HomeMy WebLinkAboutFA-1724_29037_I_UST-10B_20220905Page 1 of 7 9/5/2022 1:33 PM
North Carolina
Department of Environmental Quality
Underground Storage Tank
UST-10BPrinted:9/5/2022 1:33 PM
Inspection Result:Failed Inspection Date:8/30/2022
Partial Inspection:No Arrive and Depart Times:1:45 PM-2:15 PM
Facility ID:00-0-0000022006 Inspector Pamela Harrelson
Facility Name THE CORNER STORE Insp.Type Compliance
Facility Address 220 W MAIN STREET
ROWLAND,NC 28383
Robeson County
Located facility,USTs onsite
Reason(s)Routine Compliance
Location 34.53833,-79.29444
Permit Exp.3/31/2013
Facility Phone (910)422-9647
CONTACTS
Contact Type Contact Information
Regulatory Operator
since 10/4/2006
FRANK E THOMPSON,739 GADDY MILLS ROAD ROWLAND,NC 28383,Phone:
(910)422-9674
Owner
since 10/4/2006
FRANK E THOMPSON,739 GADDY MILLS ROAD ROWLAND,NC 28383,Phone:
(910)422-9674
Manager
since 4/24/2002
FRANK E THOMPSON,220 W MAIN STREET ROWLAND,NC 28383,Phone:(910)
422-9674
OWNERSHIP CHANGE
New Owner Change Date Basis Transfer of Ownership Form (UST-15)Submitted
No
EMERGENCY RESPONSE
Emergency response placard with emergency response operator contact information is
posted in the dispensing areas if the dispensers are left on without an attendant present?
N/A
OTHER PARTICIPANTS
Name Organization
INSPECTOR COMMENTS
Type Date Comment
ADDITIONAL INSPECTOR COMMENTS
TANKS AND PIPING INFORMATION
Tanks Tank #1(Plus)Tank #2(Premium)Tank #3(Regular)
Tank ID Plus Premium Regular
TIMS Tank ID 2 3 1
Is tank registered?Yes Yes Yes
Date tank installed 9/23/1982 5/10/1976 5/8/1985
Capacity of Tank in Gallons 4000 4000 8000
Is tank regulated Yes Yes Yes
Diameter (Inches)
Tank /Product use Motor Fuel Motor Fuel Motor Fuel
Product stored in Tank Gasoline,Gas Mix Gasoline,Gas Mix Gasoline,Gas Mix
Product Detail Mid-Grade Premium Regular
If hazardous substance,CAS#or
description
UST-10B Facility ID:00-0-0000022006
Page 2 of 7 9/5/2022 1:33 PM
Tanks Tank #1(Plus)Tank #2(Premium)Tank #3(Regular)
If other,description
Tank status Temporarily Closed Temporarily Closed Temporarily Closed
Tank closure report submitted
Date tank last operated 2/1/2008 2/1/2008 4/30/2013
Inches of product in Tank 0.000000 0.000000 0.500000
Compartment tank No No No
Other compartment(s)
Base compartment
Manifolded tank No No No
Manifolded with tank(s)
Master manifold tank
New Tank System installed in
accordance with NC or MI
N/A N/A N/A
Tank Construction Material (DW
required after 11/1/07)
Single Wall Steel Single Wall Steel Single Wall Steel
If other,description
Tank Manufacturer/Model Unknown Unknown Unknown
If other,describe
Tank material verified by UST-7A/B UST-7A/B UST-7A/B
Date Pipe Installed 9/23/1982 5/10/1976 5/8/1985
Was UST Piping Installed on or
after 11/1/2007?
No No No
Piping Construction Material (DW
required after 11/1/07)
Single Wall Steel Single Wall Steel Single Wall Steel
If other,description
Pipe Manufacturer/Model Unknown Unknown Unknown
If other,describe
Pipe material verified by UST-7A/B UST-7A/B UST-7A/B
If E-blend >10%or Biodiesel
Blend >20%;Was UST-20
completed and approved?
N/A N/A N/A
CORROSION PROTECTION
Tank Corrosion Protection Tank #1(Plus)Tank
#2(Premium)
Tank
#3(Regular)
DWM notified of current CP method Yes Yes Yes
Integrity assessment performed after 3/1/06 No No No
CP Method 1 Impressed
Current
Impressed
Current
Impressed
Current
if other,Description
CP Installation Date 10/15/1999 10/15/1999 10/15/1999
CP Method 2
if other,Description
CP Installation Date
Flex Connector ,Piping Extensions,and/or other metal
fittings Present
None None None
Flex connector isolated from ground
Source of verification of CP for Flex Connectors,piping
extensions and/or other metal fittings
if other,Description
Submersible pump (STP)is isolated from ground N/A N/A N/A
Piping extensions and/or other metal fittings are
isolated from ground
Flex connector,STP and/or other metal fittings
protected from corrosion
Corrosion protection method Impressed
Current
Impressed
Current
Impressed
Current
UST-10B Facility ID:00-0-0000022006
Page 3 of 7 9/5/2022 1:33 PM
Tank Corrosion Protection Tank #1(Plus)Tank
#2(Premium)
Tank
#3(Regular)
Flex connector ,Piping extensions,and/or other metal
fittings CP Installation Date
10/15/1999 10/15/1999 10/15/1999
Dielectric Coating Installed (If tank installed after
12/22/88
N/A N/A N/A
Pipe Corrosion Protection Tank #1(Plus)Tank
#2(Premium)
Tank
#3(Regular)
DWM notified of current CP method Yes Yes Yes
CP method Impressed
Current
Impressed
Current
Impressed
Current
if other,Description
CP Installation Date 10/15/1999 10/15/1999 10/15/1999
Dielectric Coating Installed (If piping installed
after 12/22/88
N/A N/A N/A
Dispenser Corrosion Protection Dispenser
#1(PLUS)
Dispenser
#2(PREMIUM)
Dispenser
#3(REGULAR)
Flex Connector ,Piping Extensions,and/or other
metal fittings Present
Other Metal Other Metal Other Metal
Flex connector isolated from ground N/A N/A N/A
Source of verification of CP for Flex Connectors,
piping extensions and/or other metal fittings
Visual Visual Visual
if other,Description
Piping extensions and/or other metal fittings are
isolated from ground
No No No
Flex Connectors,Piping extensions and/or other
metal fittings protected from corrosion
Yes Yes Yes
Corrosion protection method Impressed
Current
Impressed
Current
Impressed
Current
Flex connector,Piping extensions,and/or other
metal fittings CP Installation Date
10/15/1999 10/15/1999 10/15/1999
Source of Information for verification of corrosion
protection for Riser pipe and other metal piping
Visual Visual Visual
if other,Description
CP Conclusions
CP Requirements Met?No
Issues Permanently close the UST system (MT1H &CL1 if TOS)
Impressed Current Systems IC System #1
Applies to Tanks #1(Plus),#2(Premium),#3(Regular)
Current Voltage (Gauge)0
Current Amperage (Gauge)0
Current Voltage (Multimeter)
Measured Shunt Voltage (mV)
Rectifier Shunt Factor (Amps/mV)
Amps -Calculated
Last three 60-day readings available No
System operating properly No
If no,select all that apply 0 volts and/or 0 amps,System disabled or
not operational
If other,describe
Hour meter reading?
UST-10B Facility ID:00-0-0000022006
Page 4 of 7 9/5/2022 1:33 PM
Impressed Current Systems IC System #1
Hour meter installed No
CP Test
No CP Test Results Provided
SPILL PREVENTION
Has DWM been notified of spill methods?Yes
Spill/Overfill Details Tank #1(Plus)Tank
#2(Premium)
Tank
#3(Regular)
Is a drop tube present?N/A N/A N/A
Type of Stage I vapor recovery?Dual Point Dual Point Dual Point
Local Fill Tank #1(Plus)Tank
#2(Premium)
Tank
#3(Regular)
Does Tank have a Second Fill?No No No
Spill Protection Catchment
Basin
Catchment
Basin
Catchment
Basin
Is spill prevention equipment provided and verified?Yes Yes Yes
Manufacturer/Model OPW:1-21XX
DEVR Series
(SW)
OPW:1-21XX
DEVR Series
(SW)
OPW:1-21XX
DEVR Series
(SW)
If other,describe
Spill bucket is double-walled?N/A N/A N/A
Monitoring Type
(UST-6B)
Is spill bucket interstice monitored every 30 days?
(If installed before 11/1/07)
Spill bucket is isolated or made of non-corroding
materials?(If installed after 11/1/07)
N/A N/A N/A
Date spill prevention provided 12/15/2001 12/15/2001 12/15/2001
Last 12 monthly spill bucket checks completed and
all deficiencies corrected (UST-27)?
Is spill prevention operating properly?Yes Yes Yes
If No,select all that apply
If other,describe
O&M walkthrough inspection completed in
accordance with national standard (e.g.PEI RP 900)
(UST-27)?
3 Year Tightness Test Date
(UST-6D/23A)
Primary Tightness Test Result
(UST-6D/23A)
Secondary Tightness Test Result
(UST-6D/23A)
Tightness Testing done in accordance with a
standard?
OVERFILL PREVENTION
Has DWM been notified of overfill methods?Yes
Overfill Control Tank #1(Plus)Tank
#2(Premium)
Tank
#3(Regular)
Is overfill prevention equipment provided and
verified?
Yes Yes Yes
Date overfill control provided 12/15/2001 12/15/2001 12/15/2001
UST-10B Facility ID:00-0-0000022006
Page 5 of 7 9/5/2022 1:33 PM
Overfill Control Tank #1(Plus)Tank
#2(Premium)
Tank
#3(Regular)
Type of overfill equipment Auto Shutoff
Device
Auto Shutoff
Device
Auto Shutoff
Device
Source of information for overfill control verification Visual
observation
Visual
observation
Visual
observation
If other,describe
Manufacturer/Model OPW:61SO
Series (FV)
OPW:61SO
Series (FV)
OPW:61SO
Series (FV)
If other,describe
Is overfill control operating properly?Yes Yes Yes
If No,select all that apply
If other,describe
Overfill check date (UST-22A)
Overfill check result (UST-22A)
Capacity of Tank in Gallons 4000 4000 8000
Diameter (Inches)
Dispenser Sumps Dispenser
#1(PLUS)
Dispenser
#2(PREMIUM)
Dispenser
#3(REGULAR)
Are containment sumps present?No No No
Installation Date
Sump Manufacturer
If Other (Specify)
Sump Construction Type
Sump Construction Material
If Other (Specify)
Are containment sumps monitored?
Is monitoring required per 2N .0900?No No No
Piping components and/or STP were
installed/replaced on or after 11/1/07?
No No No
Are spills or small weeps evident in sumps?No No No
Are single wall piping components located in
containment sump?(If installed after 11/1/07)
UDC Visual Inspection Date
(annually)(UST-22C)
UDC Visual Inspection Results
(UST-22C)
Annual containment sump check completed in
accordance with national standard (e.g.PEI RP
900)?
SITING AND SECONDARY CONTAINMENT
Siting And Sec.Containment-General Tank #1(Plus)Tank
#2(Premium)
Tank
#3(Regular)
UST system upgraded with corrosion protection,
spill and overfill before 1/1/91?
No No No
UST system and/or piping are located within siting
and secondary containment areas?
No No No
LEAK DETECTION
General Tank #1(Plus)Tank
#2(Premium)
Tank
#3(Regular)
DWM notified of leak detection method?Yes Yes Yes
Piping Type
UST-10B Facility ID:00-0-0000022006
Page 6 of 7 9/5/2022 1:33 PM
General Tank #1(Plus)Tank
#2(Premium)
Tank
#3(Regular)
Piping type Suction System Suction System Suction System
if other,specify
Suction check type Dispenser Dispenser Dispenser
Type LLD present.Not Required Not Required Not Required
Tank Release Detection
Primary leak detection method Not Required Not Required Not Required
if other,specify
Primary LD install date 5/1/2002 5/1/2002 5/1/2002
Secondary leak detection method
if other,specify
Piping Release Detection
Primary leak detection method Not Required Not Required Not Required
if other,specify
Primary LD install date 5/1/2002 5/1/2002 5/1/2002
Secondary leak detection method
if other,specify
Equipment Checks
Last 12 monthly RD equipment checks completed
and all deficiencies corrected (UST-27)?
if no,select all that apply
Annual RD equipment operability check result
(UST-22B)
N/A N/A N/A
if Fail,select all that apply
Annual RD equipment operability check date
(UST-22B)
RD equipment checks completed per national
standard (e.g.PEI RP 900/1200)(UST-22B/27)?
TEMPORARY CLOSURE
Temporary Closure
Temporary Closure Requirements Met?No
Issues CP system not maintained:Permanently close UST System
(CL3:A7)
REPAIRS
Repairs
Any Repair Issues?No
Issues
Delivery Information Tank #1(Plus)Tank #2(Premium)Tank #3(Regular)
All deliveries made to permitted tanks N/A N/A N/A
UST-10B Facility ID:00-0-0000022006
Page 7 of 7 9/5/2022 1:33 PM
SITE DIAGRAM 1
Facility #00-0-0000022006
Page 1 of 1
North Carolina
Department of Environmental Quality
Underground Storage Tank
Field Inspection Report
Facility ID:00-0-0000022006 Inspection Date:8/30/2022
Facility Name:THE CORNER STORE Facility Address:
220 W MAIN STREET
ROWLAND,NC,28383
Robeson County
The following issues were noted during this inspection.
Violations
Violation #1 Violation Code:CL1
Failure to permanently close a substandard UST.Required Corrective Action(s):
• Close substandard UST.(Site#00-0-0000022006)
Violation #2 Violation Code:CL3
Improper Temporary Closure.Required Corrective Action(s):
• Permanently close USTs (Site#00-0-0000022006)
Inspector’s Printed Name
Pamela Harrelson
Signature
Date 9/5/2022
Disclaimer:This document is an informal evaluation of the deficiencies documented during the inspection and
does not constitute a final determination of compliance status with either state or federal Underground Storage
Tank (UST)regulations.A formal Notice of Violation listing the violations of the states UST regulations may be
sent to the owner and/or operator of the facility.
Facility ID:00-0-0000022006
Page 1 of 16 9/5/2022 1:32 PM
NC DEQ Facility Inspection Photos
PICDIAG SITE PHOTO
Facility ID:00-0-0000022006
Page 2 of 16 9/5/2022 1:32 PM
PICDIAG CLOSED BUILDING
Facility ID:00-0-0000022006
Page 3 of 16 9/5/2022 1:32 PM
PICDIAG DISPENSERS
Facility ID:00-0-0000022006
Page 4 of 16 9/5/2022 1:32 PM
PICDIAG 4.75 INCHES WATER 0 INCHES OF PRODUCT
Facility ID:00-0-0000022006
Page 5 of 16 9/5/2022 1:32 PM
PICDIAG PREMIUM SPILL BUCKET NO LOCK ON FILL PORT
Facility ID:00-0-0000022006
Page 6 of 16 9/5/2022 1:32 PM
PICDIAG PREMIUM TANK BED
Facility ID:00-0-0000022006
Page 7 of 16 9/5/2022 1:32 PM
PICDIAG RECTIFIER BOX ON SIDE OF BUILDING
Facility ID:00-0-0000022006
Page 8 of 16 9/5/2022 1:32 PM
PICDIAG PLUS AND REGULAR TANK BEDS
Facility ID:00-0-0000022006
Page 9 of 16 9/5/2022 1:32 PM
PICDIAG RECTIFIER BOX
Facility ID:00-0-0000022006
Page 10 of 16 9/5/2022 1:32 PM
PICDIAG NO VOLTS NO AMPS
Facility ID:00-0-0000022006
Page 11 of 16 9/5/2022 1:32 PM
PICDIAG PLUS HAS 6 INCHES WATER 0 PRODUCT
Facility ID:00-0-0000022006
Page 12 of 16 9/5/2022 1:32 PM
PICDIAG PLUS SPILL BUCKET NO LOCK ON FILL PORT
Facility ID:00-0-0000022006
Page 13 of 16 9/5/2022 1:32 PM
PICDIAG PLUS TANK BED
Facility ID:00-0-0000022006
Page 14 of 16 9/5/2022 1:32 PM
PICDIAG 0.5 IN GASOLINE 31 INCHES WATER
Facility ID:00-0-0000022006
Page 15 of 16 9/5/2022 1:32 PM
PICDIAG REGULAR SPILL BUCKET NO LOCK ON FILL PORT
Facility ID:00-0-0000022006
Page 16 of 16 9/5/2022 1:32 PM
PICDIAG REGULAR TANK BED