Loading...
HomeMy WebLinkAbout10061_OPR Brownfields Site_VIMP_Rev 1_01182021 Via Email January 18, 2021 NCDEQ – Division of Waste Management Brownfields Program 1646 Mail Service Center Raleigh, NC 27699-1646 Attn: Mr. Kelly Johnson, PG Re: Vapor Intrusion Mitigation Plan – Revision 1 Old Pineville Road Charlotte, North Carolina Brownfields Project No. 10061-06-060 H&H Project No. NVR-010 Dear Mr. Johnson: Enclosed please find a copy of the Vapor Intrusion Mitigation Plan (VIMP) – Revision 1 prepared for the Old Pineville Road Brownfields property (Brownfields Project No. 10061-06-060) located in Charlotte, Mecklenburg County. Should you have any questions or need additional information, please do not hesitate to contact us at (704) 586-0007. Sincerely, Hart & Hickman, PC Trinh DeSa, PE Alexis McKenzie, EI Senior Project Engineer Project Engineer Enclosure cc: Mr. Christopher DeCorte, NVR, Inc. (Via Email) Mr. Kevin Slaughter, NCDEQ (Via Email) Ms. Jordan Thompson, NCDEQ (Via Email) Mr. Ralph McGee, H&H (Via Email) #C-1269 Engineering #C-245 Geology Vapor Intrusion Mitigation Plan Revision 1 Old Pineville Road 4928 Old Pineville Road & 649 Scholtz Road Charlotte, North Carolina Brownfields Project No. 10061-06-060 H&H Job No. NVR-010 September 10, 2020 Revised January 18, 2021 i \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx Vapor Intrusion Mitigation Plan – Revision 1 Old Pineville Road Charlotte, North Carolina Brownfields Project No. 10061-06-060 H&H Job No. NVR-010 Table of Contents 1.0 Introduction ................................................................................................................ 1 2.0 Design Basis ................................................................................................................ 3 3.0 Quality Assurance / Quality Control ........................................................................ 7 4.0 Post-Construction System Effectiveness Testing .................................................... 8 5.0 Post-Construction VIMS Vacuum Influence Monitoring .................................... 14 6.0 Future Tenants & Building Uses ............................................................................ 15 7.0 Reporting .................................................................................................................. 16 Figures Figure 1 Site Development Plan Figure 2 Sample Location Map Tables Table 1 Summary of Soil and Sediment Analytical Data Table 2 Summary of Groundwater Analytical Data Attachments Attachment 1 Vapor Intrusion Mitigation Plan – Sheets VM-1 through VM-4 Attachment 2 Vapor Intrusion Mitigation System Product Specifications 1 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx Vapor Intrusion Mitigation Plan – Revision 1 Old Pineville Road Charlotte, North Carolina Brownfields Project No. 10061-06-060 H&H Job No. NVR-010 1.0 Introduction Hart & Hickman, PC (H&H) has prepared this Vapor Intrusion Mitigation Plan (VIMP) for installation of a vapor intrusion mitigation system (VIMS) during construction of the proposed townhome development at the Old Pineville Road Brownfields property (Brownfields Project No. 10061-06-060) located at 4928 Old Pineville Road and 649 Scholtz Road in Charlotte, North Carolina (Site or subject Site). The proposed redevelopment is known as Old Pineville Townhomes. The Old Pineville Townhomes project is being developed for residential use by Ryan Homes, an NVR, Inc. (NVR) company, and includes proposed for-sale townhome units. This development will include construction of fifteen (15) townhome complexes which includes one 3-unit townhome complex, one 4-unit townhome complex, five 7-unit townhome complexes, and eight 8-unit townhome complexes for a total of 106 individual residential townhome units. A Site Development Plan depicting the proposed townhome building layout is included as Figure 1. As outlined in the North Carolina Department of Environmental Quality (DEQ) approved Environmental Management Plan (EMP) dated January 3, 2020, results of previous soil and groundwater sampling completed at the Site did not indicate that vapor mitigation is warranted for the ground level residential component of each proposed building. However, based on the DEQ Brownfields Program Minimum Requirements for Townhome Developments document, installation of a minimum of a passive vapor intrusion mitigation system is needed for each townhome building. A summary of soil, sediment, and groundwater analytical data is provided as Tables 1 and 2, and a sample location map is provided as Figure 2. This VIMP has been prepared for installation of a passive VIMS in accordance with Land Use Restriction 4.a. of the recorded Notice of Brownfields Property for the Site and DEQ Brownfields minimum requirements for townhome developments. The VIMP is described in the following 2 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx sections and was designed in accordance with the DEQ Division of Waste Management (DWM) Vapor Intrusion Guidance (VI Guidance) dated March 2018 and the DEQ Brownfields Program Preliminary Vapor Intrusion Mitigation System Design Submittal New Construction Minimum Requirements Checklist included as Appendix H of the VI Guidance document. 3 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx 2.0 Design Basis The VIMP is included in Attachment 1 (Sheets VM-1, VM-1A, VM-2, VM-3, and VM-4) and will be used to guide construction of the VIMS. Each of the 106 proposed Old Pineville Townhome residential townhome units are three- or four-story structures that will be built with a concrete slab-on-grade foundation with block footings below load bearing walls. The block footings are proposed to be poured prior to the slab-on-grade. Each townhome unit includes a stairwell, garage, and/or living spaces located on the ground floor of the structure. The ground floor for each townhome unit is approximately 640 square feet. The majority of the units will contain three floors, but some units will contain a loft located on a fourth floor. Some homes are proposed to have a small attic space above the fourth floor to house mechanical equipment and the other townhomes are proposed to have a flat roof. Based on information provided by Ryan Homes, there are three internal unit floor plans and three end unit floor plans with two potential elevations for each townhome unit. Therefore, the VIMS design includes each potential floor plan as depicted on Sheets VM-2, VM-3, and VM-4. The different building elevations do not change the structural layout as depicted in the Attachment 1 Sheets. Please note that the final floor plan orientation for each specific lot will be selected at a later date. The VIMP includes installation of the Vaporblock® Plus 20 (VBP20) vapor barrier manufactured by Raven Industries (Raven) beneath the concrete slab for each residential unit. VBP20 is an ASTM-certified 20-mil, multi-layer, chemically resistant vapor barrier, designed to prevent the migration of VOCs. Technical specifications and installation instructions obtained from Raven for the VBP20 vapor barrier are provided in Attachment 2. The VIMP specifies that the vapor barrier will be installed per manufacturer installation instructions (Attachment 2). Briefly, VBP20 will be installed by the construction contractor to cover the ground surface below the entire area of each proposed ground floor slab. The exterior edges of the VBP20 will be laid above the block footings below the concrete slab or attached and sealed to existing concrete by utilizing VaporSeal™ tape or Butyl Seal double-sided tape. Seams 4 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx within the building footprint will have a minimum 12-inch overlap and will be sealed with VaporSeal™ tape. Small puncture holes will be sealed with the VaporSeal™ tape or Pour-N- Seal™ and larger holes, tears, or damage will be repaired using a patch that overlaps the damaged area and then will be taped along the seams. In areas where utility penetrations (i.e., piping, ducts, etc.) are present and the use of tape is not practical or deemed as “ineffective” by the design engineer, the Pour-N-Seal™ method will be used to form an airtight seal. Note that other vapor barrier bonding products (i.e., tapes, epoxies, etc.) that do not contain compounds of concern for the Site and are approved by the design engineer and by the vapor barrier manufacturer may be used to seal the liner. Please also note that an equivalent vapor barrier approved by the design engineer which meets the criteria specified in Sheet VM-1A of the VIMP may also be used by the installation contractor, such as Drago Wrap® manufactured by Stego Industries. If Drago Wrap® or another design engineer approved alternative vapor barrier is selected for use, DEQ will be notified in writing. The VIMP also includes installation of a passive mitigation system beneath the ground level slab of each occupied residential space to further reduce the potential for vapor intrusion through passive sub-slab vapor extraction. Out of an abundance of caution, the VIMS and sub-slab vapor extraction treatment will be extended below the ground-level garages of the townhomes. Sub-slab vapor extraction will be accomplished using siphon ventilators and poly-vinyl chloride (PVC) vapor collection/conveyance piping which will collect vapor from beneath the ground floor slabs of each building and discharge the vapor through exhaust stacks above the building roof. To enhance sub-slab vapor transmission and collection effectiveness, a uniform layer of high permeability stone (clean #57 or similar stone) will be installed directly below the concrete slab to allow for air movement beneath the entirety of the slab. Sub-slab vapor collection piping (3-inch diameter) will be installed within the high permeability stone layer. The thickness of the high permeability stone around the piping will extend a minimum of 1-inch above the piping and minimum of 1-inch below the sub-slab piping (for example, 5-inches of gravel around a 3-inch pipe). In areas without sub-slab piping, a minimum thickness of 4 inches of clean stone is required. 5 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx The VIMP includes Empire Model Ventilator SV04SS (stainless steel) siphon ventilator (or an equivalent alternative passive ventilator approved by the design engineer) installed on the discharge end of the exhaust stack penetrating the roof and discharging vapor to the atmosphere above the roof. The siphon ventilator is a stationary exhaust device with no moving parts that functions to enhance the stack effect and promote air exhaust from the VIMS piping when wind is blowing. During times of no wind, the siphon ventilator continues to be open to the atmosphere to allow for vapors to discharge from the riser pipe due to the stack effect. One SV04SS siphon ventilator will be installed at each individual townhome unit. Ryan Homes has indicated that the townhomes include fee-simple property ownership contracts. Therefore, interconnected pipes between townhome units are not allowed by the contracts. Thus, each townhome unit will contain its own VIMS with sub-slab vent piping, one riser with exhaust ventilator, and one monitoring point. Based on the small size of each unit footprint (640 sq ft), one exhaust riser pipe with siphon ventilator per unit is expected to sufficiently provide the necessary vapor extraction from the sub-slab annular space. In accordance with ANSI radon system standards for townhomes, the discharge point location of the exhaust riser piping shall be a minimum of 1-ft above the building roof in a vertical orientation. In addition, the exhaust discharge point location shall be a minimum of 10-ft horizontally from an operable opening (e.g., window, door, air intake, etc.), or a minimum of 2-ft above a stationary opening (e.g., window or door), or a minimum of 3-ft above a mechanical air intake. The locations for the siphon ventilator on these townhomes will be positioned in accordance with the standards noted above. In the event the system needs to be activated with electric fans (see Section 4.4), the VIMP includes vacuum measuring points (depicted in Sheets VM-1A, VM-2, VM-3, and VM-4) to measure the pressure differential between indoor air and the sub-slab. A minimum of one vacuum measuring point will be installed for each townhome unit. To prevent disrupting residents in the future once the units are occupied, the vacuum measuring point access ports will be located on the outside of the buildings (see Sheets VM-1 and VM-1A). The multi-unit townhome buildings will contain one vacuum measuring point located under the living space or front of each interior unit, and one measuring point located under the garage or backside of each end unit (see Details 10A and 10B on Sheet VM-1A). 6 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx During VMS installation, minor modifications to the VIMS piping, monitoring points, and exhaust locations may be necessary to account for construction activities related to non-VIMS building components. These modifications will be approved by the design engineer and will be completed in general accordance with this VIMS design in the DEQ-approved VIMP. 7 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx 3.0 Quality Assurance / Quality Control For quality assurance and quality control purposes, inspections will be conducted for each section of slab during the following phases of VIMS installation activities: • after installation of horizontal collection system and gravel base placement, • after vapor barrier installation and prior to the pouring the concrete building slab, • after installation of vertical exhaust riser pipe and exhaust ventilator. Each inspection will be performed by, or under direction of, the design engineer certifying the VIMP. The inspections will include field logs and photographs for each section of slab. As requested, the engineer certifying the report, or designee, will provide DEQ with 48-hrs notice prior to conducting the inspections. 8 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx 4.0 Post-Construction System Effectiveness Testing Vacuum Influence Testing Following installation of the horizontal extraction piping, vapor barrier, and the concrete slab has been poured, vacuum influence testing will be conducted on the VIMS vent piping network to confirm that the VIMS will provide adequate vacuum influence below the slab should the system be activated with electric fans in the future. Electric radon fans will be attached to the vertical risers and vacuum will be measured at the extraction fan locations and at the vacuum measuring points for the section of slab being evaluated. The type of fans used for the vacuum influence testing will be provided to DEQ along with the vacuum influence testing results. The results of the influence tests will be submitted to DEQ with the vapor mitigation system installation report, unless the influence test reveals that modifications are needed to the VIMS to achieve vacuum influence of a minimum of 4 pascals (0.016 inches water content). In this case, the test results will be provided to DEQ to facilitate VIMS repairs or modifications. As described above, the VIMS design includes one siphon ventilator and exhaust riser per unit (one per 640 sq ft). The vacuum influence testing will be conducted with radon style electric fans (i.e., RadonAway RP-145 or Festa AMG Legend) similar to fans that would be used in an active VIMS scenario. One electric fan will be placed on each riser in each unit and vacuum will be measured at the corresponding monitoring point. Vacuum influence testing results will be documented in the VIMS installation completion report. Sub-Slab Soil Gas Sampling Upon completion of successful vacuum influence testing and prior to occupancy of the Site buildings, sub-slab soil gas samples will be collected from beneath the townhome buildings to evaluate the potential presence of compounds at levels of potential concern with the VIMS operational. Two sub-slab soil gas samples will be collected from select vacuum measuring points in townhome buildings with three and four units, and three sub-slab soil gas samples will be collected beneath each slab of townhome buildings with seven or eight units. The sub-slab soil gas sample locations will be chosen in conservative locations, such as areas with lower vacuum as measured during the vacuum influence testing. Preliminary locations of the proposed sub-slab soil gas sampling points are shown on the design sheet VM-1A (Attachment 1). Sub-slab soil gas 9 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx testing will be conducted after a minimum of two weeks following the installation of the concrete slab. Due to the anticipated construction schedule, multiple visits will likely be required to complete sub-slab soil gas sampling activities. One duplicate sub-slab soil gas sample will be collected for each townhome building for quality assurance/quality control (QA/QC) purposes. The duplicate will be collected from one of the measuring points using a laboratory supplied stainless-steel sample “T” fitting which allows two samples to be collected simultaneously from a single measuring point. The vacuum measuring points will be sampled by securing an expandable plug with sample port (i.e., an Ex-Cap) into the vacuum measuring point to create an air-tight seal. The sub-slab soil gas sample will then be collected in general accordance with the DEQ DWM VI Guidance. Prior to sample collection, a leak test will be performed on each vacuum measuring point by placing a shroud around the sealed sampling point and sampling train, flooding the air within the shroud with helium gas, then purging sub-slab soil gas from the sampling point with an electric air pump or syringe and collecting the purged vapor into a Tedlar bag. A helium gas detector will be used to measure helium concentrations within the shroud and the Tedlar bag sample and the concentrations will be recorded in the field notes. The leak test will be considered successful if the helium concentration measured in the sub-slab soil gas purged from the sampling point and collected into the Tedlar bag is less than 10% of the concentration measured within the shroud. If the helium test is unsuccessful, measures will be taken to identify and address the source of the leak and additional leak testing will be performed. A minimum of 3 volumes will be purged from the sample train prior to and during the leak check. The sub-slab soil gas samples will be collected in 1-liter Summa canisters at an approximate flow rate of 100 mL/min. The vacuum of the Summa canisters will be measured at the start and end of sampling event, and will be recorded on the chain-of-custody and within the field notes. The vacuum in each canister at the conclusion of the sampling event must remain above 0 inches of mercury (inHg), and ideally around 5 inHg, in accordance with laboratory standard operating procedures. 10 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx The samples will be submitted to a qualified laboratory under standard chain of custody protocols for analysis of volatile organic compounds (VOCs) by EPA Method TO-15 and the laboratory will be instructed to report J-flag concentrations for each compound. In addition, H&H will request that the laboratory report compound concentrations to the lower of the laboratory method detection limits or the DEQ DWM Residential Vapor Intrusion Sub-slab and Exterior Soil Gas Screening Levels (SGSLs). Upon receipt of the sub-slab soil gas sample analytical results, H&H will use the most current version of the DEQ Risk Calculator to evaluate potential vapor intrusion risks for a residential use scenario based on the proposed use of the Site. If calculated cumulative risks are greater than 1x10-4 for potential carcinogenic risks and/or above a hazard index of 1 for potential non-carcinogenic risks, indoor air sampling will be completed, as described below. Note that the generic sub-slab soil gas to indoor air attenuation factor that is the basis for DEQ risk calculation is conservative and is intended to estimate a potential upper-bound indoor air concentration accounting for temporal variability. In addition, the sub-slab soil gas to indoor air attenuation factors do not account for a VIMS with a vapor barrier and sub-slab vapor extraction that will greatly reduce the potential for vapor intrusion. DEQ DWM VI Guidance indicates that if sub-slab soil gas concentrations do not exceed acceptable risk levels, typically no further investigation is necessary. However, as a very conservative approach, if the chlorinated solvents PCE or TCE are detected in the sub-slab soil gas samples above their respective Residential Vapor Intrusion SGSLs, indoor air sampling will be conducted as described below. Post-construction sub-slab soil gas sampling will be completed on an annual basis for two years following completion of the initial sampling event. A Site-specific list of VOCs for analysis will be developed after the initial round of sub-slab soil gas sampling. Supplemental sub-slab soil gas sampling will be completed using the methods discussed above. If sub-slab soil gas sample results are within acceptable risk levels for the three sampling events (including the initial sampling event) a request to reduce the frequency of sub-slab soil gas sampling to one sample every 5 years will be submitted for DEQ review. 11 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx Indoor Air Sampling (if warranted) The buildings are intended to be occupied shortly following construction completion and operation of the HVAC systems. Therefore, the indoor air sampling event (if warranted) for each affected slab will be conducted following construction, including completion of the VIMS, but prior to connecting the building to utilities. If indoor sampling is warranted, one indoor air sample will be collected from each individual building slab based on the sub-slab soil gas sample analytical data as described above. Because each slab contains multiple units, the indoor air sample will either be collected from a central unit, or from a unit directly above the sub-slab sample location that contained unacceptable risk levels or detections of PCE or TCE at concentrations above the DEQ DWM Residential Vapor Intrusion SGSLs. Each indoor air sample will be collected in accordance with the DWM VI Guidance, using a laboratory supplied individually certified 6-liter Summa canister over a 24-hour period and analyzed for select VOCs by EPA Method TO-15. The VOCs for the select analyte list will be determined based on the compounds detected within the sub-slab soil gas samples, and per discussion between H&H and DEQ. Each indoor air Summa canister will be connected to a dedicated 3 ft sampling cane which will place the indoor air sample intake at a height consistent with the breathing zone when the sample canister is set on its base. Periodic checks will be conducted by H&H to monitor the pressure within the Summa canisters to confirm adequate sample volume is collected. Following sample collection, the samples will be shipped to the laboratory under standard chain of custody protocol. The analytical laboratory will be instructed to report J-flag concentrations for each compound. In addition, the laboratory will be requested to report results to laboratory method detection limits below the DEQ DWM Residential Vapor Intrusion Indoor Air Screening Levels (IASLs). For QA/QC purposes, one duplicate sample and one background air sample will be collected during each indoor air sampling event. In addition, the Indoor Air Building Survey (Appendix C of the DWM VI Guidance) will be completed for each sampling event. Note, new construction materials, such as paint, carpet, etc., which could be sources of compounds of concern in indoor air, may cause interference with Site-specific compounds during indoor air 12 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx sampling. Therefore, the construction contractor will be requested to provide safety data sheets (SDS) for materials used during construction which will be submitted to DEQ. Based upon the results of the indoor air sampling, H&H will make recommendations in general accordance with the DWM VI Guidance. It is anticipated that the recommendations will consist of one of the following: • The VIMS is effective, and no further sampling of indoor air is warranted (per the DWM VI Guidance, in the case where calculated cumulative risks are below 1 x 10-4 for potential carcinogenic risks and below a hazard index of 1 for potential non-carcinogenic risks). • Additional indoor air sampling is warranted to confirm that the VIMS is effective (per the DWM VI Guidance, in the case where calculated cumulative risks are greater than 1x10-4 for potential carcinogenic risks or above a hazard index of 1 for potential non-carcinogenic risks). If additional indoor air sampling is required, modifications to the existing system(s) will first be evaluated to increase effectiveness (i.e., installing a different siphon ventilator or a wind-driven turbine ventilator fan). DEQ will be notified of alterations to the system(s). Should results of post-construction indoor air testing continue to indicate potential unacceptable vapor intrusion risks to occupants of the building(s), active fans will be installed at the discharge end of the riser duct piping (as needed) to convert the system from passive to active sub-slab depressurization. DEQ will be notified of alterations to the system(s). Sub-Slab Soil Gas and Indoor Air and Effectiveness Reporting The results of the sub-slab soil gas and indoor air sampling (if warranted) will be submitted to DEQ with the VIMS installation completion report for the proposed townhome buildings. However, if additional indoor air sampling is required based upon the recommendations above, a report of the indoor air sampling will be submitted to DEQ after completion of the sampling and receipt of the analytical data. As mentioned above, two post-construction sub-slab soil gas sampling events will be completed on an annual basis following construction of the townhomes. 13 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx Brief reports will be submitted to DEQ to document the results of the post-construction sub-slab soil gas sampling events after completion of the sampling and receipt of the analytical data. 14 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx 5.0 Post-Construction VIMS Vacuum Influence Monitoring The VIMS is proposed as a passive system which will utilize sub-slab vapor extraction through vapor extraction piping and siphon ventilators to enhance the stack effect. As such, post-occupancy differential pressure testing is not anticipated. If the VIMS is converted to an active system based on results of post-construction sub-slab soil gas and indoor air assessment results, vapor mitigation system modifications and plans for additional indoor air sampling and long-term differential pressure monitoring across the slab will be submitted to DEQ Brownfields Program for approval prior to implementation. Example specifications for a fan that may be used if conversion to an active system is deemed necessary are included in Attachment 2. Please note that the results of the influence testing (Section 4.0) will be reviewed and used to select an appropriate fan, in the event that conversion to an active system is warranted. If the system is converted to active, low vacuum alarms will be installed with the electric fans at each riser location. 15 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx 6.0 Future Tenants & Building Uses The home owner’s association (HOA) or property management group will be responsible for the continued operation of the VIMS in accordance with the VIMP. The future use of the proposed Site buildings is individual ownership of the townhome units. After occupancy in the townhomes, the townhome community HOA will maintain the vapor mitigation piping and fans. If vapor mitigation components are damaged or need to be altered for building renovations, the homeowners will be instructed to contact the HOA. The HOA shall contact a North Carolina PE to oversee or inspect the activities, and a report will be submitted to DEQ detailing the repairs or alterations. To aid in identification of the vapor mitigation piping, the mitigation piping will be labeled with “Vapor Mitigation – Contact HOA”, or similar language, on all accessible piping at intervals of no greater than 10-linear feet and the active fans will be labeled with “Vapor Mitigation System – Contact HOA if Fan Is Not Operating or Damaged”, or similar. 16 \\hhfs01\masterfiles\aaa-master projects\nvr, inc\nvr-010 opr\revision 1\opr brownfields vimp_rev 1.docx 7.0 Reporting A vapor intrusion mitigation system installation report (sealed by a NC-licensed PE) that documents installation activities associated with the VIMS will be submitted to DEQ following confirmation that the mitigation system is installed, effective, and operating as designed. The report will include a summary of VIMS installation activities, quality assurance and quality control measures, post-installation system effectiveness testing including sub-slab soil gas and/or indoor air assessment (if warranted) results, inspection documents, SDSs, and an opinion as to whether the VIMS was installed in accordance with the DEQ approved VIMP and is protective of public health as defined by the PE seal on the report. Due to the townhome construction and occupancy schedule, several vapor mitigation system installation completion reports may be submitted to DEQ for review. In order to provide guidance for post-construction maintenance of the VIMS, an operations and maintenance (O&M) plan will be prepared by a NC-licensed PE and submitted to DEQ upon construction of all the units. The O&M plan will include the procedures to be followed during required annual third-party inspections of the VIMS. Inspections will include visual observations of the building slabs and perimeter/footer edges for cracks or damage and inspections of the siphon ventilators for damage or rust. The inspections will be documented in a system certification letter to be submitted with the annual LURU. The certification letter will be signed and sealed by a NC licensed PE. Further details will be provided in the O&M plan submittal. Figures REVISION NO. 0 JOB NO. NVR-010 DATE: 8-28-20 FIGURE NO. 1 OLD PINEVILLE ROAD 4928 OLD PINEVILLE ROAD & 649 SCHOLTZ ROAD CHARLOTTE, NORTH CAROLINA SITE DEVELOPMENT PLAN LEGEND SITE PROPERTY BOUNDARY LYNX LIGHT RAIL PROPOSED TOWNHOME FOOTPRINTS 2923 South Tryon Street-Suite 100 Charlotte, North Carolina 28203 704-586-0007(p) 704-586-0373(f) License # C-1269 / #C-245 Geology ACME SOUTHERN / SOUTH BLVD (4900 SOUTH BLVD)OLD PINEVILLE ROADSCHOLTZ R O A D FORMER CATAWBA CHAR-LAB FACILITY (5046 OLD PINEVILLE ROAD) NOTES: 1.PROPOSED REDEVELOPMENT OVERLAY OBTAINED FROM SITE PLAN PROVIDED BY BOHLER ENGINEERING. COMMERCIAL RETAIL COMMERCIAL / L I G H T I N D U S T R I A L COMMERCIAL / L I G H T I N D U S T R I A L S:\AAA-Master Projects\NVR, Inc\NVR-010 OPR\Figures\Site and Surround Map_R1.dwg, 8/28/2020 5:55:59 PM, amckenzie REVISION NO. 0 JOB NO. BOU-012 DATE: 11-7-19 FIGURE NO. 2 OLD PINEVILLE ROAD 4928 OLD PINEVILLE ROAD CHARLOTTE, NORTH CAROLINA SAMPLE LOCATION MAP LEGEND BROWNFIELDS PROPERTY BOUNDARY DRAINAGE DITCH LYNX LIGHT RAIL HISTORICAL SOIL BORING HISTORICAL TEMPORARY GROUNDWATER MONITORING WELL HISTORICAL SURFACE WATER SAMPLE LOCATION HISTORICAL SEDIMENT SAMPLE LOCATION SB-1 SB-2 BG SW-2 SW-1 TW-3 TW-4 TW-1 TW-2 SB-4 SB-3 SB-6 2923 South Tryon Street-Suite 100 Charlotte, North Carolina 28203 704-586-0007(p) 704-586-0373(f) License # C-1269 / #C-245 GeologyOLD PINEVILLE ROADSCHOLTZ RO A D NOTES: 1.HISTORICAL SOIL, GROUNDWATER, SEDIMENT, AND SURFACE WATER SAMPLES WERE COLLECTED BY ECS DURING PHASE II ESA ACTIVITES ON JANUARY 29-31, 2007. FORMER METAL WAREHOUSE OUTFALL S:\AAA-Master Projects\NVR, Inc\NVR-010 OPR\Figures\Site and Surround Map_R1.dwg, 9/2/2020 9:29:31 AM, amckenzie Tables Table 1Summary of Soil and Sediment Analytical DataOld Pineville RoadBPN 10061-06-060Charlotte, North CarolinaH&H Job No. BOU-012SB-1 SB-2 SB-3 SB-4 SB-5 TW-1 TW-2 TW-3 TW-4 OUTFALL BG-1 BG-2Depth (ft bgs) 0.5-2 0.5-2 0.5-2 0.5-2 0.5-2 0.5-2 0.5-2 0.5-4 0.5-4 Sediment 0.5-2 3-5Date 1/29/2007 1/30/2007 1/30/2007 1/30/2007 1/30/2007 1/30/2007 1/30/2007 1/30/2007 1/30/2007 1/29/2007 1/30/2007 1/30/2007 Range Range MeanVOCs (8260B) mg/kgAcetone 0.140 0.330 0.0023 0.074<0.00220.330 0.053 0.120 0.031 0.057NA NA12,000 140,000-- -- --Methyl Ethyl Ketone (2-Butanone)<0.026 <0.024 <0.019 <0.023 <0.0220.031<0.026 <0.020 <0.023 <0.019 NA NA5,500 40,000p-Isopropyltoluene<0.0190.0054<0.014 <0.017 <0.0017 <0.018 <0.019 <0.015 <0.017 <0.014 NA NA NE NE -- -- --Toluene<0.00650.0082<0.0046 <0.0058 <0.0055 <0.0061 <0.0064 <0.0051 <0.0058 <0.0047 NA NA0.87 4.0-- -- --SVOCs (8270D) mg/kg-- --Fluoranthene<0.110 <0.430 <0.420 <0.420 <0.450 <1.800 <0.430 <0.420 <0.4500.670 JNA NA480 6,000--Pyrene<0.940 <0.430 <0.420 <0.420 <0.450 <1.800 <0.430 <0.420 <0.4500.940 JNA NA360 4,500--Metals (6010/7470) mg/kgArsenic 4.8 6.6 5.2 4.7 5.2 5.5 4.8 7.8 4.7 2.3 11 9.10.68 3.0 9.1 - 11 1.0 - 18 4.8Barium 110 66 40 72 69 110 32 150 62 100 100 673,100 47,000 67 - 100 50 - 1,000 356Cadmium 0.65 J 1.1 1.1 0.86 J 0.80 J 0.92 J 1 1 1.1 0.36 J 2.8 1.914 200 1.9 -2.8 1.0 - 10* 4.3Chromium (total) 35 45 60 44 38 41 52 49 36 22 60 49-- -- 49 - 60 7.0 - 300 65Hexavalent ChromiumNA NA NA NA NA NA NA NA NA NA NA NA0.31 6.5NANS NSTrivalent ChromiumNA NA NA NA NA NA NA NA NA NA NA NA23,000 350,000NANS NSLead 38 5.2 12 11 11 56 29 14 23.0 61.0 18 12400 800 12 - 18 ND - 50 16Mercury 0.11 0.091 0.18 0.15 0.22 0.11 0.12 0.082 0.23 0.066 0.28 0.0572.3 9.7 0.057 - 0.28 0.03 - 0.52 0.121Selenium<2.1 <2.0 <1.9 <1.9 <2.0 <2.0<1.9 <1.9 <2.0 <1.7 <2.0 <2.078 1,200 ND - 2.0 <0.1 - 0.8 0.42Silver<1.0 <0.98 <0.96 <0.95 <1.0 <1.0 <0.97 <0.94 <1.0 <0.86 <1.0 <0.9878 1,200 ND - 1.0 ND - 5.0 NSNotes:1) North Carolina Department of Environmental Quality (DEQ) Inactive Hazardous Sites Branch (IHSB) Preliminary Soil Remediation Goals (PSRGs) (May 2019)2) Range and mean values of background metals for North Carolina soils taken from Elements in North American Soils by Dragun and Chekiri, 2005. Background Cd and Ag concentrations were taken from Southeastern and Conterminous US soils.Soil concentrations are reported in milligrams per kilogram (mg/kg).Compound concentrations are reported to the laboratory method detection limits.Aside from metals, only those compounds detected in at least one sample are shown above.Laboratory analytical methods are shown in parentheses.VOCs = volatile organic compounds; SVOCs = semi-volatile organic compounds; ft bgs= feet below ground surfaceBRL = below laboratory reporting limit; NE = Not Established; ND = Non Detect; NS= Not Specified; NA = Not Analyzed; -- = Not ApplicableJ = compound was detected above the laboratory method detection limit, but below the laboratory reporting limit resulting in an estimated concentration. Soil and sediment samples collected by ECS during Phase II ESA activities. Sample IDSample LocationPhase II ESA (ECS - 2007)StainDrainage DitchDrainage Ditch Stain BuildlingResidential PSRGs (1)Industrial/ Commercial PSRGs (1)Site-specific Background Metals in SoilRegional Background Metals in Soil (2)BackgroundBuildingDowngradientUpgradientSouthern BoundarySediment at Scholtz Road OutfallS:\AAA‐Master Projects\Boulevard Realty Estate Advisors (BOU)\BOU‐012  4928 Old Pineville Rd\EMP\4928 Old Pineville Road EMP Data Tables11/6/2019Table 1 (Page 1 of 1)Hart & Hickman, PC Table 2Summary of Groundwater Analytical DataOld Pineville RoadCharlotte, North CarolinaBrownfields Property No. 10061-06-060H&H Job No. BOU-012Sample ID TW-1 TW-2 TW-3 TW-4Date 1/31/2007 1/31/2007 1/31/2007 1/31/2007Sample LocationUpgradient at Drainage DitchCross/Downgradient DowngradientDowngradient at BuildingUnitsVOCs (8260B/6200B/602)Trichlorofluoromethane<2.0 <2.0 <2.09.72,000NE NESVOCs (8270D/625)ALL BRL ALL BRL ALL BRL ALL BRL-- -- --PCBs (8082)ALL BRL ALL BRL ALL BRL ALL BRL-- -- --Metals (6010B/7470A)Arsenic<0.010 <0.010 <0.0010 <0.01010-- --Barium0.032 0.068 0.029 0.12700-- --Cadmium<0.0010 <0.0010 <0.0010 <0.00102-- --Chromium (total)0.0038 J 0.0030 J<0.00500.0039 J10-- --Lead0.0033 J 0.0026 J 0.0032 0.0041 J15-- --Mercury<0.0002 <0.0002 <0.0002 <0.00021-- --Selenium<0.020 <0.020 <0.020 <0.02020-- --Silver<0.0050 <0.0050 <0.0050 <0.005020-- --Notes:1) North Carolina Department of Environmental Quality (DEQ) 15A North Carolina Administrative Code 02L.0202 Groundwater Quality Standard (2L Standard) revised February 2018.2) DEQ Division of Waste Management (DWM) Vapor Intrusion Groundwater Screening Levels (GWSLs) (Februrary 2018)Compound concentrations are reported in micrograms per liter (μg/L).Compound concentrations are reported to the laboratory method detection limits.Aside from metals, only those compounds detected in at least one sample are shown above.Laboratory analytical methods are shown in parenthesesVOCs = volatile organic compounds; SVOCs = semi-volatile organic compounds; PCBs = polychlorinated biphenylsNE = Not Established; -- = Not Applicable; BRL = below reporting limitJ = compound was detected above the laboratory method detection limit, but below the laboratory reporting limit resulting in an estimated concentration.Groundwater samples collected by ECS during Phase II ESA activities. µg/L2L Groundwater Standard (1)Residential Vapor Intrusion GWSLs (2) Non-Residential Vapor Intrusion GWSLs (2)S:\AAA‐Master Projects\Boulevard Realty Estate Advisors (BOU)\BOU‐012  4928 Old Pineville Rd\EMP\4928 Old Pineville Road EMP Data Tables11/6/2019Table 3 (Page 1 of 1)Hart & Hickman, PC Attachment 1 Vapor Intrusion Mitigation Plan – Sheets VM-1 through VM-4 VIMS VAPOR LINER AND BASE COURSE (TYP)1 BASE COURSE - CLEAN #57 STONE MIN 4" THICK BENEATH VIMS VAPOR LINER VAPOR LINER (SEE SPECIFICATION #1) CONCRETE FLOOR SLAB SUBBASE NTSVM1 SECTION THROUGH TURNED DOWN SLAB AT DRIVEWAY4 NTSVM1 VAPOR LINER SEALED TO CONCRETE PER MANUFACTURER INSTRUCTIONS. GARAGE DRIVEWAY STUD WALL OR EXTERNAL WALL (NOT PRESENT IN ALL LOCATIONS) BASE COURSE (SEE SPECIFICATION #1) VIMS SLOTTED COLLECTION PIPE (TYP)2 3" SCH 40 THREADED FLUSH JOINT SLOTTED PVC PIPE (0.020" SLOT WIDTH, 1/8" SLOT SPACING) SET WITHIN MIN 5" BASE COURSE WITH MIN 1" BASE COURSE BENEATH AND ABOVE SLOTTED PVC PIPE (SEE SPECIFICATION #1) VAPOR LINER (SEE SPECIFICATION #1) SUBBASE NTSVM1 CONCRETE FLOOR SLAB SUBBASE OLD PINEVILLE ROAD AND SHOLTZ ROADCHARLOTTE, NORTH CAROLINABROWNFIELDS PROJECT NO. 10061-06-060OLD PINEVILLE TOWNHOMESRYAN HOMES, AN NVR, INC COMPANY 10710 SIKES PLACE SUITE 200 CHARLOTTE, NORTH CAROLINA 28277 VAPOR MITIGATION PLAN PREPARED BY 2923 South Tryon Street-Suite 100Charlotte, North Carolina 28203 704-586-0007(p) 704-586-0373(f) License # C-1269 / #C-245 Geology PROFESSIONAL APPROVAL / SEAL H&H NO. NVR-010 VAPOR INTRUSION MITIGATION SYSTEM PLAN SECTION DETAILS JANUARY 18, 2021 VM-1 REVISION 1 ISSUED FOR CONSTRUCTION 3" SCH 40 PVC RISER POTENTIAL LOCATION FOR ELECTRICAL JUNCTION BOX FOR FUTURE VACUUM FAN ON ROOF (SEE SPECIFICATION #8) 01/18/21 POTENTIAL LOCATION FOR ELECTRICAL JUNCTION BOX FOR FUTURE VACUUM FAN IN ENCLOSED ATTIC (SEE SPECIFICATION #8), IF WARRANTED SECTION THROUGH EXTERIOR WALL NTSVM1 BRICK OR HOUSE SIDING EXTERNAL WALL (NOT PRESENT AT ALL LOCATIONS) STUD WALL BASE COURSE (SEE SPECIFICATION #1) VAPOR LINER SEALED TO CONCRETE PER MANUFACTURER INSTRUCTIONS. SUBBASE 3 VIMS RISER AT VERTICAL SLAB PENETRATION7 VM1 NTS BRICK OR HOUSE SIDING EXTERNAL WALL (NOT PRESENT AT ALL LOCATIONS) STUD WALL BASE COURSE (SEE SPECIFICATION #1) VAPOR LINER SEALED TO PIPE AND CONCRETE PER MANUFACTURER INSTRUCTIONS. SUBBASE FLOOR SYSTEM SEE FRAMING PLANS RUN RISER PIPE TO ROOF (SEE DETAIL #9) INSIDE (OCCUPIED SPACE) OUTSIDE/ ADJACENT UNIT 3" SOLID SCH 40 PVC 3" SCH 40 PVC RISER DUCT PIPE (SEE SPECIFICATION #3 & #5) SECTION THROUGH TENANT SEPARATION BLOCK WALL NTSVM1 BRICK OR HOUSE SIDING EXTERNAL WALL (NOT PRESENT AT ALL LOCATIONS) STUD WALL BASE COURSE (SEE SPECIFICATION #1) VAPOR LINER SEALED TO CONCRETE PER MANUFACTURER INSTRUCTIONS. SUBBASE 5 SECTION THROUGH TENANT SEPARATION BLOCK WALL WITH PIPE NTSVM1 BASE COURSE (SEE SPECIFICATION #1) VAPOR LINER SEALED TO CONCRETE PER MANUFACTURER INSTRUCTIONS SUBBASE 6 SINGLE OR DOUBLE STUD SEPARATION WALL OPEN ENDED SCH 40 SLOTTED PVC VAPOR LINER BENEATH CONCRETE BLOCK FOUNDATION AT AREAS WITH MEASURING POINTS, VAPOR LINER SHALL BE SEALED TO PIPE PENETRATION AND CONCRETE PER MANUFACTURER INSTRUCTIONS SECTION THROUGH EXTERIOR WALL NTSVM1 BRICK OR HOUSE SIDING EXTERNAL WALL (NOT PRESENT AT ALL LOCATIONS)STUD WALL SUBBASE 8 FULLY GROUTED CMU BLOCK WALL VAPOR LINER SEALED TO FOOTER PER MANUFACTURER INSTRUCTIONS WITH DOUBLE-SIDED TAPE 2" PVC 90 DEGREE ELBOW IRRIGATION BOX OR WATER METER ENCLOSURE WITH LOCKABLE LID SECURE PIPE WITHIN ENCLOSURE TO PREVENT MOVEMENT VIMS SIPHON VENTILATOR EXHAUST (TYPICAL)9 NTSVM1 3" TO 4" HEAVY DUTY NO HUB COUPLING 4" SIPHON VENTILATOR (EMPIRE SV04SS SYPHON VENTILATOR OR ENGINEER APPROVED EQUIVALENT) RISER DUCT PIPE THROUGH ROOF FLASHING ROOFTOP COMPACTED FILL BELOW DRIVEWAY EXTEND VAPOR LINER TO OUTSIDE OF FOOTER, WHERE POSSIBLE BLOCK FOOTER BLOCK FOOTER BLOCK FOOTER BLOCK FOOTER BLOCK FOOTER FULLY GROUTED CMU BLOCK WALL FULLY GROUTED CMU BLOCK WALL FULLY GROUTED CMU BLOCK WALL \\hhfs01\MasterFiles\AAA-Master Projects\NVR, Inc\NVR-010 OPR\Figures\VMP Figures R1.dwg, 1/18/2021 6:52:29 PM VAPOR INTRUSION MITIGATION SYSTEM (VIMS) SPECIFICATIONS 1.THIS VAPOR INTRUSION MITIGATION PLAN IS INTENDED TO BE USED FOR DIRECTION OF VIMS COMPONENT INSTALLATION ONLY AND IS NOT INTENDED TO GUIDE CONSTRUCTION OF STRUCTURAL COMPONENTS NOT RELATED TO THE VIMS. CONSTRUCTION CONTRACTOR SHALL VERIFY CONSISTENCY OF VIMS DETAILS WITH APPLICABLE STRUCTURAL, ARCHITECTURAL, MECHANICAL, AND PLUMBING PLANS AND RESOLVE INCONSISTENCIES WITH THE DESIGN ENGINEER PRIOR TO VIMS INSTALLATION. 2.CONSTRUCTION CONTRACTORS AND SUB-CONTRACTORS SHALL USE "LOW OR NO VOC" (INCLUDING NO PCE OR TCE) PRODUCTS AND MATERIALS, WHEN POSSIBLE. THE CONSTRUCTION CONTRACTOR AND SUB-CONTRACTORS SHALL PROVIDE SAFETY DATA SHEETS (SDS) TO THE ENGINEER FOR PRODUCTS AND MATERIALS USED DURING CONSTRUCTION. 3.VIMS VAPOR LINER SHALL BE VAPORBLOCK PLUS 20 VAPOR BARRIER MANUFACTURED BY RAVEN INDUSTRIES (OR, EQUIVALENT ALTERNATIVE VAPOR LINER APPROVED BY THE ENGINEER AND NORTH CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY (DEQ); I.E., DRAGO WRAP 20-MIL VAPOR INTRUSION BARRIER MANUFACTURED BY STEGO INDUSTRIES LLC. THE VAPOR LINER SHALL BE INSTALLED AS SPECIFIED HEREIN AND PER MANUFACTURER INSTALLATION INSTRUCTIONS TO CREATE A CONTINUOUS LINER BELOW GROUND FLOOR SLABS. A BASE COURSE CONSISTING OF CLEAN #57 STONE (OR SIMILAR HIGH PERMEABILITY STONE APPROVED BY THE ENGINEER) SHALL BE INSTALLED BENEATH THE VIMS VAPOR LINER. IN AREAS AROUND THE SUB-SLAB PIPING, THE BASE COURSE LAYER MUST BE THICK ENOUGH TO COVER THE SUB-SLAB PIPING WITH A MINIMUM 1-INCH LAYER ABOVE AND BELOW THE PIPING. IN AREAS WITHOUT PIPING, THE BASE COURSE SHOULD BE A MINIMUM OF 4-INCHES THICK. THE BUILDER CAN ELECT TO INSTALL A GEOTEXTILE LAYER BETWEEN THE SUB-SURFACE SOIL AND CLEAN #57 STONE. IF A GEOTEXTILE LAYER IS USED, IT SHALL BE MIRAFI FW500, OR SIMILAR. 4.ALL PENETRATIONS SHALL BE SEALED ACCORDING TO VAPOR LINER MANUFACTURER INSTALLATION INSTRUCTIONS AS FOUND IN THE MANUFACTURER INSTALLATION GUIDELINES. IF VAPORBLOCK PLUS 20 IS USED, SMALL PUNCTURE HOLES SHALL BE SEALED WITH THE VAPORSEALTM TAPE OR POUR-N-SEALTM AND LARGER HOLES, TEARS, OR DAMAGE SHALL BE REPAIRED USING A PATCH THAT OVERLAPS THE DAMAGED AREA AND THEN SHALL BE TAPED ALONG THE SEAMS. IN AREAS WHERE UTILITY PENETRATIONS (I.E. PIPING, DUCTS, ETC) ARE PRESENT AND THE USE OF TAPING IS NOT PRACTICAL OR DEEMS AS "INEFFECTIVE" BY THE DESIGN ENGINEER, POUR-N-SEALTM SHALL BE POURED INTO FORM TO PATCH THE PENETRATION WITH AN AIR-TIGHT SEAL. 5.CONSTRUCTION CONTRACTORS AND SUB-CONTRACTORS SHALL AVOID THE USE OF TEMPORARY FORM BOARDS THAT PENETRATE THE VAPOR LINER WHERE POSSIBLE. IF TEMPORARY FORM BOARDS ARE USED, THE SIZE AND NUMBER OF PENETRATIONS THROUGH THE VAPOR LINER SHALL BE LIMITED AND SMALL DIAMETER STAKES (I.E. SOLID METAL STAKES) SHALL BE USED. IN ALL CASES, AS FORM BOARDS ARE REMOVED, THE CONTRACTOR OR SUB-CONTRACTORS SHALL SEAL ALL PENETRATIONS IN ACCORDANCE WITH VAPOR LINER MANUFACTURER INSTALLATION INSTRUCTIONS. 6.VIMS BELOW AND ABOVE GRADE PIPING SHALL NOT BE TRAPPED AND SHALL BE SLOPED A MINIMUM OF 18 UNIT VERTICAL IN 12 UNITS HORIZONTAL (1% SLOPE) TO GRAVITY DRAIN. SOLID SECTIONS OF HORIZONTAL COLLECTION PIPE SHALL BE SUPPORTED TO PREVENT PIPE SAG OR LOW POINT AND MAINTAIN 1% SLOPE TOWARD SLOTTED SECTIONS TO DRAIN CONDENSATION. HORIZONTAL COLLECTION PIPE SHALL CONSIST OF 3" SCH 40 PVC (OR OTHERWISE NOTED IN THE DRAWINGS). SUB-SLAB SLOTTED VAPOR COLLECTION PIPE SHALL BE THREADED FLUSH JOINT OR GLUE JOINT 3" SCH 40 PVC PIPE WITH 0.020" SLOT WIDTH AND 18" SLOT SPACING. AN ALTERNATE SLOT PATTERN WITH SIMILAR OPEN AREA PER FT OF PIPE MAY BE USED WITH APPROVAL BY ENGINEER. 7.3” SCH 40 PVC RISER DUCT PIPING SHALL EXTEND IN A VERTICAL ORIENTATION THROUGH THE BUILDING ROOF AND TERMINATE A MINIMUM OF 2 FT ABOVE THE BUILDING ROOF LINE. EMPIRE SYPHON VENTILATOR (OR APPROVED ALTERNATE) SHALL BE INSTALLED ON THE EXHAUST DISCHARGE END OF EACH RISER DUCT PIPE. A 4" X 3" PVC ADAPTOR COUPLING SHALL BE INSTALLED AT THE DISCHARGE END OF THE 3" RISER DUCT PIPE AND THE FAN SHALL BE SECURED TO THE PVC RISER IN A VERTICAL ORIENTATION. EXHAUST DISCHARGE LOCATIONS SHALL NOT: 7.1.BE LESS THAN 1 FT ABOVE THE ROOF MEASURED AT THE HIGHEST POINT OF PENETRATION. 7.2.BE LESS THAN 10 FT ABOVE GRADE NEAREST THE POINT OF DISCHARGE. 7.3.BE LESS THAN 10 FT HORIZONTALLY FROM A VERTICAL WALL THAT EXTENDS ABOVE THE ROOF PENETRATED. EXHAUST DISCHARGE SHALL NOT BE LESS THAN 10 FT (IN ANY DIRECTION), OR NOT LESS THAN 2 FT VERTICALLY ABOVE, AIR INTAKE OPENINGS. AIR INTAKE OPENINGS INCLUDE WINDOWS, DOORS, AND OTHER GRAVITY AIR INTAKE OPENINGS AND EXCLUDE ATTIC VENTILATION OPENINGS. THE CLEARANCES SPECIFIED, APPLY TO THE STRUCTURE FITTED WITH VIMS AND ANY ADJACENT STRUCTURES. EXHAUST DISCHARGE OF VIMS PIPING SHALL NOT BE LESS THAN 3 FT ABOVE OR 10 FT AWAY FROM MECHANICAL AIR INTAKE OPENINGS SUCH AS THOSE FOR EVAPORATIVE COOLERS, MAKE-UP AIR, AND HEAT/ENERGY RECOVERY VENTILATORS. THE 10 FT DISTANCE SHALL BE MEASURED AROUND INTERVENING OBSTACLES. NOTE THAT DISCHARGE LOCATIONS ON THE ROOFTOP DEPICTED IN THE VAPOR MITIGATION PLAN MAY BE REPOSITIONED AS LONG AS THE NEW POSITION MEETS THE REQUIREMENTS PRESENTED ABOVE, PENDING ENGINEER APPROVAL. AN ELECTRICAL JUNCTION BOX (120V, 60HZ AC REQUIRED) SHALL BE INSTALLED NEAR THE FAN LOCATION ON THE ROOFTOP FOR CONVERSION TO ELECTRIC FANS, IF REQUIRED. ALL WIRING AND ELECTRICAL TO BE INSTALLED PER APPLICABLE BUILDING AND ELECTRICAL CODES. 8.ABOVE-SLAB ACCESSIBLE RISER DUCT PIPING SHALL BE PERMANENTLY IDENTIFIED BY MEANS OF A TAG OR STENCIL AT A MINIMUM OF ONCE EVERY 10-LINEAR FT WITH "VAPOR MITIGATION - CONTACT HOA". THE RISER PIPE AT THE SYPHON VENTILATOR WILL BE LABELED WITH "VAPOR MITIGATION SYSTEM - CONTACT HOA IF DAMAGED" IN AN ACCESSIBLE LOCATION ON THE ROOF. 9.INSPECTIONS: INSPECTIONS OF EACH COMPONENT OF THE VIMS SHALL BE CONDUCTED BY THE ENGINEER, OR ENGINEER'S DESIGNEE, TO CONFIRM VIMS COMPONENTS ARE INSTALLED PER THE APPROVED DESIGN. THE REQUIRED INSPECTIONS INCLUDE: (1) INSPECTION OF SUB-SLAB PIPING LAYOUT AND GRAVEL PLACEMENT PRIOR TO INSTALLING VAPOR LINER; (2) INSPECTION OF VAPOR LINER PRIOR TO POURING CONCRETE; (3) INSPECTION OF ABOVE-GRADE PIPING LAYOUT; AND (4) INSPECTION OF FAN AND VENT PIPE CONNECTIONS. THE CONSTRUCTION CONTRACTOR(S) SHALL COORDINATE WITH THE ENGINEER TO PERFORM THE REQUIRED INSPECTIONS. DEQ WILL BE CONTACTED 48-HOURS PRIOR TO THE INSPECTION BEING CONDUCTED. FIELD NOTES, PHOTOGRAPHS, AND ANY ADDITIONAL INSPECTION DOCUMENTATION WILL BE INCLUDED IN THE FINAL DELIVERABLE TO DEQ. GARAGE OR BACK SIDE OF UNIT FRONT OF UNITS MEASURING POINT LAYOUT IN BUILDINGS CONTAINING 3 OR 4 UNITS. INTERIOR UNIT MEASURING POINT LOCATIONS SHALL BE IN THE FRONT SIDE OF UNIT. END UNIT MEASURING POINTS SHALL BE IN THE GARAGE SPACE OR BACK SIDE OF UNIT. VACUUM MEASURING POINT LAYOUT - 3 OR 4 CONNECTED UNITS10A VM1A NTS PERMANENT VACUUM MEASURING POINT - SEE DETAIL 8 ON SHEET VM-1 LEGEND FOR DETAILS 10A & 10B GARAGE OR BACK SIDE OF UNIT FRONT OF UNITS MEASURING POINT LAYOUT IN BUILDINGS CONTAINING 7 OR 8 UNITS. INTERIOR UNIT MEASURING POINT LOCATIONS SHALL BE IN THE FRONT SIDE OF UNIT. END UNIT MEASURING POINTS SHALL BE IN THE GARAGE SPACE OR BACK SIDE OF UNIT. VACUUM MEASURING POINT LAYOUT - 7 OR 8 CONNECTED UNITS10B VM1A NTS PERMANENT VACUUM MEASURING POINT - SEE DETAIL 8 ON SHEET VM-1 - PROPOSED SUB-SLAB SAMPLE LOCATION RYAN HOMES, AN NVR, INC COMPANY 10710 SIKES PLACE SUITE 200 CHARLOTTE, NORTH CAROLINA 28277 VAPOR MITIGATION PLAN PREPARED BY 2923 South Tryon Street-Suite 100Charlotte, North Carolina 28203704-586-0007(p) 704-586-0373(f) License # C-1269 / #C-245 Geology PROFESSIONAL APPROVAL / SEAL H&H NO. NVR-010 VAPOR INTRUSION MITIGATION SYSTEM PLAN SPECIFICATIONS JANUARY 18, 2021 VM-1A REVISION 1 ISSUED FOR CONSTRUCTION OLD PINEVILLE ROAD AND SHOLTZ ROADCHARLOTTE, NORTH CAROLINABROWNFIELDS PROJECT NO. 10061-06-060OLD PINEVILLE TOWNHOMES01/18/21 \\hhfs01\MasterFiles\AAA-Master Projects\NVR, Inc\NVR-010 OPR\Figures\VMP Figures R1.dwg, 1/18/2021 6:12:55 PM 1 VM1 1 VM1 2 VM1 2 VM1 6 VM1 3A VM1 4 VM1 4 VM1 7/9 VM1 7/9 VM1 8 VM1 8 VM1 5 VM1 6 VM1 6 VM1 6 VM1 LEGEND EXTENT OF VAPOR BARRIER - SEE SPECIFICATION #1 ON SHEET VM-1A 3" SCH 40 PVC SLOTTED PIPE (INSTALL 3" VENT CAP AT END OF SLOTTED SECTIONS) 3" SCH 40 PVC SOLID PIPE VERTICAL RISER (3" SCH 40 PVC) AND EXHAUST LOCATION (REFER TO DETAIL #9 FOR SYPHON VENTILATOR SET-UP) VACUUM MEASURING POINT IF LAYOUT IS END UNIT (2" SCH 40 PVC WITH OPEN END) THICKENED SLAB AT LOAD BEARING WALL THICKENED SLAB STEP AT GARAGE STEP DOWN NOTES: 1.LAYOUTS FOR GIH OPTION ARE SHOWN. THIS VIMS SHEET SHALL ONLY APPLY TO THIS LAYOUT OPTION. SEE SHEETS VM-3 AND VM-4 FOR LAYOUTS OF GIT AND GIZ UNITS. 2.ONE VACUUM MEASURING POINT SHALL BE INSTALLED PER UNIT. IF THE UNIT IS AN END UNIT, THEN VACUUM MEASURING POINT SHALL BE INSTALLED ON THE BACKSIDE OF THE UNIT. IF THE UNITS ARE INTERIOR UNITS, THEN THE VACUUM MEASURING POINT SHALL BE INSTALLED ON THE FRONT SIDE OF THE UNIT. REFER TO DETAIL 10A AND 10B ON SHEET VM-1A. 3.POSITION INTAKE OF VACUUM MEASURING POINT A MINIMUM OF 5-FT FROM ANY EXTERIOR TURNED DOWN SLAB. 4.POSITION SLOTTED SUB-SLAB COLLECTION PIPE A MINIMUM OF 5-FT FROM ANY EXTERIOR TURNED DOWN SLAB. 5.GROUND FLOOR LEVEL OF EACH BUILDING SHOWN. REFER TO STRUCTURAL AND ARCHITECTURAL DRAWINGS FOR FINAL BUILDING LAYOUT. THIS VIMS LAYOUT IS FOR GIT OPTION UNITS. 6.REFER TO SPECIFICATIONS 1 THROUGH 10 AND SECTION DETAILS ON SHEETS VM-1 AND VM-1A. 7.EACH UNIT IS APPROXIMATELY 640 SQ FT. GIH OPTIONGIH OPTION RYAN HOMES, AN NVR, INC COMPANY 10710 SIKES PLACE SUITE 200 CHARLOTTE, NORTH CAROLINA 28277 VAPOR MITIGATION PLAN PREPARED BY 2923 South Tryon Street-Suite 100Charlotte, North Carolina 28203704-586-0007(p) 704-586-0373(f) License # C-1269 / #C-245 Geology PROFESSIONAL APPROVAL / SEAL H&H NO. NVR-010 VAPOR INTRUSION MITIGATION SYSTEM PLAN GIH OPTION JANUARY 18, 2021 VM-2 REVISION 1 ISSUED FOR CONSTRUCTION OLD PINEVILLE ROAD AND SHOLTZ ROADCHARLOTTE, NORTH CAROLINABROWNFIELDS PROJECT NO. 10061-06-060OLD PINEVILLE TOWNHOMES01/18/21 \\hhfs01\MasterFiles\AAA-Master Projects\NVR, Inc\NVR-010 OPR\Figures\VMP Figures R1.dwg, 1/18/2021 6:13:08 PM 8 8 1 VM1 1 VM1 1 VM1 1 VM1 2 VM1 2 VM1 2 VM1 2 VM1 3A VM1 5 VM1 3A VM1 5 VM1 4 VM1 4 VM1 4 VM14 VM1 7/9 VM1 8 VM1 8 VM1 8 VM1 8 VM1 7 VM1 6 VM1 6 VM1 6 VM1 6 VM1 7/9 VM1 7/9 VM1 7/9 VM1 LEGEND EXTENT OF VAPOR BARRIER - SEE SPECIFICATION #1 ON SHEET VM-1A 3" SCH 40 PVC SLOTTED PIPE (INSTALL 3" VENT CAP AT ENDS OF SLOTTED SECTIONS) 3" SCH 40 PVC SOLID PIPE VERTICAL RISER (3" SCH 40 PVC) AND EXHAUST LOCATION (REFER TO DETAIL #8 FOR SYPHON VENTILATOR SET-UP) VACUUM MEASURING POINT (2" SCH 40 PVC WITH OPEN END) THICKENED SLAB AT LOAD BEARING WALL THICKENED SLAB STEP AT GARAGE STEP DOWN NOTES: 1.LAYOUTS FOR GIT OPTION ARE SHOWN. THIS VIMS SHEET SHALL ONLY APPLY TO THIS LAYOUT OPTION. SEE SHEETS VM-2 AND VM-4 FOR LAYOUTS OF GIH AND GIZ UNITS. 2.ONE VACUUM MEASURING POINT SHALL BE INSTALLED PER UNIT. IF THE UNIT IS AN END UNIT, THEN VACUUM MEASURING POINT SHALL BE INSTALLED ON THE GARAGE SIDE OF THE UNIT. IF THE UNITS ARE INTERIOR UNITS, THEN THE VACUUM MEASURING POINT SHALL BE INSTALLED WITHIN THE LIVING AREA. REFER TO DETAILS 10A & 10B ON SHEET VM-1A. 3.POSITION INTAKE OF VACUUM MEASURING POINT A MINIMUM OF 5-FT FROM ANY EXTERIOR TURNED DOWN SLAB. 4.POSITION SUB-SLAB COLLECTION PIPE A MINIMUM OF 5-FT FROM ANY EXTERIOR TURNED DOWN SLAB. 5.GROUND FLOOR LEVEL OF EACH BUILDING SHOWN. REFER TO STRUCTURAL AND ARCHITECTURAL DRAWINGS FOR FINAL BUILDING LAYOUT. THIS VIMS LAYOUT IS FOR GIT OPTION UNITS. 6.REFER TO SPECIFICATIONS 1 THROUGH 10 AND SECTION DETAILS ON SHEETS VM-1 AND VM-1A. 7.EACH UNIT IS APPROXIMATELY 640 SQ FT. GIT OPTIONGIT OPTIONGIT OPTIONGIT OPTION RYAN HOMES, AN NVR, INC COMPANY 10710 SIKES PLACE SUITE 200 CHARLOTTE, NORTH CAROLINA 28277 VAPOR MITIGATIONPLAN PREPARED BY 2923 South Tryon Street-Suite 100 Charlotte, North Carolina 28203 704-586-0007(p) 704-586-0373(f) License # C-1269 / #C-245 Geology PROFESSIONAL APPROVAL / SEAL H&H NO. NVR-010 VAPOR INTRUSION MITIGATION SYSTEM PLAN GIT OPTION JANUARY 18, 2021 VM-3 REVISION 1 ISSUED FOR CONSTRUCTION OLD PINEVILLE ROAD AND SHOLTZ ROADCHARLOTTE, NORTH CAROLINABROWNFIELDS PROJECT NO. 10061-06-060OLD PINEVILLE TOWNHOMES01/18/21 \\hhfs01\MasterFiles\AAA-Master Projects\NVR, Inc\NVR-010 OPR\Figures\VMP Figures R1.dwg, 1/18/2021 6:31:57 PM 1 VM1 1 VM1 1 VM1 1 VM1 2 VM1 2 VM1 2 VM1 2 VM1 3A VM13A VM1 5 VM1 4 VM1 4 VM1 4 VM1 4 VM1 8 VM1 8 VM1 8 VM1 VM1 6 VM1 6 VM1 5 VM1 6 VM1 6 VM1 5 VM1 7/9 VM17/9 VM1 7/9 VM1 7/9 VM1 8 LEGEND EXTENT OF VAPOR BARRIER - SEE SPECIFICATION #1 ON SHEET VM-1A 3" SCH 40 PVC SLOTTED PIPE (INSTALL 3" VENT CAP AT ENDS OF SLOTTED SECTIONS) 3" SCH 40 PVC SOLID PIPE VERTICAL RISER (3" SCH 40 PVC) AND EXHAUST LOCATION (REFER TO DETAIL #8 FOR SYPHON VENTILATOR SET-UP) VACUUM MEASURING POINT (2" SCH 40 PVC WITH OPEN END) THICKENED SLAB AT LOAD BEARING WALL NOTES: 1.LAYOUTS FOR GIZ OPTION ARE SHOWN. THIS VIMS SHEET SHALL ONLY APPLY TO THIS LAYOUT OPTION. SEE SHEETS VM-2 AND VM-3 FOR LAYOUTS OF GIT AND GIH UNITS. 2.ONE VACUUM MEASURING POINT SHALL BE INSTALLED PER UNIT. IF THE UNIT IS AN END UNIT, THEN VACUUM MEASURING POINT SHALL BE INSTALLED ON THE BACKSIDE OF THE UNIT. IF THE UNITS ARE INTERIOR UNITS, THEN THE VACUUM MEASURING POINT SHALL BE INSTALLED ON THE FRONT SIDE OF THE UNIT. REFER TO DETAILS 10A & 10B ON SHEET VM-1A. 3.POSITION INTAKE OF VACUUM MEASURING POINT A MINIMUM OF 5-FT FROM ANY EXTERIOR TURNED DOWN SLAB. 4.POSITION SUB-SLAB COLLECTION PIPE A MINIMUM OF 5-FT FROM ANY EXTERIOR TURNED DOWN SLAB. 5.GROUND FLOOR LEVEL OF EACH BUILDING SHOWN. REFER TO STRUCTURAL AND ARCHITECTURAL DRAWINGS FOR FINAL BUILDING LAYOUT. THIS VIMS LAYOUT IS FOR GIT OPTION UNITS. 6.REFER TO SPECIFICATIONS 1 THROUGH 10 AND SECTION DETAILS ON SHEETS VM-1 AND VM-1A. 7.EACH UNIT IS APPROXIMATELY 640 SQ FT. GIZ OPTION GIZ OPTION GIZ OPTION GIZ OPTION RYAN HOMES, AN NVR, INC COMPANY 10710 SIKES PLACE SUITE 200 CHARLOTTE, NORTH CAROLINA 28277 VAPOR MITIGATION PLAN PREPARED BY 2923 South Tryon Street-Suite 100Charlotte, North Carolina 28203 704-586-0007(p) 704-586-0373(f) License # C-1269 / #C-245 Geology PROFESSIONAL APPROVAL / SEAL H&H NO. NVR-010 VAPOR INTRUSION MITIGATION SYSTEM PLAN GIZ OPTION JANUARY 18, 2021 VM-4 REVISION 1 ISSUED FOR CONSTRUCTION OLD PINEVILLE ROAD AND SHOLTZ ROADCHARLOTTE, NORTH CAROLINABROWNFIELDS PROJECT NO. 10061-06-060OLD PINEVILLE TOWNHOMES01/18/21 \\hhfs01\MasterFiles\AAA-Master Projects\NVR, Inc\NVR-010 OPR\Figures\VMP Figures R1.dwg, 1/18/2021 6:13:40 PM Attachment 2 Vapor Intrusion Mitigation System Product Specifications PRODUCT PART # VaporBlock® Plus™ 20 ................................................................ VBP20 UNDER-SLAB VAPOR / GAS BARRIER Under-Slab Vapor/Gas Retarder © 2018 RAVEN INDUSTRIES INC. All rights reserved. VAPORBLOCK® PLUS™VBP20 PRODUCT DESCRIPTION VaporBlock® Plus™ is a seven-layer co-extruded barrier made using high quality virgin-grade polyethylene and EVOH resins to provide unmatched impact strength as well as superior resistance to gas and moisture transmission. VaporBlock® Plus™ 20 is more than 100 times less permeable than typical high-performance polyethylene vapor retarders against Methane, Radon, and other harmful VOCs. Tested and verified for unsurpassed protection against BTEX, HS, TCE, PCE, methane, radon, other toxic chemicals and odors. VaporBlock® Plus™ 20 multi-layer gas barrier is manufactured with the latest EVOH barrier technology to mitigate hazardous vapor intrusion from damaging indoor air quality, and the safety and health of building occupants. VBP20 is one of the most effective underslab gas barriers in the building industry today far exceeding ASTM E-1745 (Plastic Water Vapor Retarders Used in Contact with Soil or Granular Fill Under Concrete Slabs) Class A, B and C requirements. Available in a 20 (Class A) mil thicknesses designed to meet the most stringent requirements. VaporBlock® Plus™ 20 is produced within the strict guidelines of our ISO 9001 Certified Management System. PRODUCT USE VaporBlock® Plus™ 20 resists gas and moisture migration into the building envelop when properly installed to provide protection from toxic/harmful chemicals. It can be installed as part of a passive or active control system extending across the entire building including floors, walls and crawl spaces. When installed as a passive system it is recommended to also include a ventilated system with sump(s) that could be converted to an active control system with properly designed ventilation fans. VaporBlock® Plus™ 20 works to protect your flooring and other moisture-sensitive furnishings in the building’s interior from moisture and water vapor migration, greatly reducing condensation, mold and degradation. SIZE & PACKAGING VaporBlock® Plus™ 20 is available in 10’ x 150’ rolls to maximize coverage. All rolls are folded on heavy-duty cores for ease in handling and installation. Other custom sizes with factory welded seams are available based on minimum volume requirements. Installation instructions and ASTM E-1745 classifications accompany each roll. APPLICATIONS Radon Barrier Methane Barrier VOC Barrier Brownfields Barrier Vapor Intrusion Barrier Under-Slab Vapor Retarder Foundation Wall Vapor Retarder VaporBlock® Plus™ is a seven-layer co-extruded barrier made using high quality virgin-grade polyethylene and EVOH resins to provide unmatched impact strength as well as superior resistance to gas and moisture transmission. VaporBlock® Plus™ Placement All instructions on architectural or structural drawings should be reviewed and followed. Detailed installation instructions accompany each roll of VaporBlock® Plus™ and can also be located at www.ravenefd.com. ASTM E-1643 also provides general installation information for vapor retarders. VAPORBLOCK® PLUS™ 20 PROPERTIES TEST METHOD IMPERIAL METRIC AppeArAnce White/Gold Thickness, nominAl 20 mil 0.51 mm WeighT 102 lbs/MSF 498 g/m² clAssificATion ASTM E 1745 CLASS A, B & C ³ Tensile sTrengTh ASTM E 154Section 9(D-882)58 lbf 102 N impAcT resisTAnce ASTM D 1709 2600 g permeAnce (neW mATeriAl) ASTM E 154Section 7ASTM E 96Procedure B 0.0098 Perms grains/(ft²·hr·in·Hg) 0.0064 Perms g/(24hr·m²·mm Hg) permeAnce (AfTer condiTioning) (sAme meAsuremenT As Above permeAnce) ASTM E 154Section 8, E96Section 11, E96Section 12, E96Section 13, E96 0.00790.00790.00970.0113 0.00520.00520.00640.0074 WvTr ASTM E 96Procedure B 0.0040 grains/hr-ft²0.0028 gm/hr-m² benzene permeAnce See Note ⁶1.13 x 10-¹⁰ m²/sec or 3.62 x 10-¹³ m/s Toluene permeAnce See Note ⁶1.57 x 10-¹⁰ m²/sec or 1.46 x 10-¹³ m/s eThylbenzene permeAnce See Note ⁶1.23 x 10-¹⁰ m²/sec or 3.34 x 10-¹⁴ m/s m & p-Xylenes permeAnce See Note ⁶1.17 x 10-¹⁰ m²/sec or 3.81 x 10-¹⁴ m/s o-Xylene permeAnce See Note ⁶1.10 x 10-¹⁰ m²/sec or 3.43 x 10-¹⁴ m/s hydrogen sulfide See Note 9 1.92E-⁰⁹ m/s TrichloroeThylene (Tce) See Note ⁶7.66 x 10-¹¹ m²/sec or 1.05 x 10-¹⁴ m/s perchloroeThylene (pce)See Note ⁶7.22 x 10-¹¹ m²/sec or 1.04 x 10-¹⁴ m/s rAdon diffusion coeffiecienT K124/02/95 < 1.1 x 10-13 m2/s meThAne permeAnce ASTM D 1434 3.68E-¹² m/sGas Transmission Rate (GTR):0.32 mL/m²•day•atm mAXimum sTATic use TemperATure 180° F 82° C minimum sTATic use TemperATure - 70° F - 57° C UNDER-SLAB VAPOR / GAS BARRIER VAPORBLOCK® PLUS™VBP20 © 2018 RAVEN INDUSTRIES INC. All rights reserved. Scan QR Code to download current technical data sheets via the Raven website. Note: To the best of our knowledge, unless otherwise stated, these are typical property values and are intended as guides only, not as specification limits. Chemical resistance, odor transmission, longevity as well as other performance criteria is not implied or given and actual testing must be performed for applicability in specific applications and/or conditions. RAVEN INDUSTRIES MAKES NO WARRANTIES AS TO THE FITNESS FOR A SPECIFIC USE OR MERCHANTABILITY OF PRODUCTS REFERRED TO, no guarantee of satisfactory results from reliance upon contained information or recommendations and disclaims all liability for resulting loss or damage. Limited Warranty available at www.RavenEFD.com 061318 EFD 1125 RAVEN ENGINEERED FILMSP.O. Box 5107 Sioux Falls, SD 57117-5107Ph: +1 (605) 335-0174 • TF: +1 (800) 635-3456 efdsales@ravenind.comwww.ravenefd.com ³ Tests are an average of machine and transverse directions.5 Raven Industries performs seam testing at 20” per minute.6 Aqueous Phase Film Permeance. Permeation of Volatile Organic Compounds through EVOH Thin Film Membranes and Coextruded LLDPE/EVOH/ LLDPE Geomembranes, McWatters and Rowe, Journal of Geotechnical and Geoenvironmental Engineering© ASCE/ September 2015. (Permeation is the Permeation Coefficient adjusted to actual film thickness - calculated at 1 kg/m³.) The study used to determine PCE and TCE is titled: Evaluation of diffusion of PCE & TCE through high performance geomembranes by Di Battista and Rowe, Queens University 8 Feb 2018.9 The study used to determine diffusion coefficients is titled: Hydrogen Sulfide (H₂S) Transport through Simulated Interim Covers with Conventional and Co-Extruded Ethylene-Vinyl Alcohol (EVOH) Geomembranes. INSTALLATION GUIDELINES - With VaporSeal™ Tape VaporSeal™ 4” Tape VaporSeal™ 4” Tape Optional Butyl Seal 2-Sided Tape Gas Barrier Applications Elements of a moisture/gas-resistant floor system. General illustration only.(Note: This example shows multiple options for waterstop placement. VaporSeal™ 4” Tape VaporSeal™ 4” Tape Optional Butyl Seal 2-Sided Tape Gas Barrier Applications Fig. 2: VaporBlock® Plus™ Overlap Joint Sealing Methods Fig. 1: VaporBlock® Plus™ Overlapping Roll-out Method Please Note: Read these instructions thoroughly before installation to ensure proper use of VaporBlock® Plus™. ASTM E 1465, ASTM E 2121 and, ASTM E 1643 also provide valuable information regarding the installation of vapor / gas barriers. When installing this product, contractors shall conform to all applicable local, state and federal regulations and laws pertaining to residential and commercial building construction. • When VaporBlock® Plus™ gas barrier is used as part of an active control system for radon or other gas, a ventilation system will be required. • If designed as a passive system, it is recommended to install a ventilation system that could be converted to an active system if needed. Materials List:VaporBlock® Plus™ Vapor / Gas BarrierVaporSeal™* 4” Seaming TapeVaporSeal™* 12” Seaming/Repair TapeButyl Seal 2-Sided TapeVaporBoot Plus Pipe Boots 12/Box (recommended)VaporBoot Tape (optional)POUR-N-SEAL™ (optional)1” Foam Weather Stripping (optional)Mako® Screed Supports (optional) VAPORBLOCK® PLUS™ PLACEMENT 1.1. Level and tamp or roll granular base as specified. A base for a gas-reduction system may require a 4” to 6” gas permeable layer of clean coarse aggregate as specified by your architectural or structural drawings after installation of the recommended gas collection system. In this situation, a cushion layer consisting of a non-woven geotextile fabric placed directly under VaporBlock® Plus™ will help protect the barrier from damage due to possible sharp coarse aggregate. 1.2. Unroll VaporBlock® Plus™ running the longest dimension parallel with the direction of the pour and pull open all folds to full width. (Fig. 1) 1.3. Lap VaporBlock® Plus™ over the footings and seal with Raven Butyl Seal tape at the footing-wall connection. Prime concrete surfaces, when necessary, and assure they are dry and clean prior to applying Raven Butyl Seal Tape. Apply even and firm pressure with a rubber roller. Overlap joints a minimum of 6” and seal overlap with 4” VaporSeal™ Tape. When used as a gas barrier, overlap joints a minimum of 12” and seal in-between overlap with an optional 2-sided Raven Butyl Seal Tape. Then seal with 4” VaporSeal™ Tape centered on the overlap seam. (Fig. 2) Page 1 of 4 Top original diagram and figure #1 were reprinted with permission by the Portland Cement Association.Reference: Kanare, Howard M., Concrete Floors and Moisture, EB119, Portland Cement Association, Skokie, Illinois, and National Ready Mixed Concrete Association, Silver Spring, Maryland, USA, 2008, 176 pages. 1.4. Seal around all plumbing, conduit, support columns or other penetrations that come through the VaporBlock® Plus™ membrane. 1.4a. Method 1: Pipes four inches or smaller can be sealed with Raven VaporBoot Plus preformed pipe boots. VaporBoot Plus preformed pipe boots are formed in steps for 1”, 2”, 3” and 4” PVC pipe or IPS size and are sold in units of 12 per box (Fig. 3 & 5). Pipe boots may also be fabricated from excess VaporBlock® Plus™ membrane (Fig. 4 & 6) and sealed with VaporBoot Tape or VaporSeal™ Tape (sold separately). 1.4b. Method 2: To fabricate pipe boots from VaporBlock® Plus™ excess material (see Fig. 4 & 6 for A-F): A) Cut a square large enough to overlap 12” in all directions. B) Mark where to cut opening on the center of the square and cut four to eight slices about 3/8” less than the diameter of the pipe. C) Force the square over the pipe leaving the tightly stretched cut area around the bottom of the pipe with approximately a 1/2” of the boot material running vertically up the pipe. (no more than a 1/2” of stretched boot material is recommended) D) Once boot is positioned, seal the perimeter to the membrane by applying 2-sided Raven Butyl Seal Tape in between the two layers. Secure boot down firmly over the membrane taking care not to have any large folds or creases. E) Use VaporBoot Tape or VaporSeal™ Tape to secure the boot to the pipe. VaporBoot Tape (option) – fold tape in half lengthwise, remove half of the release liner and wrap around the pipe allowing 1” extra for overlap sealing. Peel off the second half of the release liner and work the tape outward gradually forming a complete seal. VaporSeal™ Tape (option) - Tape completely around pipe overlapping the VaporBlock® Plus™ square to create a tight seal against the pipe. F) Complete the process by taping over the boot perimeter edge with VaporSeal™ Tape to create a monolithic membrane between the surface of the slab and gas/moisture sources below and at the slab perimeter. (Fig. 4 & 6) Preformed Pipe Boot Square Material Pipe Boot Fig. 3 SINGLE PENETRATION PIPE BOOT INSTALLATION Fig. 5 Fig. 6 1. Cut a square of VaporBlock® Plus™ barrier to extend at least 12” from the pipe in all directions. 2. Cut four to eight slices about 3/8” less than the diameter of the pipe. 5. Use Raven VaporBoot or VaporSeal™ Tape and overlap 1” at the seam. 4. Tape over the boot perimeter edge with VaporSeal™ Tape. 1. Cut out one of the preformed boot steps (1” to 4”). 2. Tape the underside boot perimeter with 2-sided Butyl Seal Tape. 3. Force the boot over pipe and press tape firmly in place. 4. Use VaporSeal™ Tape to secure boot to the pipe. 5. Tape around entire boot edge with VaporSeal™ Tape. VaporBoot Flexible Tapeor VaporSeal™ 4” TapeVaporSeal™ 4” Tape VaporBlock® Plus™Material VaporSeal™ 4” Tape Raven Butyl Seal2-Sided Tape Raven Butyl Seal2-Sided Tape VaporBoot PlusPreformed Boot 12”(minimum) 3. Force over pipe and tape the underside boot perimeter to existing barrier with 2-sided Butyl Seal Tape. Fig. 4 Page 2 of 4 Original figure #4 diagram is reprinted with permission by the Portland Cement Association.Reference: Kanare, Howard M., Concrete Floors and Moisture, EB119, Portland Cement Association, Skokie, Illinois, and National Ready Mixed Concrete Association, Silver Spring, Maryland, USA, 2008, 176 pages.Method 1 Method 2 VaporSeal™4” Tape VaporBoot PlusPerformed Boot Raven Butyl Seal 2-sided Tape Raven Butyl Seal 2-sided Tape 1.5. Sealing side-by-side multiple penetrations (option 1); A) Cut a patch large enough to overlap 12” in all directions (Fig. 7) of penetrations. B) Mark where to cut openings and cut four to eight slices about 3/8” less than the diameter of the penetration for each. C) Force patch material over penetration to achieve a tight fit and form a lip. D) Once patch is positioned, seal the perimeter to the membrane by applying 2-sided Raven Butyl Seal Tape in-between the two layers. (Fig. 8) E) After applying Raven Butyl Seal Tape between the patch and membrane, tape around each of the penetrations and the patch with VaporSeal™ 4” tape. (Fig. 9) For additional protection apply POUR-N-SEAL™ or an acceptable polyurethane elastomeric sealant around the penetrations. (Fig. 10) Fig. 7 Fig. 8 Fig. 9 Fig. 10 MULTIPLE PENETRATION PIPE BOOT INSTALLATION Fig. 6 Cut a patch large enough to overlap 12” in all directions and slide over penetrations (Make openings as tight as possible.) Once the overlay patch is positioned, seal the perimeter to the membrane by applying 2-sided Raven Butyl Seal Tape in-between the two layers. After applying Raven Butyl Seal Tapebetween the patch and membrane, tape around the perimeter of the penetration and the patch with VaporSeal™ 4” Tape. For additional protection apply POUR-N-SEAL™ or an acceptable polyurethane elastomeric sealant around the penetrations. VaporSeal™ 4” Tape VaporSeal™ 4” Tape Page 3 of 4 Option 1 Raven Butyl Seal 2-sided Tape 1.6. POUR-N-SEAL™ method of sealing side-by-side multiple penetrations (option 2); A) Install the vapor barrier as closely as possible to pipe penetrations to minimize the amount of POUR-N-SEAL™ necessary to seal around all penetrations. B) Once barrier is in place, remove soil or other particles with a dry cloth or a fine broom to allow for improved adhesion to the POUR-N-SEAL™ liquid. C) Create a dam around the penetration area approximately 2” away from the pipe or other vertical penetrations by removing the release liner from the back of a 1” weather stripping foam and adhere to the vapor barrier. Form a complete circle to contain the POUR-N-SEAL™ materials (Fig. 11). D) Once mixed, pour contents around the pipe penetrations. If needed, a brush or a flat wooden stick can be used to direct the sealant completely around penetrations creating a complete seal (Fig. 12-13). E) DO NOT leave excess POUR-N-SEAL™ in plastic container for longer than the time it takes to pour sealant. Fig. 12 Fig. 13 Fig. 11 Option 2 VAPORBLOCK® PLUS™ REPAIR INSTRUCTIONS 1.7. Proper installation requires all holes and openings are repaired prior to placing concrete. When patching small holes, simply cut a 12” long piece of 12” wide VaporSeal™ tape. Remove release liner and center over the opening. Apply pressure to create a seal (Fig. 14-15). 1.8. When installing VaporBlock® Plus™ around pipe penetrations, vertical columns, electrical ducts and other obstructions, you will find it necessary to cut it to the nearest outside edge. This cut can be easily sealed with 12” wide VaporSeal™ tape, by simply centering it over the cut, 6” on either side. Once the tape is placed correctly, apply pressure to assure a complete seal (Fig. 16). Reminder Note: All holes or penetrations through the membrane will need to be patched with 12” VaporSeal™ Tape. Fig. 14 Page 4 of 5 Fig. 15 2.1. When installing reinforcing steel and utilities, in addition to the placement of concrete, take precaution to protect VaporBlock® Plus™. Carelessness during installation can damage the most puncture–resistant membrane. Sheets of plywood cushioned with geotextile fabric temporarily placed on VaporBlock® Plus™ provide for additional protection in high traffic areas including concrete buggies. 2.2. Use only brick-type or chair-type reinforcing bar supports to protect VaporBlock® Plus™ from puncture. 2.3. Avoid driving stakes through VaporBlock® Plus™. If this cannot be avoided, each individual hole must be repaired per section 1.7. 2.4. To avoid penetrating VaporBlock® Plus™ when installing screed supports, utilize non-penetrating support, such as the Mako® Screed Support System (Fig. 17). Avoid driving stakes through VaporBlock® Plus™. If this cannot be avoided, each individual hole must be repaired per figures 14-15. 2.5. If a cushion or blotter layer is required in the design between VaporBlock® Plus™ and the slab, additional care should be given if sharp crushed rock is used. Washed rock will provide less chance of damage during placement. Care must be taken to protect blotter layer from precipitation before concrete is placed. VaporBlock® Plus™ Gas & Moisture Barrier can be identified on site as gold/white in color printed in black ink with following logo and classification listing (Fig. 18) Page 5 of 5 VaporBlock® Plus™ Gas & Moisture Barrier Note: To the best of our knowledge, unless otherwise stated, these are typical property values and are intended as guides only, not as specification limits. Chemical resistance, odor transmission, longevity as well as other performance criteria is not implied or given and actual testing must be performed for applicability in specific applications and/or conditions. RAVEN INDUSTRIES MAKES NO WARRANTIES AS TO THE FITNESS FOR A SPECIFIC USE OR MERCHANTABILITY OF PRODUCTS REFERRED TO, no guarantee of satisfactory results from reliance upon contained information or recommendations and disclaims all liability for resulting loss or damage. Limited Warranty available at wwww.RavenEFD.com ENGINEERED FILMSP.O. Box 5107 Sioux Falls, SD 57117-5107Ph: +1 (605) 335-0174 • TF: +1 (800) 635-3456 efdsales@ravenind.comwww.ravenefd.com 020316 EFD 1127 VAPORBLOCK® PLUS™ PROTECTION Fig. 16 Fig. 18 Fig. 17 * Patent Pending © Raven 2016. All Rights Reserved. EVECO VENTILATOR APPROX.EXHAUST WEIGHT CAPACITY SIZE GALV.COPPER PACKED 4-MIWIND (inches)(gauge)(ounces)(pounds)(CFM) 4 26-28 16 3 40 5 26-28 16 3 45 6 26-28 16 3 50 7 26-28 16 4 60 8 26-28 16 4 75 9 26-28 16 5 100 10 26-28 16 5 120 12 26 16 6 170 14 24-26 16 9 280 15 24-26 16 10 325 16 24-26 16 10 375 IB 24-26 16-20 12 450 20 24-26 16-20 14 580 24 22-24 16-20 24 750 30 22-24 16-20 48 1100 36 22-24 20-24 90 1600 The Eveco Ventilator is a single cone vent, ideal for low cost ventilation. Thoughthe cost ofthis unit isslight, itprovides maximum ventilation in ail types of weather. SYPHON VENTILATOR The Empire Syphon Ventilator is a dependable stationary exhauster that functions efficiently in the slightest breeze,its design utilizes every wind current to create a pow erful suction through the stack,while the storm band circling the upper cone prevents rain from driving into the ventilator and adds to its exhaust capacity.Air outlet is more than dou ble that of the stack area. APPROX.EXHAUST WEIGHT CAPACITY SIZE GALV.COPPER PACKED 4-MIWIND (Inches)(gauge)(ounces)(pounds)(CFM) 4 26-28 16 7 65 5 26-28 16 7 70 6 26-28 16 8 75 7 26-28 16 9 85 8 26-28 16 10 105 9 26-28 16 11 140 10 26-28 16 12 190 12 26 16 15 275 14 24-26 16-20 21 380 15 24-26 16-20 25 450 16 24-26 16-20 30 500 18 24-26 16-20 35 620 20 22-24 20 45 740 24 22-24 20-24 70 1010 Empire Ventilation Equipment Co.,Inc. 35-39 Vernon Boulevard Long Island City, NY 11106-5195 TEL:(718)728-2143 FAX:(718)267-0143 EMPIRE INSTALLATION & OPERATING INSTRUCTIONS Instruction P/N IN015 Rev E FOR CHECKPOINT IIa TM P/N 28001-2 & 28001-3 RADON SYSTEM ALARM INSTALLATION INSTRUCTIONS (WALL MOUNTING) Select a suitable wall location near a vertical section of the suction pipe. The unit should be mounted about four or five feet above the floor and as close to the suction pipe as possible. Keep in mind that with the plug-in transformer provided, the unit must also be within six feet of a 120V receptacle. NOTE: The Checkpoint IIa is calibrated for vertical mounting, horizontal mounting will affect switchpoint calibration. Drill two ¼” holes 4” apart horizontally where the unit is to be mounted. Install the two ¼” wall anchors provided. Hang the CHECKPOINT IIa from the two mouting holes located on the mounting bracket. Tighten the mounting screws so the unit fits snugly and securely against the wall. Drill a 5/16” hole into the side of the vent pipe about 6” higher than the top of the unit. Insert the vinyl tubing provided about 1” inside the suction pipe. Cut a suitable length of vinyl tubing and attach it to the pressure switch connector on the CHECKPOINT IIa. CALIBRATION AND OPERATION. The CHECKPOINT IIa units are calibrated and sealed at the factory to alarm when the vacuum pressure falls below the factory setting and should not normally require field calibration. Factory Settings are: 28001-2 -.25” WC Vacuum 28001-3 -.10” WC Vacuum To Verify Operation: With the exhaust fan off or the pressure tubing disconnected and the CHECKPOINT IIa plugged in, both the red indicator light and the audible alarm should be on. Turn the fan system on or connect the pressure tubing to the fan piping. The red light and the audible alarm should go off. The green light should come on. Now turn the fan off. The red light and audible alarm should come on in about two or three seconds and the green light should go out. Manufactured by: RadonAway Ward Hill, MA (978)-521-3703 WARRANTY INFORMATION Subject to applicable consumer protection legislation, RadonAway warrants that the CHECKPOINT IIa will be free from defective material and workmanship for a period of (1) year from the date of purchase. Warranty is contingent on installation in accordance with the instructions provided. This warranty does not apply where repairs or alterations have been made or attempted by others; or the unit has been abused or misused. Warranty does not include damage in shipment unless the damage is due to the negligence of RadonAway. All other warranties, expressed or written, are not valid. To make a claim under these limited warranties, you must return the defective item to RadonAway with a copy of the purchase receipt. RadonAway is not responsible for installation or removal cost associated with this warranty. In no case is RadonAway liable beyond the repair or replacement of the defective product FOB RadonAway. THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. THERE IS NO WARRANTY OF MERCHANTIBILITY. ALL OTHER WARRANTIES, EXPRESSED OR WRITTEN, ARE NOT VALID. For service under these warranties, contact RadonAway for a Return Material Authorization (RMA) number and shipping information. No returns can be accepted without an RMA. If factory return is required, the customer assumes all shipping costs to and from factory. RP Radon Mitigation Fan All RadonAway® fans are specifically designed for radon mitigation. RP Series Fans provide superb performance, run ultra-quiet and are attractive. They are ideal for most sub-slab radon mitigation systems. Features • NEW Stay-White™ housing • Energy efficient • RP140 - ENERGY STAR Most Efficient 2018 • Ultra-quiet operation • Meets all electrical code requirements • Water-hardened motorized impeller • Seams sealed to inhibit radon leakage (RP140 & RP145 double snap sealed) • ETL Listed - for indoor or outdoor use • Thermally protected motor • Rated for commercial and residential use For Further Information, Contact Your Radon Professional: Rev B 0618 P/N 02051© 2018 RadonAway Installs white, stays white A C B All RadonAway® inline radon fans are covered by our 5-year, hassle-free warranty. MODEL P/N FAN DUCT DIAMETER WATTS RECOM. MAX. OP. PRESSURE “WC TYPICAL CFM vs. STATIC PRESSURE WC 0”.5”1.0”1.5”2.0” RP140 28460 4”15-21 0.7 135 70 --- RP145 28461 4”41-72 1.7 166 126 82 41 3 RP260 28462 6”47-65 1.3 251 157 70 -- RP265 28463 6”95-139 2.3 375 282 204 140 70 RP380*28208 8”96-138 2.0 531 415 268 139 41 ETL Listed RP140 Only *Currently not stay-white material. Model A B C RP140 4.5”9.7”8.5” RP145 4.5”9.7”8.5” RP260 6”11.75”8.6” RP265 6”11.75”8.6” RP380 8”13.41”10.53” with U.S. and imported parts. IN095 Rev B 0718 13 Saber Way, Ward Hill, MA 01835 | radonaway.com RP, GP, XP Pro Series Installation Instructions IN095 Rev B 0718 23 Saber Way Ward, Hill, MA 01835 | radonaway.com Fan Installation & Operating Instructions RP, GP, XP Series Fans Please Read and Save These Instructions. DO NOT CONNECT POWER SUPPLY UNTIL FAN IS COMPLETELY INSTALLED. MAKE SURE ELECTRICAL SERVICE TO FAN IS LOCKED IN “OFF” POSITION. DISCONNECT POWER BEFORE SERVICING FAN. 1. WARNING! For General Ventilating Use Only. Do Not Use to Exhaust Hazardous, Corrosive or Explosive Materials, Gases or Vapors. See Vapor Intrusion Application Note #AN001 for important information on VI Applications. RadonAway.com/vapor-intrusion 2. NOTE: Fan is suitable for use with solid state speed controls; however, use of speed controls is not generally recommended. 2. WARNING! Check voltage at the fan to insure it corresponds with nameplate. 3. WARNING! Normal operation of this device may affect the combustion airflow needed for safe operation of fuel burning equipment. Check for possible backdraft conditions on all combustion devices after installation. 4. NOTICE! There are no user serviceable parts located inside the fan unit. Do NOT attempt to open. Return unit to the factory. (See Warranty, p. 8, for details.) 5. WARNING! Do not leave fan unit installed on system piping without electrical power for more than 48 hours. Fan failure could result from this non-operational storage. 6. WARNING! TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: a) Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer. (See p. 8.) b) Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel. c) Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire rated construction. d) Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturers’ guidelines and safety standards such as those published by any National Fire Protection Association, and the American Society for Heating, Refrigerating and Air Conditioning Engineers (ASHRAE), and the local code authorities. e) When cutting or drilling into a wall or ceiling, do not damage electrical wiring and other hidden utilities. f) Ducted fans must always be vented to outdoors. g) If this unit is to be installed over a tub or shower, it must be marked as appropriate for the application and be connected to a GFCI (Ground Fault Circuit Interrupter) protected branch circuit. IN095 Rev B 0718 33 Saber Way, Ward Hill, MA 01835 | radonaway.com 1.0 SYSTEM DESIGN CONSIDERATIONS 1.1 INTRODUCTION The RP, GP and XP Series Radon Fans are intended for use by trained, professional, certified/licensed radon mitigators. The purpose of these instructions is to provide additional guidance for the most effective use of RP, GP and XP Series Fans. These instructions should be considered supplemental to EPA/radon industry standard practices, state and local building codes and regulations. In the event of a conflict, those codes, practices and regulations take precedence over these instructions. 1.2 FAN SEALING The RP, GP and XP Series Fans are factory sealed; no additional caulk or other materials are required to inhibit air leakage. 1.3 ENVIRONMENTALS The RP, GP and XP Series Fans are designed to perform year-round in all but the harshest climates without additional concern for temperature or weather. For installations in an area of severe cold weather, please contact RadonAway for assistance. When not in operation, the fan should be stored in an area where the temperature is never less than 32 degrees F or more than 100 degrees F. 1.4 ACOUSTICS The RP, GP and XP Series Fans, when installed properly, operate with little or no noticeable noise to the building occupants. The velocity of the outgoing air should be considered in the overall system design. In some cases the “rushing” sound of the outlet air may be disturbing. In these instances, the use of a RadonAway Exhaust Muffler is recommended. (To ensure quiet operation of inline and remote fans, each fan shall be installed using sound attenuation techniques appropriate for the installation. For bathroom and general ventilation applications, at least 8 feet of insulated flexible duct shall be installed between the exhaust or supply grille(s) and the fan(s). RP, GP and XP Series Fans are not suitable for kitchen range hood remote ventilation applications.) 1.5 GROUND WATER In the event that a temporary high water table results in water at or above slab level, water may be drawn into the riser pipes, thus blocking air flow to the RP, GP and XP Series Fan. The lack of cooling air may result in the fan cycling on and off as the internal temperature rises above the thermal cutoff. Should this condition arise, it is recommended that the fan be turned off until the water recedes, allowing for return to normal operation. 1.6 SLAB COVERAGE The RP, GP and XP Series Fans can provide coverage up to 2000+ sq. ft. per slab penetration. This will primarily depend on the sub-slab material in any particular installation. In general, the tighter the material, the smaller the area covered per penetration. Appropriate selection of the RP, GP and XP Series Fan best suited for the sub-slab material can improve the slab coverage. The RP, GP and XP Series have a wide range of models to choose from to cover a wide range of sub-slab materials. The RP140 and 145 are best suited for general purpose use. The RP 260 can be used where additional airflow is required, and the RP265 and RP 380 are best suited for large slab, high airflow applications. Additional suction points can be added as required. It is recommended that a small pit (5 to 10 gallons in size) be created below the slab at each suction hole. Fan Installation & Operating Instructions RP Series RP140 | P/N 28460 RP145 | P/N 28461 RP260 | P/N 28462 RP265 | P/N 28463 RP380 | P/N 28464 GP Series GP201 | P/N 28465 GP301 | P/N 28466 GP401 | P/N 28467 GP501 | P/N 28468 XP Series XP151 | P/N 28469 XP201 | P/N 28470 IN095 Rev B 0718 43 Saber Way Ward, Hill, MA 01835 | radonaway.com 1.7 CONDENSATION & DRAINAGE Condensation is formed in the piping of a mitigation system when the air in the piping is chilled below its dew point. This can occur at points where the system piping goes through unheated space such as an attic, garage or outside. The system design must provide a means for water to drain back to a slab hole to remove the condensation. The RP, GP and XP Series Fan MUST be mounted vertically plumb and level, with the outlet pointing up for proper drainage through the fan. Avoid mounting the fan in any orientation that will allow water to accumulate inside the fan housing. The RP, GP and XP Series Fans are NOT suitable for underground burial. For RP, GP and XP Series Fan piping, the following table provides the minimum recommended pipe diameter and pitch under several system conditions. See p. 7 for detailed specifications. Pipe Diameter Minimum Rise per Ft of Run* @25 CFM @50 CFM @100 CFM 4”1/8”1/4”3/8” 3”1/4”3/8”1 1/2” 1.8 SYSTEM MONITOR & LABEL A System Monitor, such as a manometer (P/N 50017) or audible alarm (P/N 28001-2, 28001-4 or 28421), is required to notify the occupants of a fan system malfunction. A System Label (provided with Manometer P/N 50017) with instructions for contacting the installing contractor for service and identifying the necessity for regular radon tests to be conducted by the building occupants must be conspicuously placed in a location where the occupants frequent and can see the label. 1.9 ELECTRICAL WIRING The RP, GP and XP Series Fans operate on standard 120V, 60Hz AC. All wiring must be performed in accordance with National Fire Protection (NFPA) National Electrical Code, Standard #70, current edition, for all commercial and industrial work, and state and local building codes. All wiring must be performed by a qualified and licensed electrician. Outdoor installations require the use of a UL Listed watertight conduit. Ensure that all exterior electrical boxes are outdoor rated and properly sealed to prevent water penetration into the box. A means, such as a weep hole, is recommended to drain the box. 1.10 SPEED CONTROLS The RP, GP and XP Series Fans are rated for use with electronic speed controls; however, speed controls are generally not recommended. If used, the recommended speed control is Pass & Seymour Solid State Speed Control (Cat. No. 94601-1). RUNRISE 120 VAC Common Ground CapacitorWhite Black Brn Brn/Wht Green Motor RP, GP, XP Series Fan Wiring Diagram IN095 Rev B 0718 53 Saber Way, Ward Hill, MA 01835 | radonaway.com 2.0 INSTALLATION The RP, GP and XP Series Fans can be mounted indoors or outdoors. (It is suggested that EPA and radon mitigation standards recommendations be followed in choosing the fan location.) The GP fans have an integrated mounting bracket; RP and XP Series Fans may be mounted directly on the system piping or fastened to a supporting structure by means of an optional mounting bracket. The ducting from the fan to the outside of the building has a strong effect on noise and fan energy use. Use the shortest, straightest duct routing possible for best performance, and avoid installing the fan with smaller ducts than recommended. Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing ducts may not achieve their rated airflow. 2.1 MOUNTING Mount the RP, GP and XP Series Fan vertically with outlet up. Insure the unit is plumb and level. When mounting directly on the system piping assure that the fan does not contact any building surface to avoid vibration noise. 2.2 MOUNTING BRACKET (optional) The RP and XP Series Fans may be optionally secured with the RadonAway P/N 25007 mounting bracket. Foam or rubber grommets may also be used between the bracket and mounting surface for vibration isolation. 2.3 SYSTEM PIPING Complete piping run, using flexible couplings as a means of disconnect for servicing the unit and for vibration isolation. As the fan is typically outside of the building thermal boundary and is venting to the outside, installation of insulation around the fan is not required. 2.4 ELECTRICAL CONNECTION Connect wiring with wire nuts provided, observing proper connections (See Section 1.9). Note that the fan is not intended for connection to rigid metal conduit. 2.5 VENT MUFFLER (optional) Install the muffler assembly in the selected location in the outlet ducting. Solvent weld all connections. The muffler is normally installed at the end of the vent pipe. TYPICAL OUTDOOR INSTALLATION TYPICAL INDOOR INSTALLATION 2.6 OPERATION CHECKS & ANNUAL SYSTEM MAINTENANCE ______ Verify all connections are tight and leak-free. ______ Ensure the RP, GP and XP Series Fan and all ducting are secure and vibration-free. ______ Verify system vacuum pressure with manometer. Insure vacuum pressure is within normal operating range and less than the maximum recommended operating pressure. (Based on sea-level operation, at higher altitudes reduce by about 4% per 1000 feet) (Further reduce Maximum Operating Pressure by 10% for High Temperature environments.) See Product Specifications. If this is exceeded, increase the number of suction points. ______ Verify Radon levels by testing to EPA Protocol and applicable testing standards. IN095 Rev B 0718 63 Saber Way Ward, Hill, MA 01835 | radonaway.com Typical CFM Vs. Static Pressure “WC 0”.5”1.0”1.5”1.75”2.0” XP151 150 115 69 --- XP201 112 95 70 40 -- Model Size Weight Inlet/Outlet XP151 9.5”H x 8.5” Dia.6 lbs 4.5”OD (4.0” PVC Sched 40 size compatible) XP201 9.5”H x 8.5” Dia.6 lbs 4.5” OD Model Power Consumption 120VAC, 60Hz, 1.5 Amp Maximum Maximum Recommended Operation Pressure* (Sea Level Operation)** XP151 45 - 60 watts 1.3” WC XP201 45 - 66 watts 1.7” WC *Reduce by 10% for High Temperature Operation **Reduce by 4% per 1000 ft. of altitude. THE FOLLOWING CHARTS SHOW THE PERFORMANCE OF THE RP, GP and XP SERIES FANS XP Series Product Specifications Typical CFM Vs. Static Pressure “WC Model 0”.25”.5”.75”1.0”1.25”1.5”1.75”2.0” RP140 135 103 70 14 ---- RP145 166 146 126 104 82 61 41 21 3 RP260 251 209 157 117 70 26 --- RP265 375 330 282 238 204 170 140 108 70 RP380 531 490 415 340 268 200 139 84 41 Model Size Weight Inlet/Outlet L.2 RP140 8.5”H x 9.7” Dia.5.5 lbs 4.5”OD (4.0” PVC Sched 40 size compatible)25 RP145 8.5”H x 9.7” Dia.5.5 lbs 4,5” OD 15 RP260 8.6”H x 11.75” Dia.5.5 lbs 6.0” OD 48 RP265 8.6”H x 11.75” Dia.6.5 lbs 6.0” OD 30 RP380 10.53”H x 13.41” Dia.11.5 lbs 8.0” OD 57 Model Power Consumption 120VAC, 60Hz, 1.5 Amp Maximum Maximum Recommended Operation Pressure* (Sea Level Operation)** RP140 15 - 21 watts 0.7” WC RP145 41 - 72 watts 1.7” WC RP260 47-65 watts 1.3” WC RP265 95 - 139 watts 2.3” WC RP380 96 - 138 watts 2.0” WC L.2 = Estimated Equivalent Length of Rigid Metal Ducting resulting in .2” WC pressure loss for Duct Size listed. Longer Equivalent Lengths can be accommodated at Flows Lower than that at .2” WC pressure loss (see CFM Vs Static Pressure “WC Table). *Reduce by 10% for High Temperature Operation **Reduce by 4% per 1000 ft. of altitude. RP Series Product Specifications IN095 Rev B 0718 73 Saber Way, Ward Hill, MA 01835 | radonaway.com Typical CFM Vs. Static Pressure “WC 1.0”1.5”2.0”2.5”3.0”3.5”4.0” GP201 54 42 11 ---- GP301 64 54 41 4 --- GP401 -61 52 44 22 -- GP501 --66 58 50 27 4 Model Size Weight Inlet/Outlet GP201 13”H x 12.5” Dia.12 lbs 3.5”OD (3.0” PVC Sched 40 size compatible) GP301 13”H x 12.5” Dia.12 lbs 3.5” OD GP401 13”H x 12.5” Dia.12 lbs 3.5” OD GP501 13”H x 12.5” Dia.12 lbs 3.5” OD Model Power Consumption 120VAC, 60Hz, 1.5 Amp Maximum Maximum Recommended Operation Pressure* (Sea Level Operation)** GP201 31-65 watts 1.8” WC GP301 56-100 watts 2.3” WC GP401 62-128 watts 3.0” WC GP501 68 - 146 watts 3.8” WC *Reduce by 10% for High Temperature Operation **Reduce by 4% per 1000 ft. of altitude. GP Series Product Specifications Typical CFM Vs. Static Pressure “WC Model0”.25”.5”.75”1.0”1.25”1.5”1.75”2.0” RP1401351037014---- RP145166146126104826141213 RP2602512091571177026--- RP26537533028223820417014010870 RP3805314904153402682001398441 Model Recommended Duct PVC Pipe Mounting Thermal Cutout Insulation Class RP140 3” or 4” Schedule 20/40 PVC Mount on the duct pipe or with optional mounting bracket. For Ventilation: 4”, 6” or 8” Rigid or Flexible Ducting. 130oC/266oF Class B Insulation RP145 130oC/266oF Class F InsulationRP260150oC/302oF RP265 150oC/302oF RP380 6” Schedule 20/40 PVC Pipe 150oC/302oF XP151 3” or 4” Schedule 20/40 PVC Fan may be mounted on the duct pipe or with integral flanges.120oC/248oF Class B InsulationXP201 GP201 3” or 4” Schedule 20/40 PVC Fan may be mounted on the duct pipe or with integral flanges.120oC/248oF Class B InsulationGP301 GP401 GP501 RP, XP and GP Series Additional Specifications Continuous Duty 3000 RPM Thermally Protected RP, GP Residential and Commercial XP Residential Only Rated for Indoor or Outdoor Use IN095 Rev B 0718 83 Saber Way Ward, Hill, MA 01835 | radonaway.com IMPORTANT INSTRUCTIONS TO INSTALLER Inspect the RadonAway® RP, GP and XP Series Fan for shipping damage within 15 days of receipt. Notify RadonAway of any damages immediately. RadonAway is not responsible for damages incurred during shipping. However, for your benefit, RadonAway does insure shipments. There are no user serviceable parts inside the fan. Do not attempt to open the housing. Return unit to factory. (See Warranty below). Install the RP, GP and XP Series Fan in accordance with all EPA, ANSI/AARST standard practices, and state and local building codes and regulations. Provide a copy of this instruction or comparable radon system and testing information to the building occupants after completing system installation. Warranty RadonAway® warrants that the RP, GP (excluding GP500) and XP Series Fan (the “Fan”) will be free from defects in materials and workmanship for a period of 12 months from the date of purchase or 18 months from the date of manufacture, whichever is sooner (the “Warranty Term”). RadonAway® will replace any fan which fails due to defects in materials or workmanship during the Warranty Term. This Warranty is contingent on installation of the Fan in accordance with the instructions provided. This Warranty does not apply where any repairs or alterations have been made or attempted by others, or if the unit has been abused or misused. Warranty does not cover damage in shipment unless the damage is due to the negligence of RadonAway®. The Fan must be returned (at Owner’s cost) to the RadonAway® factory. Any Fan returned to the factory will be discarded unless the Owner provides specific instructions along with the Fan when it is returned regardless of whether or not the Fan is actually replaced under this warranty. Proof of purchase must be supplied upon request for service under this Warranty. 5-YEAR EXTENDED WARRANTY WITH PROFESSIONAL INSTALLATION. RadonAway® will extend the Warranty Term of the fan to 60 months (5 years) from date of purchase or 66 months from date of manufacture, whichever is sooner, provided that the fan is installed by a professional radon mitigation contractor. Proof of purchase and/or proof of professional installation may be required for service under this warranty. No extended warranty is offered outside the Continental United States and Canada beyond the standard 12 months from the date of purchase or18 months from the date of manufacture, whichever is sooner. RadonAway® is not responsible for installation, removal or delivery costs associated with this Warranty. LIMITATION OF WARRANTY EXCEPT AS STATED ABOVE, THE RP, GP (excluding GP500) and XP SERIES FANS ARE PROVIDED WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULARPURPOSE. IN NO EVENT SHALL RADONAWAY BE LIABLE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF, OR RELATING TO, THE FAN OR THE PERFORMANCE THEREOF. RADONAWAY’S AGGREGATE LIABILITY HEREUNDER SHALL NOT IN ANY EVENT EXCEED THE AMOUNT OF THE PURCHASE PRICE OF SAID PRODUCT. THE SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY SHALL BE THE REPAIR OR REPLACEMENT OF THE PRODUCT, TO THE EXTENT THE SAME DOES NOT MEET WITH RADONAWAY’S WARRANTY AS PROVIDED ABOVE. For service under this Warranty, contact RadonAway for a Return Material Authorization (RMA) number and shipping information. No returns can be accepted without an RMA. If factory return is required, the customer assumes all shipping costs, including insurance, to and from factory. RadonAway® 3 Saber Way Ward Hill, MA 01835 USA TEL (978) 521-3703 FAX (978) 521-3964 Email to: Returns@RadonAway.com Record the following information for your records: Serial Number: Purchase Date: