaning devices and appurtenances described below:
__..� ___ ...._... ....____. ..__. ..____ _.._ a Emission Source Control Control System
Emission
Source ID Description System ID Description
one indirectly heated tenter frame(964 pounds of
ES-1 fabric per hour maximum throughput;maximum oil
E content of fabric 3 0%) i
one indirectly heated tenter frame(964 pounds of 1 one condenser-type packed
ES-2 fabric per hour maximum throughput;maximum oil CD-6 j bed mist eliminator(20,000
content of fabric 3.0%) acfm gas flow rate)
one indirectly heated tenter frame(840 pounds of
ES-3 fabric per hour maximum throughput,maximum oil
s content of fabric 3.0%)
one in heated tenter frame(840 pounds of — �one condenser-type packed-
ES-4 fabric per hour maximum throughput;maximum oil' CD-4 bed mist eliminator(20,000
_ . _ _ _I g_
w rate)
content of fabric 3.0/o �— one ventuflo
scrubber in
j !one natural gas-fired flame laminator(3.0 series with a vertical packed
ES-5 (mmBtu/hr maximum capacity) CD-5 tower and mist eliminator
I I (6,000 acfm gas flow rate)
Permit No. 09231RI3
Page 2
Emission Emission Source Control Control System
Source ID Description System ID Description
one indirectly heated tenter frame(2,400 pounds of
ES-6 1,fabric per hour maximum throughput;maximum oil'
content of fabric 3 0%)
one indirectly heated tenter frame(2,400 pounds of one condenser-type packed-
ES-7 fabric per hour maximum throughput;maximum oil CD-4 bed mist eliminator(20,000 i
1 content of fabric 3 0%) acfin gas flow rate)
��one indirectly heated tenter frame(1,200 pounds of
{ ES-8 j fabric per hour maximum throughput;maximum oil
content of fabric 3.0%)
ES 9 one indirectly heated tenter frame with no presetting N/A N/A
capacity ....__. I .... _.... .._.._... . __....... ....._..
...
one indirectly heated tenter frame with no presetting
ES-10 ca aci � N/A � N/A
_ ._ p_c n' _ l.. _.__. _..__.._ ................ ...
in accordance with the completed application 1200180.16A received October 13, 2016 including
any plans, specifications,previous applications, and other supporting data, all of which are filed
with the Department of Environmental Quality, Division of Air Quality(DAQ) and are incorporated
as part of this permit.
This permit is subject to the following specified conditions and limitations including any
TESTING, REPORTING, OR MONITORING REQUIREMENTS:
A. SPECIFIC CONDITIONS AND LIMITATIONS
1. Any air emission sources or control devices authorized to construct and operate above must
be operated and maintained in accordance with the provisions contained herein. The
Permittee shall comply with applicable Environmental Management Commission
Regulations, including Title 15A North Carolina Administrative Code (NCAC), Subchapter
2D .0202, 2D .0515, 2D .0516, 2D .0521, 2D .0535, 2D .0540, 2D .1100, 2Q .0315 and 2Q
.0711.
2. PERMIT RENEWAL AND EMISSION INVENTORY REQUIREMENT - The Permittee,
at least 90 days prior to the expiration date of this permit, shall request permit renewal by
letter in accordance with 15A NCAC 2Q .0304(d) and (f). Pursuant to 15A NCAC 2Q
.0203(i), no permit application fee is required for renewal of an existing air permit(without
a modification request). The renewal request (with AA application form) should be
submitted to the Regional Supervisor, DAQ. Also, at least 90 days prior to the expiration
date of this permit, the Permittee shall submit the air pollution emission inventory report
(with Certification Sheet) in accordance with 15A NCAC 2D .0202,pursuant to N.C.
General Statute 143 215.65. The report shall be submitted to the Regional Supervisor, DAQ
and shall document air pollutants emitted for the 2016 calendar year.
3. PARTICULATE CONTROL REQUIREMENT -As required by 15A NCAC 2D .0515
"Particulates from Miscellaneous Industrial Processes," particulate matter emissions from
the emission sources shall not exceed allowable emission rates. The allowable emission rates
are, as defined in 15A NCAC 2D .0515, a function of the process weight rate and shall be
Permit No. 09231R13
Page 3
determined by the following equation(s), where P is the process throughput rate in tons per
hour(tons/hr) and E is the allowable emission rate in pounds per hour(lbs/hr).
E=4.10 * (P) 0-61 for P <= 30 tons/hr, or
E= 55 * (P) o.ii_ 40 for P>30 tons/hr
4. SULFUR DIOXIDE CONTROL REQUIREMENT-As required by 15A NCAC 2D .0516
"Sulfur Dioxide Emissions from Combustion Sources," sulfur dioxide emissions from the
combustion sources shall not exceed 2.3 pounds per million Btu heat input.
5. VISIBLE EMISSIONS CONTROL REQUIREMENT -As required by 15A NCAC 2D
.0521 "Control of Visible Emissions," visible emissions from the emission sources,
manufactured after July 1, 1971, shall not be more than 20 percent opacity when averaged
over a six-minute period, except that six-minute periods averaging not more than 87 percent
opacity may occur not more than once in any hour nor more than four times in any 24-hour
period. However, sources which must comply with 15A NCAC 2D .0524 "New Source
Performance Standards" or .1110 "National Emission Standards for Hazardous Air
Pollutants" must comply with applicable visible emissions requirements contained therein.
6. NOTIFICATION REQUIREMENT - As required by 15A NCAC 2D .0535,the Permittee of
a source of excess emissions that last for more than four hours and that results from a
malfunction, a breakdown of process or control equipment or any other abnormal
conditions, shall:
a. Notify the Director or his designee of any such occurrence by 9:00 a.m. Eastern time
of the Division's next business day of becoming aware of the occurrence and
describe:
i. the name and location of the facility,
ii. the nature and cause of the malfunction or breakdown,
iii. the time when the malfunction or breakdown is first observed,
iv. the expected duration, and
V. an estimated rate of emissions.
b. Notify the Director or his designee immediately when the corrective measures have
been accomplished.
This reporting requirement does not allow the operation of the facility in excess of
Environmental Management Commission Regulations.
7. FUGITIVE DUST CONTROL REQUIREMENT- As required by 15A NCAC 2D .0540
"Particulates from Fugitive Dust Emission Sources," the Permittee shall not cause or allow
fugitive dust emissions to cause or contribute to substantive complaints or excess visible
emissions beyond the property boundary. If substantive complaints are received or excessive
fugitive dust emissions from the facility are observed beyond the property boundaries for six
Permit No. 09231R13
Page 4
minutes in any one hour (using Reference Method 22 in 40 CFR, Appendix A),the owner or
operator may be required to submit a fugitive dust plan as described in 2D .0540(f).
"Fugitive dust emissions means particulate matter that does not pass through a process
stack or vent and that is generated within plant property boundaries from activities such as:
unloading and loading areas,process areas stockpiles, stock pile working, plant parking lots,
and plant roads (including access roads and haul roads).
8. TOXIC AIR POLLUTANT EMISSIONS LIMITATION AND REPORTING
REQUIREMENT -Pursuant to 15A NCAC 2D .1100 "Control of Toxic Air Pollutants," and
in accordance with the approved application for an air toxic compliance demonstration,the
following permit limits shall not be exceeded:
� Emission
Affected Sources) Toxic Air Pollutant _Limit
Hydrogen cyanide (as HCN -Component of 0.042 lb/hr
I CNC) (74 90 8) 1.00 lb/day..
natural gas-fired flame laminator Hydrogen chloride (hydrochloric acid) —�
0.4181b/hr
(ES-5) (7647-01-0)
Toluene diisocyanate, 2,4- and 2,6- isomers 0.0007
(584-84-9,91-08-7) lb/day
a. Restrictions - To ensure compliance with the above limits,the following restrictions
shall apply:
i. emissions from the natural gas-fired flame laminator(ID No. ES-5) shall be
controlled by the venturi scrubber and packed tower(ID No. CD-5)
ii. the venture scrubber and packed tower stack(ID No. CD-5) shall be located
and operated per information provided by the facility on April 2, 2012.
9. LIMITATION TO AVOID 15A NCAC 2Q .0501 -Pursuant to 15A NCAC 2Q .0315
"Synthetic Minor Facilities," to avoid the applicability of 15A NCAC 2Q .0501 "Purpose of
Section and Requirement for a Permit," as requested by the Permittee, facility-wide
emissions shall be less than the following:
Emission Limit
Pollutant(Tons per consecutive 12-month period)
PM10 100
a. Inspection and Maintenance Requirements -
i. Condenser/Mist Eliminator Requirements - Emissions shall be controlled as
described in the permitted equipment list. To comply with the provisions of
this permit and ensure that emissions do not exceed the regulatory limits,the
Permittee shall.perform periodic inspections and maintenance (I&M) as
recommended by the manufacturer. In addition,the Permittee shall perform
Permit No. 09231R13
Page 5
an annual (for each 12 month period following the initial inspection)
inspection of each condenser system.
As a minimum, the I&M program and each annual inspection should include
the following:
A. inspection and maintenance of the structural integrity of each
condenser, including inspection for leakage of coolant and, if the
system is under positive gauge pressure, leakage of the contaminated
gas stream. To determine.leakage of the coolant,the condensate shall
be inspected for the presence of coolant.
B. inspection and maintenance of the structural integrity of duct work
and piping leading to and coming from each condenser.
ii. PM-Scrubber(Packed Tower) Requirements - Particulate matter emissions
shall be controlled as described in the permitted equipment list. To comply
with the provisions of this permit and ensure that emissions do not exceed the
regulatory limits,the Permittee shall perform periodic inspections and
maintenance (I&M) as recommended by the manufacturer. In addition,the
Permittee shall perform an annual (for each 12 month period following the
initial inspection) internal inspection of each scrubber system.
I
As a minimum,the I&M program and each annual inspection should include
the following:
A. inspection of spray nozzles,packing material, chemical feed system
(if so equipped), and the cleaning/calibration of all associated
instrumentation annually.
B. two weeks following initial start-up and startup following major
maintenance of each scrubber, the Permittee shall shut down the
system and inspect for nozzle plugging and settling of the packing.
b. RecordkeepingLRequirements - A log book shall be kept on site for each control
device and made available to Division of Air Quality personnel upon request. The
Permittee shall record all inspection,maintenance and monitoring requirements,
listed above in the log book. Any variance from the manufacturer's recommendations
shall be investigated with corrections made and date of actions recorded in the log
book.
a
10. TOXIC AIR POLLUTANT EMISSIONS LIMITATION REQUIREMENT -Pursuant to
15A NCAC 2Q .0711 "Emission Rates Requiring a Permit," for each of the below listed
toxic air pollutants (TAPs),the Permittee has made a demonstration that facility-wide actual
emissions, where one or more emission release points are obstructed or non-vertically
oriented, do not exceed the Toxic Permit Emission Rates (TPERs) listed in 15A NCAC 2Q
.0711(a). The facility shall be operated and maintained in such a manner that emissions of
any listed TAPs from the facility, including fugitive emissions, will not exceed TPERs listed
in 15A NCAC 2Q .0711(a).
Permit No. 09231R13
Page 6
a. A permit to emit any of the below listed TAPs shall be required for this facility if
actual emissions from all sources will become greater than the corresponding
TPERs.
b. PRIOR to exceeding any of these listed TPERs, the Permittee shall be responsible
for obtaining a permit to emit TAPs and for demonstrating compliance with the
requirements of 15A NCAC 2D .1100 "Control of Toxic Air Pollutants".
c. In accordance with the approved application, the Permittee shall maintain records of
operational information demonstrating that the TAP emissions do not exceed the
TPERs as listed below:
Chronic i Acute Systemic , Acute
Pollutant Carcinogens Toxicants Toxicants i Irritants
(Ib/yr)
(lb/day) (Ib/hr) (lb/hr)
Acetaldehyde (75-07-0)
Dioxane, - ! ..._ 12 �
d. Compliance with these emission limitations shall be demonstrated as set forth in
Specific Condition No. 9.
B. GENERAL CONDITIONS AND LIMITATIONS
1. In accordance with G.S. 143-215.108(c)(1), TWO COPIES OF ALL DOCUMENTS,
REPORTS, TEST DATA, MONITORING DATA,NOTIFICATIONS, REQUESTS FOR
RENEWAL,AND ANY OTHER INFORMATION REQUIRED BY THIS PERMIT shall
be submitted to the:
Regional Supervisor
North Carolina Division of Air Quality
Asheville Regional Office
2090 U.S. Highway 70
Swannanoa,NC 28778
828-296-4500
For identification purposes, each submittal should include the facility name as listed on the
permit,the facility identification number, and the permit number.
2. RECORDS RETENTION REQUIREMENT - In accordance with 15A NCAC 2D .0605,
any records required by the conditions of this permit shall be kept on site and made available
to DAQ personnel for inspection upon request. These records shall be maintained in a form
suitable and readily available for expeditious inspection and review. These records must be
kept on site for a minimum of 2 years, unless another time period is otherwise specified.
3. ANNUAL FEE PAYMENT- Pursuant to 15A NCAC 2Q .0203(a),the Permittee shall pay
the annual permit fee within 30 days of being billed by the DAQ. Failure to pay the fee in a
timely manner will cause the DAQ to initiate action to revoke the permit.
Permit No. 09231R13
Page 7
4. EQUIPMENT RELOCATION - In accordance with 15A NCAC 2Q .0301, anew air permit
shall be obtained by the Permittee prior to establishing, building, erecting, using, or
operating the emission sources or air cleaning equipment at a site or location not specified in
this permit.
5. REPORTING REQUIREMENT - In accordance with 15A NCAC 2Q .0309, any of the
following that would result in previously unpermitted, new, or increased emissions must be
reported to the Regional Supervisor, DAQ:
a. changes in the information submitted in the application regarding facility emissions;
b. changes that modify equipment or processes of existing permitted facilities; or
c. changes in the quantity or quality of materials processed.
If appropriate, modifications to the permit may then be made by the DAQ to reflect any
necessary changes in the permit conditions. In no case are any new or increased emissions
allowed that will cause a violation of the emission limitations specified herein.
6. In accordance with 15A NCAC 2Q .0309,this permit is subject to revocation or
modification by the DAQ upon a determination that information contained in the application
or presented in the support thereof is incorrect, conditions under which this permit was
granted have changed, or violations of conditions contained in this permit have occurred. In
accordance with G.S. 143-215.108(c)(1),the facility shall be properly operated and
maintained at all times in a manner that will effect an overall reduction in air pollution.
Unless otherwise specified by this permit, no emission source may be operated without the
concurrent operation of its associated air cleaning device(s) and appurtenances.
7. In accordance with G.S. 143-215.108(c)(1),this permit is nontransferable by the Permittee.
Future owners and operators must obtain a new air permit from the DAQ.
8. In accordance with G.S. 143-215.108(c)(1),this issuance of this permit in no way absolves
the Permittee of liability for any potential civil penalties which may be assessed for
violations of State law which have occurred prior to the effective date of this permit.
9. In accordance with G.S. 143-215.108(c)(1),this permit does not relieve the Permittee of the
responsibility of complying with all applicable requirements of any Federal, State, or Local
water quality or land quality control authority.
s
10. In accordance with 15A NCAC 2D .0605, reports on the operation and maintenance of the
facility shall be submitted by the Permittee to the Regional Supervisor, DAQ at such
intervals and in such form and detail as may be required by the DAQ. Information required
in such reports may include, but is not limited to,process weight rates, firing rates, hours of
operation, and preventive maintenance schedules.
11. A violation of any term or condition of this permit shall subject the Permittee to enforcement
pursuant to G.S. 143-215.114A, 143-215.11413, and 143-215.114C, including assessment of
civil and/or criminal penalties.
Permit No. 09231 R13
Page 8
12. Pursuant to North Carolina General Statute 143-215.3(a)(2), no person shall refuse entry or
access to any authorized representative of the DAQ who requests entry or access for
purposes of inspection, and who presents appropriate credentials, nor shall any person
obstruct, hamper, or interfere with any such representative while in the process of carrying
out his official duties. Refusal of entry or access may constitute grounds for permit
revocation and assessment of civil penalties.
13. In accordance with G.S. 143-215.108(c)(1),this permit does not relieve the Permittee of the
responsibility of complying with any applicable Federal, State, or Local requirements
governing the handling, disposal, or incineration of hazardous, solid, or medical wastes,
including the Resource Conservation and Recovery Act(RCRA) administered by the
Division of Waste Management.
14. PERMIT RETENTION REQUIREMENT - In accordance with 15A NCAC 2Q .0110, the
Permittee shall retain a current copy of the air permit at the site. The Permittee must make
available to personnel of the DAQ, upon request,the current copy of the air permit for the
site.
15. CLEAN AIR ACT SECTION 112(r)REQUIREMENTS -Pursuant to 15A NCAC 2D .2100
"Risk Management Program," if the Permittee is required to develop and register a risk
management plan pursuant to Section 112(r) of the Federal Clean Air Act,then the
Permittee is required to register this plan with the USEPA in accordance with 40 CFR Part
68.
16. PREVENTION OF ACCIDENTAL RELEASES - GENERAL DUTY - Pursuant to Title I
Part A Section 112(r)(1) of the Clean Air Act "Hazardous Air Pollutants - Prevention of
Accidental Releases - Purpose and General Duty," although a risk management plan may not
be required, if the Permittee produces, processes, handles, or stores any amount of a listed
hazardous substance,the Permittee has a general duty to take such steps as are necessary to
prevent the accidental release of such substance and to minimize the consequences of any
release. This condition is federally-enforceable only.
17. GENERAL EMISSIONS TESTING AND REPORTING REQUIREMENTS - If emissions
testing is required by this permit, or the DAQ, or if the Permittee submits emissions testing
to the DAQ in support of a permit application or to demonstrate compliance, the Permittee
shall perform such testing in accordance with 15A NCAC 2D .2600 and follow all DAQ
procedures including protocol approval, regional notification, report submittal, and test
results approval.
Permit No. 09231 RI
Page 9
Permit issued this the 15'h of December, 2016.
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
Brendan G. Davey, P.E.
Regional Supervisor
By Authority of the Environmental Management Commission
Air Permit No. 09231R13
F
i
i
i
ATTACHMENT to Permit No. 09231R13, December 15, 2016
Insignificant/Exempt Activities
' F;f
Source ExemptionSource of TitRegulation i V Pollutants?_.__ _
IES-1 No
-P ressurized/closed fabric dyeing operation 2Q .0102 i
No
(negligible emissions expected) (g)(14)(B)
IES-2 - Six natural gas-fired steam boilers (three
!rated at 13.2 MMBtu/hr(NSPS affected),two rated 2Q .0102
at 1.2 MMBtu/hr, and one rated at 8.3 MMBtu/hr (h)(1)(B) Yes Yes I
maximum heat input) - __ ........_ _--. ..- --.; . . ._ .._ __ _. _..- . .-.
IES-3 - Two natural gas-fired hot oil boilers (8.3 2Q .01(2 —
MMBtu/hr maximum heat input, each) (h)(1)(B) Yes Yes
IES-4 - One Visco Dry process that utilizes acetic 2Q .0102
J
yes 1 Yes
acidand ink h)(3)-..._.-..__. .11 .. ..-.._ ........ .-.....- ............. ......... ..-...... _..... ..--........ .. 1- ..-.... ....-.......-.
--'[
IES-5 - One cleaning/soap process 2Q .0102 yes Yes
(h)(3) . .. .......
2Q .0102 ]Fy
I-ES8 - one 2000 gallon acetic acid storage tank es Yes ;
_. (g)(14)(B)
IES-11 -two electrically-heated embossing 2Q .0102 No ,ill Yes
operations (h)(5)
1. Because an activity is exempted from being required to have a permit or permit modification
does not mean that the activity is exempted from an applicable requirement or that the owner
or operator of the source is exempted from demonstrating compliance with any applicable
requirement.
2. When applicable,emissions from stationary source activities identified above shall be
included in determining compliance with the permit requirements for toxic air pollutants
under 15A NCAC 2D .1100 "Control of Toxic Air Pollutants" or 2Q .0711 'Emission Rates
Requiring a Permit."
z 3. Sample permit conditions showing the regulatory requirements for exempt sources subject to