Inspection Result: Failed Inspection Date: 2/26/2014
Partial Inspection: No Arrive and Depart Times: 12:20 PM-12:50 PM
Facility ID: 0-0-0000032432 Inspector Pam Harrelson
Facility Name TOWNSENDS, INC Insp. Type Compliance
Facility Address 270 MONCURE ROAD
PITTSBORO, NC 27312
Chatham County
Facility Located
Reason(s) Routine Compliance
Location 35.704468, -79.176041
Permit Exp. 9/30/2011
CONTACTS
Contact Type Contact Information
Regulatory Owner
since 12/1/2010
OMNTRON USA LLC , P O BOX 370 PITTSBORO, NC 27312
Manager
since 10/10/2002
ROGER MASHBURN, 270 MONCURE ROAD PITTSBORO, NC 27312, Phone: (919)
663-2050
Owner
since 1/1/1986
TOWNSENDS, INC , 1100 E 3RD ST/PO BOX 709 SILER CITY, NC 27344, Phone:
(919) 663-2050
OWNERSHIP CHANGE
New Owner Change Date Basis Transfer of Ownership Form (UST-15) Submitted
Yes 3/30/2010 TAX RECORDS No
EMERGENCY RESPONSE
Emergency Response Operator at inspection is listed in training log? No
Emergency Response Operator log (UST-26) onsite and completed with names of trained employees? No
OTHER PARTICIPANTS
Name Organization
INSPECTOR COMMENTS
Type Date Comment
Facility 2/26/2014 FACILITY WAS BOUGHT OUT OF BANKRUPTCY FROM
TOWNSENDS FARMS, INC. IN DECEMBER 2010. FACILITY CLOSED
IN OCTOBER 2011.
Corr. Prot. 2/26/2014 NO ELECTRICTY. RECTIFIER READING ZERO FOR VOLTS AND
AMPS. SYSTEM HAS BEEN INTEMPORARY CLOSURE SINCE
OCTOBER 2011.
TANKS AND PIPING INFORMATION
Tanks Tank #1(1)
Tank ID 1
TIMS Tank ID 1
Is tank registered? Yes
Date tank installed 2/20/1961
Capacity of Tank in Gallons 10000
Tank / Product use Motor Fuel
Product stored in Tank Diesel
if gasoline, Detail
If hazardous substance, CAS# or description
If other, description
Tank Status Temporarily Closed
Facility ID: 0-0-0000032432
Page 2 of 5 2/26/2014 6:47 PM
Tanks Tank #1(1)
Tank closure report submitted
Date tank last operated 10/31/2011
Inches of product in Tank 0.000000
Manifolded Tank No
Manifolded with tanks
New Tank System installed in accordance with NC or MI
Tank Construction Material (DW required after 11/1/07) Single Wall Steel
If other, description
Tank Manufacturer/Model Unknown
If other, describe
Tank material verified by
Date Pipe Installed 2/20/1961
Was UST Piping Installed on or after 11/1/2007? No
Piping Construction Material (DW required after 11/1/07) Single Wall FRP
If other, description
Pipe Manufacturer/Model Unknown
If other, describe
Pipe material verified by
If E-blend > 10% or Biodiesel Blend > 20%; Was UST-20 completed and approved?
CORROSION PROTECTION
Tank Corrosion Protection Tank #1(1)
DWM notified of current CP method No
Integrity assessment performed after 3/1/06 No
CP Method 1 Impressed Current
if other, Description
CP Installation Date 4/1/1993
CP Method 2
if other, Description
CP Installation Date
Flex Connector , Piping Extensions, and/or other metal fittings Present Elbow
Flex connector isolated from ground N/A
Source of verification of CP for Flex Connectors, piping extensions and/or other metal fittings Visual
if other, Description
Submersible pump (STP) is isolated from ground No
Piping extensions and/or other metal fittings are isolated from ground No
Flex connector, STP and/or other metal fittings protected from corrosion No
Corrosion protection method Impressed Current
Flex connector , Piping extensions, and/or other metal fittings CP Installation Date 4/26/1993
Dielectric Coating Installed (If tank installed after 12/22/88 N/A
Pipe Corrosion Protection Tank #1(1)
DWM notified of current CP method Yes
CP method FRP Piping
if other, Description
CP Installation Date 4/1/1993
Dielectric Coating Installed (If piping installed after 12/22/88 Yes
CP Conclusions
CP Requirements Met? No
Issues Permanently close the UST system (MT1H)
Impressed Current Systems System # 1
Applies to Tanks #1(1)
Current voltage 0.0000
Current Amperage 0.0000
Facility ID: 0-0-0000032432
Page 3 of 5 2/26/2014 6:47 PM
Impressed Current Systems System # 1
Last three 60-day readings available No
System operating properly No
If no, select all that apply System disabled or not operational
If other, describe
Hour Meter Reading? 57042
Hour meter Installed Yes
CP Test
No CP Test Results Provided
SPILL PREVENTION
Has DWM been notified of spill methods? Yes
Spill/Overfill Details Tank #1(1)
Is a drop tube present? No
Type of Stage I vapor recovery? Coaxial
Local Fill Tank #1(1)
Does Tank have a Remote Fill? No
Spill Protection Catchment Basin
Is spill prevention equipment provided and verified? N/A
Spill bucket is double-walled? (If installed after 11/1/07) N/A
Spill bucket is isolated or made of non-corroding materials? (If installed after 11/1/07) N/A
Date spill prevention provided 4/1/1993
Is spill prevention operating properly? No
If No, select all that apply N/A
If other, describe
OVERFILL PREVENTION
Has DWM been notified of overfill methods? Yes
Overfill Control Tank #1(1)
Is overfill prevention equipment provided and verified? Yes
Date overfill control provided 4/1/1993
Type of overfill equipment Auto Shutoff Device
Source of information for overfill control verification Visual observation
If other, describe
Is overfill control operating properly? Yes
If No, select all that apply
If other, describe
Annual overfill check date (If installed after 11/1/07)(UST-22A)
Annual overfill check results(UST-22A)
SITING AND SECONDARY CONTAINMENT
Siting And Sec.Containment-General Tank #1(1)
UST system upgraded with corrosion protection, spill and overfill before 1/1/91? No
UST system and/or piping are located within siting and secondary containment areas? No
LEAK DETECTION
General Tank #1(1)
DWM notified of leak detection method? No
Piping type Pressurized System
Suction Check Type
Type LLD present. MLLD
Facility ID: 0-0-0000032432
Page 4 of 5 2/26/2014 6:47 PM
General Tank #1(1)
Tank – Primary leak detection method Not Required
Tank - if other, specify
Tank – Secondary leak detection method
Tank - if other, specify
Piping - Primary leak detection method Not Required
Piping - if other, specify
Piping - Secondary leak detection method
Piping - if other, specify
Facility ID: 0-0-0000032432
Page 5 of 5 2/26/2014 6:47 PM
TEMPORARY CLOSURE
Temporary Closure
Temporary Closure Requirements Met? No
Issues CP system not maintained: Permanently close UST System (CL3:A7)
TRANSPORTER/FUEL DELIVERY INFORMATION
Delivery Information Tank #1(1)
All deliveries made to permitted tanks
SITE DIAGRAM