HomeMy WebLinkAboutAQ_F_2100073_20180911_ST_ProtRvw (4) =r
s'
14.
ROY COOPER NORTH CAROLINA
Governor Environmental Quality
MICHAEL S.REGAN
Secretary
MIC14AEL ABRACZINSKAS
Director
September 11,2018
Michael Aust
Manager Environmental,Health and Safety
Regulator Marine, Inc.
187 Peanut Drive
Edenton,NC 27932
Subject: Regulator Marine, Inc.
Edenton, Chowan County,North Carolina
Facility ID 21-00073,Air Permit No. 07132T1 I
Proposed Carbon Monoxide(CO)Emissions Testing of Diesel-Fired Peak Shaving
Generator ES-I4 by Integrity Air Monitoring,Inc. October 25,2018
DAQ Tracking No. 2018-275ST
Dear Mr.Aust:
The North Carolina Division of Air Quality(DAQ)has reviewed the protocol submittal form(PSF)for
CO emissions testing of generator ES-I4. Integrity Air Monitoring proposes EPA Method 3A for
oxygen(02) and EPA Method 10 for CO emissions testing. The proposed methods are acceptable for
demonstrating compliance with the applicable regulations.
ES-I4 is a diesel-fired peak shaving generator controlled by diesel oxidation catalyst CD-I4. The
generator is rated at 764 horsepower maximum capacity. 40 CFR 63 Subpart ZZZZ National Emissions
Standards for Hazardous Air Pollutants for Stationary Reciprocating Internal Combustion Engines
applies and specifies CO emissions shall be reduced by 70%or more using an oxidation catalyst. Permit
condition 2.1.C.3 states the temperature of the catalyst inlet should be maintained at
>_450 OF and< 1350 OF. The pressure drop across the catalyst should be maintained f 2 inches of water
from the pressure drop that was measured during the most recent performance test with the engine
operating at±10%of full load.
Integrity proposes testing at the inlet and outlet of the catalyst with the differential pressure across the
catalyst and temperatures being measured every minute and engine output being measured and recorded
every 5 minutes. The CO and 02 measurements should be dry and the engine should be tested at±10%of
maximum load.
rroa'mcaaouragR`E Q_
o�rtmia�xr� r
North Carolina Department of Environmental Quality I Division of Air Quality
217 West Jones Street 1 1641 Mail Service Center I Raleigh,North Carolina 27699-1641
919.707.8400
Mr.Michael Aust
Page 2
DAQ Tracking No. 2018-275ST
The proposed testing is acceptable for demonstrating compliance with the regulations. Approval of the
protocol does not exempt the tester from the minimum requirements of the methods. Deviation from the
methods remains subject to approval by DAQ. If there are any questions regarding this review,please
contact me at(919)707-8427 or Brent.Hall@ncdenr.gov.
Sincerely,
944���
Brent W.Hall
Environmental Engineer
Cc: Andrew Dickson, Integrity Robert Fisher,WARO
Central Files, Chowan County IBEAM Documents-2100073