HomeMy WebLinkAbout16055-Loftis-Blythe-Methane Warning System Installationi S:\AAA-Master Projects\Beacon Partners- BEP or BCP\BCP-028 5600 Cox Road\Methane Warning System Installation Rpt\Methane Warning System Installation_TCD for PE Stamp.doc Methane Warning System Installation Report Loftis-Blythe Construction Site (aka InnerLoop North Industrial Park) 5600 and 5518 David Cox Rd. Charlotte, North Carolina H&H Job No. BCP-028 Table of Contents Section Page No. 1.0 Introduction ................................................................................................................ 1 2.0 Methane Warning System Installation ..................................................................... 2 3.0 Post-Installation Inspection....................................................................................... 4 4.0 Follow-Up Methane Monitoring and System Testing............................................. 5 List of Figures Figure 1 Site Map Figure E1 Methane Warning System Specifications Figure E2 Methane Warning System Layout List of Appendices Appendix A Methane Sensor Specification Sheet Appendix B Methane Warning System Installation Certification Appendix C Installation Photographs 1 S:\AAA-Master Projects\Beacon Partners- BEP or BCP\BCP-028 5600 Cox Road\Methane Warning System Installation Rpt\Methane Warning System Installation_TCD for PE Stamp.doc Methane Warning System Installation Report Loftis-Blythe Construction Site (aka InnerLoop North Industrial Park) 5600 and 5518 David Cox Rd. Charlotte, North Carolina H&H Job No. BCP-028 1.0 Introduction This Methane Warning System Installation Report has been prepared by Hart & Hickman, PC (H&H) to document the installation and post-installation inspection and testing of the methane warning system installed in the western portion of “Building 2” at the Loftis-Blythe Construction Brownfields site (Brownfields Project No. 16055-12-060) located at 5518 David Cox Rd. in Charlotte, North Carolina. A site map is provided as Figure 1. Results of post-construction methane probe monitoring indicated that a methane warning system was warranted for the western portion of Building 2. As such, in accordance with the Environmental Management Plan (EMP) for the site, H&H provided a Methane Warning System Design Plan to the North Carolina Department of Environmental Quality (DEQ) on May 16, 2017 to monitor for elevated methane concentrations inside the western portion of Building 2. Following approval from DEQ, the Methane Warning System was installed at the site. The purpose of this report is to document the installation and post-installation inspection and testing of the Methane Warning System. 2 S:\AAA-Master Projects\Beacon Partners- BEP or BCP\BCP-028 5600 Cox Road\Methane Warning System Installation Rpt\Methane Warning System Installation_TCD for PE Stamp.doc 2.0 Methane Warning System Installation In May 2017, the methane warning system was installed in the western portion of Building 2 currently occupied by JDNA. The installation was conducted in accordance with the Methane Warning System Design Plan provided to DEQ on May 16, 2017, revised per comments from DEQ on May 19, 2017, and approved on May 22, 2017. Design specifications are included as Figure E-1. The western portion of Building 2 consists of an approximate 3,400 square foot (sq ft) office space and an approximate 41,000 sq ft open warehouse. In accordance with the approved methane warning system design, a total of seventy-seven (77) GD-2A sensors were installed in the office and warehouse space. The sensors are installed at a frequency that meet or exceed the manufacturers recommendation of one sensor per every 900 square feet. In addition (as requested by DEQ), sensors in the office area were installed in the offices, closets, and a cabinet in the break room. The locations of the sensors are shown on Figure E-2. The GD-2A sensor is designed to send an alarm signal to a central control panel in the event methane is detected above 25% of the lower explosive limit (LEL). The GD-2A is equipped with a solid-state sensor that does not require calibration, and the expected life of a GD-2A sensor is 7 to 10 years. The manufacturer specification sheet for the GD-2A senor is included in Appendix A. At the time of installation, each sensor was tested by manually pressing the “test” button located on the unit and/or exposing the sensor to combustible gas. All of the sensors passed the manual test. In the event a sensor malfunctions or loses communication with the central control panel, a “trouble” signal will be sent to the panel and a third party monitoring company which will notify personnel on-site that a sensor has lost communication or needs to be replaced. In the event of a power loss, the methane warning system will operate on a battery backup installed in the control panel. The sensors are wired into eight (8) “zones” inside the facility and tied into the building’s central alarm control panel. The layout of each zone is shown on Figure E-2. In the event the methane is detected above 25% LEL, a signal will be sent to the central control panel and the system 3 S:\AAA-Master Projects\Beacon Partners- BEP or BCP\BCP-028 5600 Cox Road\Methane Warning System Installation Rpt\Methane Warning System Installation_TCD for PE Stamp.doc alarm will be activated which will prompt an evacuation. The alarm consists of illuminated strobes and sirens in the office, warehouse space, and entryway of the JDNA space. Once an alarm is triggered, a notification will automatically be sent a third-party alarm monitoring service. The third-party monitoring service will then call and notify the on-site contact person and the property owner contact that an alarm has been triggered. The third-party monitoring service will also be able to remotely identify the “zone” that triggered the alarm and communicate the zone of the alarm to the on-site contact person and property owner contact. Following an alarm, on-site personnel and/or property management (on-call 24 hours) contacts will notify first responders to clear the building if it is suspected that the alarm was due to elevated methane. In the event of an alarm, DEQ will be notified within one business day once it has been verified that the alarm was the result of elevated levels of methane. If two (2) verified alarms occur within a six-month period, the property owner at that time will submit a plan for DEQ approval for a methane mitigation system. 4 S:\AAA-Master Projects\Beacon Partners- BEP or BCP\BCP-028 5600 Cox Road\Methane Warning System Installation Rpt\Methane Warning System Installation_TCD for PE Stamp.doc 3.0 Post-Installation Inspection On June 2, 2017, the system was inspected by a North Carolina Professional Engineer (PE) from H&H (Mr. Trinh DeSa) and a PE from Engitecture (Mr. Greg Wiley) to verify that the system was installed in accordance with the specifications included on Figure E-1 and Figure E-2 and the design goals of the warning system were met. The inspection generally included visually locating each sensor, manually testing a representative number of sensors with methane gas, confirming communication of the sensors with the central control panel, confirming the presence and operation of the alarm strobes and sirens, confirming that the correct alarm zone was displayed during an alarm event, and confirming the response from the third-party monitoring service. At the time of the inspection, the inspectors verified that the methane warning system was installed in accordance with the approved design. A sealed certification from Mr. Wiley is included in Appendix B and the seal of Mr. DeSa is included on the front cover of this report. Photographs of the system installation are included in Appendix C. 5 S:\AAA-Master Projects\Beacon Partners- BEP or BCP\BCP-028 5600 Cox Road\Methane Warning System Installation Rpt\Methane Warning System Installation_TCD for PE Stamp.doc 4.0 Follow-Up Methane Monitoring and System Testing In accordance with the approved design, each subsequent year following installation, the methane warning system shall be checked for performance by manually activating the “test” button on a representative number of GD-2A sensors and verifying communication with the sensors from the central control panel. In addition, the system check will include visually confirming that each sensor’s green “armed” light is illuminated. In accordance with the approved Methane Warning System Design, the property owner will continue monitoring of the methane probes on a quarterly basis until December 2018 to evaluate if methane concentrations continue to increase, stabilize, or decrease with time. In addition to the methane probes, methane readings will also be collected from inside both site buildings, sewer manholes on the north side of Building 2 and a drainage trench on the south side of Building 2 during the quarterly monitoring events. The first monitoring event will be conducted in June 2017. In addition, as part of the monitoring, unpaved and paved areas will be inspected for the presence of settlement areas which could be locations of methane gas accumulation and methane readings will be taken from those areas as well. If settlement areas are observed, the property owner will be notified to take corrective actions such as filling in holes or repairing pavement. Annual monitoring reports of the methane monitoring and the testing of the methane warning system will be prepared and submitted to DEQ in January of each year concurrent with the submittal of the annual Land Use Restriction Update (LURU). The annual reports will detail the following with regard to the methane monitoring: • results of the methane probe, utility, and indoor air monitoring • results of the exterior area visual inspections (including corrective actions taken, if any) • in the January 2019 submittal, a recommendation for continued methane monitoring will be included (i.e., locations and sampling frequency) 6 S:\AAA-Master Projects\Beacon Partners- BEP or BCP\BCP-028 5600 Cox Road\Methane Warning System Installation Rpt\Methane Warning System Installation_TCD for PE Stamp.doc The annual reports will also include documentation of the testing of the methane warning system: • documentation of the annual methane warning system testing • documentation of any alarm conditions and resolutions • repairs or adjustments made to the warning system The first annual report will be submitted in January 2018. MP-16 MP-15 DAVID C O X R O A D BUILDING 1 (5600 DAVID COX ROAD)OLD STATESVILLE ROADMP-17 MP-2 MP-14 MP-12 MP-10 MP-13 MP-7 MP-8 MP-9 MP-11 MP-6 MP-1 MP-10R PAVED AREA PAVED AREA BUILDING 2 (5518 DAVID COX ROAD) OFFICES OFFICES WAREHOUSE (JDNA) WAREHOUSE OFFICES WAREHOUSE BATHROOMS WAREHOUSE LEGEND SITE PROPERTY BOUNDARY CHAINLINK FENCE APPROXIMATE EXTENT OF LANDFILL AREA PERMANENT METHANE PROBE LOCATION TEMPORARY METHANE PROBE LOCATION (JULY 2013) DUKE POWER RIGHT-OF-WAY 2923 South Tryon Street-Suite 100 Charlotte, North Carolina 28203 704-586-0007(p) 704-586-0373(f) License # C-1269 / #C-245 Geology JOB NO. BCP-028 REVISION NO. 0DATE: 5-15-17 FIGURE NO. 1 LOFTIS-BLYTHE CONSTRUCTION SITE 5600 DAVID COX ROAD CHARLOTTE, NORTH CAROLINA SITE PLAN PAVED AREA PAVED AREA PAVED AREA PAVED AREA PAVED AREA FIRE ALARM GENERAL NOTES:1.COORDINATE FIRE ALARM SYSTEM SHUTDOWNS AND REPROGRAMMING WITH LANDLORD.2.PROVIDE ALL PROGRAMMING REQUIRED TO MAKE THE NEW DEVICES FUNCTIONAL.EXISTINGEXISTINGFACPFLOOR(2) EXISTINGPHONELINES TOMONITORINGSTATIONSEQUENCE OF OPERATION:UPON CHANGE IN STATUS OF ANY DEVICEON THE SYSTEM INDICATED IN THIS CHART,THE FIRE ALARM CONTROL PANEL SHALLACTIVATE AUDIBLE CHANGE INDICATORSAND DISPLAY THE SYSTEM POINT NUMBER,POINT DESCRIPTION, AND MESSAGEASSOCIATED WITH THE POINT.ACTIVATION OF ANY WATERFLOW DEVICE,SMOKE DETECTOR, OR OTHER INITIATINGDEVICE WILL CAUSE THE FUNCTION TOOCCUR NOTED IN THIS CHART.ANY GAS DETECTION ALARM SHALL ALERTSIMULTANEOUSLY A THIRD-PARTY CENTRALMONITORING COMPANY, THE GASDETECTION CONTROL PANEL, AND LOCALREPRESENTATIVE (ALARM COMPANY).INTERLOCK GAS DETECTORS WITHEXISTING FIRE ALARM CONTROL PANEL.CONTRACTOR SHALL POWER GAS DETECTIONSYSTEM BY THE 120 VOLT POWER CIRCUIT SERVINGTHE FIRE ALARM SYSTEM. CONTRACTOR SHALLPROVIDE AND INSTALL ANY 12 OR 24 VDC : 120V ACTRANSFORMER IF REQUIRED FOR CONVERSION. NOMORE THAN 180 WATTS OF LOAD IS BEING ADDEDTO THIS CIRCUIT.PART 3 EXECUTION3.01EXAMINATIONA.VERIFY THAT EQUIPMENT IS READY FOR ELECTRICAL CONNECTION, WIRING, ANDENERGIZATION.3.02ELECTRICAL CONNECTIONSA.MAKE ELECTRICAL CONNECTIONS IN ACCORDANCE WITH EQUIPMENT MANUFACTURER'SINSTRUCTIONS.B.MAKE CONDUIT CONNECTIONS TO EQUIPMENT USING FLEXIBLE CONDUIT. USE LIQUIDTIGHTFLEXIBLE CONDUIT WITH WATERTIGHT CONNECTORS IN DAMP OR WET LOCATIONS.C.CONNECT HEAT PRODUCING EQUIPMENT USING WIRE AND CABLE WITH INSULATION SUITABLEFOR TEMPERATURES ENCOUNTERED.D.PROVIDE RECEPTACLE OUTLET TO ACCOMMODATE CONNECTION WITH ATTACHMENT PLUG.E.PROVIDE CORD AND CAP WHERE FIELD-SUPPLIED ATTACHMENT PLUG IS REQUIRED.FIRE ALARM SYSTEM:1.01EXISTING SYSTEM IS A 120 VAC, ZONED, NON-CODED, CLOSED CIRCUIT, FULLY ELECTRONICALLYSUPERVISED (INCLUDING AUXILIARY SYSTEMS INTERCONNECT WIRING) SYSTEM LISTED BY UL INCOMPLIANCE WITH ALL APPLICABLE NFPA 72 AND OTHER STANDARDS AS WELL AS THE AMERICAN'SWITH DISABILITIES ACT (ADA). ALL FINAL CONNECTIONS, TESTING AND HAVE BEEN PERFORMED BYOR UNDER DIRECT SUPERVISION OF AN AUTHORIZED FACTORY REPRESENTATIVE. SYSTEM HAS A24HR MINIMUM BATTERY BACKUP.1.02INITIATING DEVICE ACTIVATION SHALL CAUSE OPERATION OF THE PROPER ALARM CIRCUIT IN THECONTROL PANEL, AND OPERATE ALL AUDIBLE AND VISUAL INDICATING ALARMS. ALL ALARM DEVICESAND LAMPS SHALL CONTINUE TO OPERATE UNTIL THE INITIATING DEVICE IS RESET. SUBSEQUENTALARMS SHALL RESOUND THE SYSTEM. AN AUDIBLE AND VISUAL SIGNAL SHALL INDICATE SYSTEMTROUBLE. THE CONTROL PANEL SHALL PROVIDE FOR ACTIVATING A UL LISTED CENTRAL STATIONSIGNAL FOR NOTIFYING THE FIRE DEPARTMENT.1.03 CONDUCTORS SHALL BE PLENUM-RATED AND INSTALLED IN CONDUIT AND INSTALLED INCOMPLIANCE WITH NFPA 70, ARTICLE 760; IN ADDITION TO WIRING METHODS 300.4.1.06ALL FIRE ALARM WIRING SHALL BE CLASS A OR B.1.07PROVIDE ALL REQUIRED MODULES, POWER EXTENDERS, PROGRAMMING, ETC. FOR A COMPLETE ANDOPERATIONAL SYSTEM.1.08SUBMIT FIRE ALARM SHOP DRAWINGS CONSISTING OF PRODUCT DATA, TO THE ENGINEER AND FORAPPROVAL.1.09WARRANTY - ALL WORK PERFORMED AND ALL MATERIALS AND EQUIPMENT FURNISHED UNDER THISCONTRACT SHALL BE FREE FROM DEFECTS AND SHALL REMAIN SO FOR A PERIOD OF AT LEAST TWO (2)YEARS FROM THE DATE OF ACCEPTANCE BY THE PROFESSIONAL ENGINEER AND/OR OWNER. THE FULLCOST OF MAINTENANCE, LABOR, AND MATERIALS REQUIRED TO CORRECT ANY DEFECT DURING THISTWO YEAR PERIOD SHALL BE IMMEDIATELY CORRECTED AT NO ADDITIONAL COST TO THE OWNER.ANY DEFECTS THAT RENDER THE SYSTEM INOPERATIVE SHALL BE REPAIRED WITHIN 24 HOURS OF THEOWNER NOTIFYING THE CONTRACTOR. OTHER DEFECTS SHALL BE REPAIRED WITHIN 48 HOURS OFTHE OWNER NOTIFYING THE CONTRACTOR.CONDUITPART 1 GENERAL1.01SECTION INCLUDESA.CONDUIT, FITTINGS AND CONDUIT BODIES.1.03SUBMITTALSA.PRODUCT DATA: PROVIDE FOR METALLIC CONDUIT, FLEXIBLE METAL CONDUIT, LIQUIDTIGHTFLEXIBLE METAL CONDUIT, METALLIC TUBING, NONMETALLIC CONDUIT, FLEXIBLE NONMETALLICCONDUIT, NONMETALLIC TUBING, FITTINGS, AND CONDUIT BODIES.B.PROJECT RECORD DOCUMENTS: ACCURATELY RECORD ACTUAL ROUTING OF CONDUITS LARGERTHAN 2 INCHES (51 MM).1.04QUALITY ASSURANCEA. CONFORM TO REQUIREMENTS OF NFPA 70. B. PRODUCTS: LISTED AND CLASSIFIED BY UNDERWRITERS LABORATORIES INC. AS SUITABLE FORPURPOSE SPECIFIED AND SHOWN.1.05DELIVERY, STORAGE, AND HANDLINGA.ACCEPT CONDUIT ON SITE. INSPECT FOR DAMAGE.B.PROTECT CONDUIT FROM CORROSION AND ENTRANCE OF DEBRIS BY STORING ABOVE GRADE.PROVIDE APPROPRIATE COVERING.C.PROTECT PVC CONDUIT FROM SUNLIGHT.PART 2 PRODUCTS2.01CONDUIT REQUIREMENTSA.CONDUIT SIZE: COMPLY WITH NFPA 70.1.MINIMUM SIZE: 1/2 INCH (13 MM) UNLESS OTHERWISE SPECIFIED.B.UNDERGROUND INSTALLATIONS:1.MORE THAN 5 FEET (1.5 METERS) FROM FOUNDATION WALL: USE RIGID STEEL CONDUIT,INTERMEDIATE METAL CONDUIT, OR PLASTIC COATED CONDUIT.2.WITHIN 5 FEET (1.5 METERS) FROM FOUNDATION WALL: USE RIGID STEEL CONDUIT,INTERMEDIATE METAL CONDUIT, PLASTIC COATED CONDUIT, OR THICKWALL NONMETALLICCONDUIT.3.IN OR UNDER SLAB ON GRADE: USE RIGID STEEL CONDUIT, INTERMEDIATE METAL CONDUIT,OR PLASTIC COATED CONDUIT.4.MINIMUM SIZE: 3/4 INCH (19 MM).C.OUTDOOR LOCATIONS ABOVE GRADE: USE RIGID STEEL CONDUIT, RIGID ALUMINUM CONDUIT,INTERMEDIATE METAL CONDUIT, OR ELECTRICAL METALLIC TUBING.D.IN SLAB ABOVE GRADE:1.USE RIGID STEEL CONDUIT, INTERMEDIATE METAL CONDUIT, ELECTRICAL METALLIC TUBING, ORTHICKWALL NONMETALLIC CONDUIT.2.MAXIMUM SIZE CONDUIT IN SLAB: 3/4 INCH (19 MM); 1/2 INCH (13 MM) FOR CONDUITSCROSSING EACH OTHER.E.WET AND DAMP LOCATIONS: USE RIGID STEEL CONDUIT, RIGID ALUMINUM CONDUIT,INTERMEDIATE METAL CONDUIT, ELECTRICAL METALLIC TUBING, THICKWALL NONMETALLICCONDUIT, OR NONMETALLIC TUBING.F.DRY LOCATIONS:1.CONCEALED: USE RIGID STEEL CONDUIT, RIGID ALUMINUM CONDUIT, INTERMEDIATE METALCONDUIT, ELECTRICAL METALLIC TUBING, THICKWALL NONMETALLIC CONDUIT, ORNONMETALLIC TUBING.2.EXPOSED: USE RIGID STEEL CONDUIT, RIGID ALUMINUM CONDUIT, INTERMEDIATE METALCONDUIT, ELECTRICAL METALLIC TUBING, OR THICKWALL NONMETALLIC CONDUIT.2.02METAL CONDUITA.RIGID STEEL CONDUIT: ANSI C80.1.B.RIGID ALUMINUM CONDUIT: ANSI C80.5.C.INTERMEDIATE METAL CONDUIT (IMC): RIGID STEEL.D.FITTINGS AND CONDUIT BODIES: NEMA FB 1; MATERIAL TO MATCH CONDUIT.2.03ELECTRICAL METALLIC TUBING (EMT)A.DESCRIPTION: ANSI C80.3; GALVANIZED TUBING.B.FITTINGS AND CONDUIT BODIES: NEMA FB 1; STEEL OR MALLEABLE IRON COMPRESSION TYPE.PART 3 EXECUTION3.01EXAMINATIONA.VERIFY THAT FIELD MEASUREMENTS ARE AS SHOWN ON DRAWINGS.B.VERIFY ROUTING AND TERMINATION LOCATIONS OF CONDUIT PRIOR TO ROUGH-IN.C.CONDUIT ROUTING IS SHOWN ON DRAWINGS IN APPROXIMATE LOCATIONS UNL3.02INSTALLATIONA.INSTALL CONDUIT SECURELY, IN A NEAT AND WORKMANLIKE MANNER, AS SPECIFIED IN NECA 1.B.INSTALL STEEL CONDUIT AS SPECIFIED IN NECA 101.C.ARRANGE SUPPORTS TO PREVENT MISALIGNMENT DURING WIRING INSTALLATION.D.SUPPORT CONDUIT USING COATED STEEL OR MALLEABLE IRON STRAPS, LAY-IN ADJUSTABLEHANGERS, CLEVIS HANGERS, AND SPLIT HANGERS.E.GROUP RELATED CONDUITS; SUPPORT USING CONDUIT RACK. CONSTRUCT RACK USING STEELCHANNEL; PROVIDE SPACE ON EACH FOR 25 PERCENT ADDITIONAL CONDUITS.F.FASTEN CONDUIT SUPPORTS TO BUILDING STRUCTURE AND SURFACES UNDER PROVISIONS OFSECTION 16070.G.DO NOT SUPPORT CONDUIT WITH WIRE OR PERFORATED PIPE STRAPS. REMOVE WIRE USED FORTEMPORARY SUPPORTS.H.DO NOT ATTACH CONDUIT TO CEILING SUPPORT WIRES.I.ARRANGE CONDUIT TO MAINTAIN HEADROOM AND PRESENT NEAT APPEARANCE.J.ROUTE EXPOSED CONDUIT PARALLEL AND PERPENDICULAR TO WALLS.K.ROUTE CONDUIT INSTALLED ABOVE ACCESSIBLE CEILINGS PARALLEL AND PERPENDICULAR TOWALLS.L.ROUTE CONDUIT IN AND UNDER SLAB FROM POINT-TO-POINT.M.MAINTAIN ADEQUATE CLEARANCE BETWEEN CONDUIT AND PIPING.N.CUT CONDUIT SQUARE USING SAW OR PIPECUTTER; DE-BURR CUT ENDS.O.BRING CONDUIT TO SHOULDER OF FITTINGS; FASTEN SECURELY.P.INSTALL NO MORE THAN EQUIVALENT OF THREE 90 DEGREE BENDS BETWEEN BOXES. USECONDUIT BODIES TO MAKE SHARP CHANGES IN DIRECTION, AS AROUND BEAMS. USE HYDRAULICONE SHOT BENDER TO FABRICATE BENDS IN METAL CONDUIT LARGER THAN 2 INCH (50 MM) SIZE.Q.AVOID MOISTURE TRAPS; PROVIDE JUNCTION BOX WITH DRAIN FITTING AT LOW POINTS INCONDUIT SYSTEM.R.PROVIDE SUITABLE FITTINGS TO ACCOMMODATE EXPANSION AND DEFLECTION WHERE CONDUITCROSSES SEISMIC.S.PROVIDE SUITABLE PULL STRING IN EACH EMPTY CONDUIT EXCEPT SLEEVES AND NIPPLES.T.USE SUITABLE CAPS TO PROTECT INSTALLED CONDUIT AGAINST ENTRANCE OF DIRT ANDMOISTURE.U.GROUND AND BOND CONDUIT UNDER PROVISIONS OF SECTION 16060.V.IDENTIFY CONDUIT UNDER PROVISIONS OF SECTION 16075.SUPPORTSA.ALL EQUIPMENT SHALL BE ADEQUATELY SUPPORTED FROM STRUCTURE.B.INSERTS IN MASONRY SHALL BE LEAD OR FIBER IN DRILLED HOLES, OR CAST IN PLACE.C.NAILS OR POWDER ACTUATED FASTENERS SHALL NOT BE USED.D.EMT/IMC/RGS SUPPORTS SHALL BE A MAXIMUM OF 8'-0" APART AND A MAXIMUM OF 3'-0" FROMBOXES.E.LIGHTING FIXTURES MOUNTED IN OR ON CEILING SHALL BE SUPPORTED FROM STRUCTURE VIA 12GAUGE STEEL WIRE. PROVIDE A MINIMUM OF FOUR WIRES, ONE ATTACHED TO EACH CORNER OFLAY-IN FIXTURES. RECESSED DOWNLIGHT FIXTURES SHALL BE SUPPORTED THE SAME. DO NOTSUPPORT RACEWAY OR FIXTURES FROM CEILING GRID OR DUCT WORK. USE U.L. LISTED GRIDCLIPS ON ALL LAY-IN FIXTURES.BOXESPART 1 GENERAL1.01SECTION INCLUDESA.PULL AND JUNCTION BOXES.1.02SUBMITTALSA.PROJECT RECORD DOCUMENTS: RECORD ACTUAL LOCATIONS AND MOUNTING HEIGHTS OFOUTLET, PULL, AND JUNCTION BOXES ON PROJECT RECORD DOCUMENTS.PART 2 EXECUTION2.01INSTALLATIONA.INSTALL BOXES SECURELY, IN A NEAT AND WORKMANLIKE MANNER, AS SPECIFIED IN NECA 1.B.INSTALL IN LOCATIONS AS SHOWN ON DRAWINGS, AND AS REQUIRED FOR SPLICES, TAPS, WIREPULLING, EQUIPMENT CONNECTIONS, AND AS REQUIRED BY NFPA 70.C.ORIENT BOXES TO ACCOMMODATE WIRING DEVICES ORIENTED AS SPECIFIED IN SECTION 16140.D.MAINTAIN HEADROOM AND PRESENT NEAT MECHANICAL APPEARANCE.E.ALIGN ADJACENT WALL MOUNTED OUTLET BOXES FOR SWITCHES, THERMOSTATS, AND SIMILARDEVICES.F.SUPPORT BOXES INDEPENDENTLY OF CONDUIT, EXCEPT CAST BOX THAT IS CONNECTED TO TWORIGID METAL CONDUITS BOTH SUPPORTED WITHIN 12 INCHES (305 MM) OF BOX.G.USE GANG BOX WHERE MORE THAN ONE DEVICE IS MOUNTED TOGETHER. DO NOT USESECTIONAL BOX.EQUIPMENT WIRINGPART 1 GENERAL1.01SECTION INCLUDESA.ELECTRICAL CONNECTIONS TO EQUIPMENT.PART 2 PRODUCTS2.01MATERIALSA.CORDS AND CAPS: NEMA WD 6; MATCH RECEPTACLE CONFIGURATION AT OUTLET PROVIDED FOREQUIPMENT.1. COLORS: CONFORM TO NEMA WD 1.2. CORD CONSTRUCTION: NFPA 70, TYPE SO, MULTICONDUCTOR FLEXIBLE CORD WITHIDENTIFIED EQUIPMENT GROUNDING CONDUCTOR, SUITABLE FOR USE IN DAMP LOCATIONS.GROUNDING AND BONDINGPART 1 GENERAL1.01SECTION INCLUDESA.GROUNDING AND BONDING COMPONENTS.B.PROVIDE ALL COMPONENTS NECESSARY TO COMPLETE THE GROUNDING SYSTEM(S)CONSISTING OF:1.EXISTING METAL UNDERGROUND WATER PIPE.2.METAL UNDERGROUND WATER PIPE.3.METAL FRAME OF THE BUILDING.4.STEEL WATER STORAGE TANK AND SUPPORTS.5.CONCRETE-ENCASED ELECTRODE.6.ROD ELECTRODES.7.PLATE ELECTRODES.8.ACTIVE ELECTRODES.1.02REFERENCESA.NETA STD ATS - ACCEPTANCE TESTING SPECIFICATIONS FOR ELECTRICAL POWERDISTRIBUTION EQUIPMENT AND SYSTEMS; INTERNATIONAL ELECTRICAL TESTINGASSOCIATION; 2007.B.NFPA 70 - NATIONAL ELECTRICAL CODE; NATIONAL FIRE PROTECTION ASSOCIATION; 2005.C.NFPA 99 - STANDARD FOR HEALTH CARE FACILITIES; NATIONAL FIRE PROTECTIONASSOCIATION; 2005.1.03PERFORMANCE REQUIREMENTSA.GROUNDING SYSTEM RESISTANCE: 5 OHMS.1.04SUBMITTALSA.PRODUCT DATA: PROVIDE FOR GROUNDING ELECTRODES AND CONNECTIONS.B.TEST REPORTS: INDICATE OVERALL RESISTANCE TO GROUND AND RESISTANCE OF EACHELECTRODE.C.MANUFACTURER'S INSTRUCTIONS: INDICATE APPLICATION CONDITIONS AND LIMITATIONSOF USE STIPULATED BY PRODUCT TESTING AGENCY SPECIFIED UNDER QUALITY ASSURANCE.INCLUDE INSTRUCTIONS FOR STORAGE, HANDLING, PROTECTION, EXAMINATION,PREPARATION, AND INSTALLATION OF PRODUCT.D.PROJECT RECORD DOCUMENTS: RECORD ACTUAL LOCATIONS OF COMPONENTS ANDGROUNDING ELECTRODES.E.CERTIFICATE OF COMPLIANCE: INDICATE APPROVAL OF INSTALLATION BY AUTHORITYHAVING JURISDICTION.1.05QUALITY ASSURANCEA.CONFORM TO REQUIREMENTS OF NFPA 70.B.MANUFACTURER QUALIFICATIONS: COMPANY SPECIALIZING IN MANUFACTURING THEPRODUCTS SPECIFIED IN THIS SECTION WITH MINIMUM THREE YEARS DOCUMENTEDEXPERIENCE WITH SERVICE FACILITIES WITHIN 100 MILES OF PROJECT.C.PRODUCTS: LISTED AND CLASSIFIED BY UNDERWRITERS LABORATORIES INC. AS SUITABLEFOR THE PURPOSE SPECIFIED AND INDICATED.PART 2 PRODUCTS2.01MANUFACTURERSA.COOPER POWER SYSTEMS:B.FRAMATOME CONNECTORS INTERNATIONAL:C.LIGHTNING MASTER CORPORATION:2.02ELECTRODESA.ROD ELECTRODES: COPPER.1.DIAMETER: 3/4 INCH (19 MM).2.LENGTH: 5 FEET (1500 MM).B.ACTIVE ELECTRODES: METALLIC-SALT-FILLED COPPER-TUBE ELECTRODE.1.SHAPE: STRAIGHT.2.LENGTH: 8 FEET (2400 MM).3.CONNECTOR: U-BOLT PRESSURE PLATE.C.FOUNDATION ELECTRODES: 2/0 AWG.2.03CONNECTORS AND ACCESSORIESA.MECHANICAL CONNECTORS: BRONZE.B.WIRE: STRANDED COPPER.C.GROUNDING ELECTRODE CONDUCTOR: SIZE TO MEET NFPA 70 REQUIREMENTS.D.GROUNDING WELL:1.WELL PIPE: 8 INCH (200 MM) BY 24 INCH (600 MM) LONG CLAY TILE PIPE WITH BELLED END.2.WELL COVER: CAST IRON WITH LEGEND "GROUND" EMBOSSED ON COVER.PART 3 EXECUTION3.01EXAMINATIONA.VERIFY EXISTING CONDITIONS PRIOR TO BEGINNING WORK.B.VERIFY THAT FINAL BACKFILL AND COMPACTION HAS BEEN COMPLETED BEFORE DRIVINGROD ELECTRODES.3.02INSTALLATIONA.INSTALL GROUND ELECTRODES AT LOCATIONS INDICATED. INSTALL ADDITIONAL RODELECTRODES AS REQUIRED TO ACHIEVE SPECIFIED RESISTANCE TO GROUND.B.PROVIDE GROUNDING WELL PIPE WITH COVER AT EACH ROD LOCATION. INSTALL WELL PIPETOP FLUSH WITH FINISHED GRADE.C.INSTALL 4 AWG BARE COPPER WIRE IN FOUNDATION FOOTING WHERE INDICATED.D.PROVIDE GROUNDING ELECTRODE CONDUCTOR AND CONNECT TO REINFORCING STEEL INFOUNDATION FOOTING WHERE INDICATED. BOND STEEL TOGETHER.E.PROVIDE BONDING TO MEET REQUIREMENTS DESCRIBED IN QUALITY ASSURANCE.F.BOND TOGETHER METAL SIDING NOT ATTACHED TO GROUNDED STRUCTURE; BOND TOGROUND.G.EQUIPMENT GROUNDING CONDUCTOR: PROVIDE SEPARATE, INSULATED CONDUCTORWITHIN EACH FEEDER AND BRANCH CIRCUIT RACEWAY. TERMINATE EACH END ON SUITABLELUG, BUS, OR BUSHING.HANGERS AND SUPPORTSPART 1 GENERAL1.01SECTION INCLUDESA.CONDUIT AND EQUIPMENT SUPPORTS.B.ANCHORS AND FASTENERS.1.02QUALITY ASSURANCEA.CONFORM TO REQUIREMENTS OF NFPA 70.B.PRODUCTS: LISTED AND CLASSIFIED BY UNDERWRITERS LABORATORIES INC. AS SUITABLEFOR THE PURPOSE SPECIFIED AND INDICATED.PART 2 EXECUTION2.01INSTALLATIONA.INSTALL HANGERS AND SUPPORTS AS REQUIRED TO ADEQUATELY AND SECURELY SUPPORTELECTRICAL SYSTEM COMPONENTS, IN A NEAT AND WORKMANLIKE MANNER, AS SPECIFIEDIN NECA 1.1.DO NOT FASTEN SUPPORTS TO PIPES, DUCTS, MECHANICAL EQUIPMENT, OR CONDUIT.2.OBTAIN PERMISSION FROM ARCHITECT BEFORE DRILLING OR CUTTING STRUCTURALMEMBERS.B.RIGIDLY WELD SUPPORT MEMBERS OR USE HEXAGON-HEAD BOLTS TO PRESENT NEATAPPEARANCE WITH ADEQUATE STRENGTH AND RIGIDITY. USE SPRING LOCK WASHERSUNDER ALL NUTS.C.INSTALL SURFACE-MOUNTED CABINETS AND PANELBOARDS WITH MINIMUM OF FOURANCHORS.D.IN WET AND DAMP LOCATIONS USE STEEL CHANNEL SUPPORTS TO STAND CABINETS ANDPANELBOARDS 1 INCH (25 MM) OFF WALL.E.USE SHEET METAL CHANNEL TO BRIDGE STUDS ABOVE AND BELOW CABINETS ANDPANELBOARDS RECESSED IN HOLLOW PARTITIONS.ELECTRICAL IDENTIFICATIONPART 1 GENERAL1.01SECTION INCLUDESA.NAMEPLATES AND LABELS.B.WIRE AND CABLE MARKERS.C.CONDUIT MARKERS.D.FIELD-PAINTED IDENTIFICATION OF CONDUIT.1.02SUBMITTALSA.MANUFACTURER'S INSTRUCTIONS: INDICATE APPLICATION CONDITIONS AND LIMITATIONSOF USE STIPULATED BY PRODUCT TESTING AGENCY SPECIFIED UNDER QUALITY ASSURANCE.INCLUDE INSTRUCTIONS FOR STORAGE, HANDLING, PROTECTION, EXAMINATION,PREPARATION AND INSTALLATION OF PRODUCT.1.03QUALITY ASSURANCEA.CONFORM TO REQUIREMENTS OF NFPA 70.B.PRODUCTS: LISTED AND CLASSIFIED BY UNDERWRITERS LABORATORIES INC. AS SUITABLEFOR PURPOSE SPECIFIED AND SHOWN.PART 2 PRODUCTS2.01NAMEPLATES AND LABELSA.NAMEPLATES: ENGRAVED THREE-LAYER LAMINATED PLASTIC, BLACK LETTERS ON WHITEBACKGROUND.B.LOCATIONS:1.EACH ELECTRICAL DISTRIBUTION AND CONTROL EQUIPMENT ENCLOSURE.2.02CONDUIT MARKERSA.LOCATION: FURNISH MARKERS FOR EACH CONDUIT LONGER THAN 6 FEET (2 M).B.SPACING: 20 FEET (6 M) ON CENTER.2.03 UNDERGROUND WARNING TAPEA.DESCRIPTION: 4 INCH (100 MM) WIDE PLASTIC TAPE, DETECTABLE TYPE COLORED REDWITH SUITABLE WARNING LEGEND DESCRIBING BURIED ELECTRICAL LINES.PART 3 EXECUTION3.01INSTALLATIONA.INSTALL NAMEPLATES AND LABELS PARALLEL TO EQUIPMENT LINES.B.SECURE NAMEPLATES TO EQUIPMENT FRONT USING SCREWS.C.SECURE NAMEPLATES TO INSIDE SURFACE OF DOOR ON PANELBOARD THAT IS RECESSED INFINISHED LOCATIONS.D.IDENTIFY UNDERGROUND CONDUITS USING UNDERGROUND WARNING TAPE. INSTALL ONE TAPEPER TRENCH AT 3 INCHES (75 MM) BELOW FINISHED GRADE.GENERAL SPECIFICATIONSA.THE WORK COVERED BY THESE SPECIFICATIONS CONSISTS OF FURNISHING ALL LABOR,EQUIPMENT, MATERIAL,S AND SUPPLIES AS NECESSARY FOR THE COMPLETE AND SATISFACTORYOPERATING ELECTRICAL SYSTEMS AS SHOWN ON THE PLANS.B.ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE, NFPA, STATEBUILDING CODE, AND ANY OTHER LOCAL REQUIREMENTS THAT MAY APPLY. CONTRACTOR SHALLPAY FOR ALL REQUIRED PERMITS, FEES, INSPECTIONS, ETC.C.CONTRACTOR SHALL OBTAIN AND PAY FOR ALL ELECTRICAL PERMITS AND INSPECTION FEES.D.ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND SHALL BE LISTED BY THE UNDERWRITER'SLABORATORIES, INC. OR BY A STATE APPROVED THIRD PARTY TESTING AGENCY FOR THE USEINTENDED WHERE A STANDARD FOR SUCH MATERIALS AND USE EXISTS. ALL ITEMS OF THE SAMETYPE AND RATING SHALL BE IDENTICAL AND OF THE SAME MANUFACTURER.E.CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND CATALOG DATA IN ELECTRONIC FORMAT (PDF)FOR ALL ELECTRICAL ITEMS IN THE SCOPE OF WORK, INCLUDING, BUT NOT LIMITED TO, RACEWAYS,BOXES, FITTINGS, CONDUCTORS, LUMINAIRES, LAMPS, BALLASTS, WIRING DEVICES, SAFETYSWITCHES, DISCONNECTS, TRANSFORMERS, PANELBOARDS, FIRE ALARM, TELECOMMUNICATIONS,ETC. FOR APPROVAL AS APPLICABLE FOR THE PROJECT. ONE COMPLETE SET OF APPROVEDSUBMITTALS SHALL BE MAINTAINED AT THE JOB SITE.F.ALL COST ASSOCIATED WITH SUBSTITUTED EQUIPMENT TO COMPLY WITH THE BASIS OF DESIGN,INCLUDING PROVIDING MAINTENANCE ACCESS, CLEARANCE, CONDUIT, WIRING, REPLACEMENT OFOTHER SYSTEM COMPONENTS, BUILDING ALTERATIONS, METHODS, ETC., SHALL BE INCLUDED INTHE ORIGINAL BASE BID. NO ADDITIONAL COSTS ASSOCIATED WITH SUBSTITUTED EQUIPMENTWILL BE APPROVED AFTER BIDS HAVE BEEN ACCEPTED AND ALL COSTS WILL BE THERESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. CREDITS SHALL BE GIVEN TO THE OWNERWHERE SUCH EQUIPMENT AND METHODS RESULT IN LESS EXPENSE TO THE CONTRACTOR.G.ONE COMPLETE SET OF THE LATEST CONSTRUCTION PLANS OF ALL TRADES SHALL BE MAINTAINEDAT THE JOB SITE. IN ADDITION, ALL ADDENDUMS, BULLETINS, AND/OR SKETCHES SHALL BEINCORPORATED INTO THE ON-SITE CONSTRUCTION PLANS AS THE JOB PROGRESSES.H.COMPLETELY ADEQUATE HOUSING SHALL BE PROVIDED FOR ALL MATERIALS STORED ON JOB SITE.ONLY CONDUIT MAY BE STORED OUTSIDE, BUT NOT IN CONTACT WITH THE GROUND.I.THE CONDUIT AND NEUTRAL SYSTEM SHALL BE GROUNDED AT THE MAIN SERVICE EQUIPMENT.GROUNDING ELECTRODE SYSTEM SHALL BE INSTALLED PER NEC 250.J.PROVIDE AN INTERSYSTEM BONDING TERMINATION DEVICE AT THE MAIN ELECTRICAL SERVICE PERNEC 250.94.K.WIRING SHALL BE TESTED FOR CONTINUITY AND GROUNDS BEFORE BEING ENERGIZED. FAULTYWIRING SHALL BE REPLACED AT NO ADDITIONAL EXPENSE TO THE OWNER.L.PROVIDE ALL CUTTING AND PATCHING FOR INSTALLATION OF WORK AND REPAIR ANY DAMAGEDONE.M.THE ELECTRICAL CONTRACTOR SHALL CONNECT ALL EQUIPMENT REQUIRING ELECTRICALCONNECTIONS (UNLESS OTHERWISE NOTED), EXCEPT FOR CONTROL WIRING FOR EQUIPMENT NOTPROVIDED BY THE ELECTRICAL CONTRACTOR. CONTROL WIRING FOR SUCH EQUIPMENT SHALL BEPROVIDED BY THE RESPECTIVE DISCIPLINE.N.ALL ELECTRICAL JUNCTION BOXES, SWITCHGEAR, CABLING, VOICE/DATA OUTLETS, LOW VOLTAGECABINETS, EMERGENCY RECEPTACLES, ETC. SHALL BE LABELED ACCORDING TO PANEL AND CIRCUITNUMBER.O.UPON COMPLETION OF WORK, CONTRACTOR SHALL PRESENT ENGINEER WITH CERTIFICATE OFAPPROVAL FROM LOCAL INSPECTOR AND/OR AUTHORITY HAVING JURISDICTION BEFORE WORKWILL BE APPROVED FOR FINAL PAYMENT.P.CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIALS FOR A PERIOD OF ONE YEAREFFECTIVE THE DATE THE PROJECT IS ACCEPTED BY THE OWNER. ANY IMPERFECT MATERIALS ORWORKMANSHIP SHALL BE REPLACED WITHOUT ADDED COST TO THE PROJECT.Q.IT SHALL NOT BE THE INTENT OF ISSUED PLANS AND/OR SPECIFICATIONS TO SHOW EVERY MINORDETAIL OF CONSTRUCTION. THE ELECTRICAL CONTRACTOR IS EXPECTED TO FURNISH AND INSTALLALL NECESSARY ITEMS FOR A COMPLETE AND OPERATING SYSTEM.R.THE WORD "PROVIDE" MEANS THAT THIS CONTRACTOR SHALL FURNISH, FABRICATE, ERECT,CONNECT, AND COMPLETELY INSTALL SYSTEMS IN PROPER OPERATING CONDITION. ALL LABOR,PRODUCT OPTIONS, ACCESSORIES AND INCIDENTAL MATERIALS REQUIRED SHALL BE INCLUDED ASPART OF THIS WORK TO COMPLETE THE INSTALLATION.S.THE WORD "CONNECT" MEANS THAT THIS CONTRACTOR SHALL PROVIDE (SEE DEFINITION ABOVE)ALL DISCONNECTING MEANS, OVERCURRENT PROTECTION AND WIRING REQUIRED TO PLACE THEEQUIPMENT AND SYSTEMS IN PROPER OPERATING CONDITION AND TO COMPLY WITH CODEREQUIREMENTS.T.CONTRACTOR SHALL COORDINATE THE ROUGH-IN OF ALL OUTLET LOCATIONS WITHARCHITECTURAL FLOOR PLANS, ELEVATIONS, AND MILLWORK SHOP DRAWINGS PRIOR TOROUGH-IN.U.ELECTRICAL CONTRACTOR SHALL NOT SCALE PLANS. CONTRACTOR SHALL REFER TOARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT, UNLESSOTHERWISE NOTED.V.IF DURING THE COURSE OF WORK, THE CONTRACTOR DISCOVERS A PROBLEM WITH THEPERFORMANCE OF THE INSTALLATION RELATIVE TO THE PLANS AND SPECIFICATIONS, THE NEC, OROTHER CODES OR REQUIREMENTS, THE CONTRACTOR SHALL IMMEDIATELY BRING THE PROBLEM TOTHE ATTENTION OF THE ARCHITECT AND/OR ENGINEER FOR RESOLUTION PRIOR TO THE EXECUTIONOF THE WORK.W.WHERE THERE ARE CONFLICTS BETWEEN THE PLANS AND SPECIFICATIONS, THE CONTRACTORSHALL BRING THE ISSUE TO THE ATTENTION OF THE ENGINEER FOR RESOLUTION PRIOR TO THEEXECUTION OF THE WORK OR ORDERING ANY MATERIALS. NO ADDITIONAL COSTS SHALL BEWARRANTED WITHOUT A CHANGE TO THE PROJECT SCOPE.X.THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND PROVIDINGTEMPORARY POWER AND LIGHTING FOR ALL TRADES. AT NO TIME SHALL EXISTING BUILDINGPOWER SYSTEMS BE UTILIZED WITHOUT WRITTEN PERMISSION FROM THE OWNER.Y.COORDINATE LOCATION AND REQUIREMENTS FOR ELECTRICAL SERVICE WITH THE POWERCOMPANY. WHERE MORE THAN ONE SERVICE IS SUPPLIED TO A BUILDING, PROVIDEIDENTIFICATION AT EACH SERVICE PER NEC 230-2(E).Z.COORDINATE LOCATION AND REQUIREMENTS FOR TELEPHONE SERVICE WITH THE TELEPHONECOMPANY.CONDUCTORSPART 1 GENERALA.CONDUCTORS SHALL BE MANUFACTURED BY SOUTHWIRE (SIMPULL), ENCORE (SUPERSLICK),UNITED COPPER (SLK), CERRO (SLP), OR APPROVED EQUAL, "PRE-LUBRICATED" BY THEMANUFACTURER.B.ALL CONDUCTORS SHALL BE COPPER, RATED 75° C WET/DRY EXCEPT WHERE OTHERWISE NOTEDOR REQUIRED BY U.L. OR OTHER CODES.C.ALL CONDUCTORS SHALL BE SINGLE INSULATED CONDUCTOR, THHN/THWN-2. SIZES #10 AWGAND SMALLER SHALL BE SOLID, SIZES #8 AWG AND LARGER SHALL BE STRANDED.D.BRANCH CIRCUITS SHALL NOT BE SMALLER THAN #12 AWG. CONTROL WIRING MAY BE #14 AWG.E.CONDUCTORS SHALL BE COLOR CODED BLACK/RED/BLUE FOR 120/208 VOLT SYSTEMS ANDBROWN/ORANGE/YELLOW FOR 277/480 VOLT SYSTEMS FOR A, B, AND C PHASES, RESPECTIVELY.NEUTRAL SHALL BE WHITE FOR 120/208 VOLT SYSTEMS AND NATURAL GRAY FOR 277/480 VOLTSYSTEMS. GROUND CONDUCTOR SHALL BE GREEN ON ALL SYSTEMS. ALL CONDUCTOR SIZESSHALL HAVE COLOR-CODED INSULATION. THE USE OF COLORED TAPE ON LARGER WIRE SIZESSHALL NOT BE ALLOWED.F.INSULATION SHALL BE DUAL RATED TYPE THHN/THWN-2 FOR FEEDERS AND BRANCH CIRCUITS.FIXTURE TAPS SHALL BE #12 THHN/THWN-2 IN FLEX WITH GREEN #12 AWG GROUNDINGCONDUCTOR.G.ALL CONDUCTORS SHALL BE IN CONDUIT.H.WIRING TO LIGHTING FIXTURES SHALL BE AS REQUIRED BY UL LABEL.I.MULTI-WIRE BRANCH CIRCUITS SHALL NOT BE ALLOWED, UNLESS EXPLICITLY INDICATED ON THEDRAWINGS. WHERE EXPLICITLY INDICATED ON THE DRAWINGS:1)ALL 20A MULTI-WIRE RECEPTACLE CIRCUITS SHALL UTILIZE A #10 AWG NEUTRALCONDUCTOR.OR2)ONLY WHERE PERMITTED UNDER "RACEWAYS", MC CABLE ASSEMBLIES CAN BE AFC "SUPERNEUTRAL" OR EQUAL, UNLESS OTHERWISE INDICATED ON THE DRAWINGS. WHEREMULTI-WIRE BRANCH CIRCUITS ARE EXPLICITLY INDICATED ON THE DRAWINGS, THEY SHALLBE INSTALLED PER NEC 210.4. MEANS SHALL BE PROVIDED TO SIMULTANEOUSLYDISCONNECT ALL UNGROUNDED CONDUCTORS AT THE POINT WHERE THE BRANCH CIRCUITORIGINATES IN ADDITION TO OTHER REQUIREMENTS PER NEC 210.4.J.JOINTS IN #10 AWG AND SMALLER SHALL BE MADE UP WITH CRIMPED CONNECTORS WITHINSULATING CAPS (NO TAPE) OR WIRENUTS (MAXIMUM OF 3 CONDUCTORS UNDER ANYCONNECTOR OR WIRENUT). LARGER WIRE SHALL USE SPLIT BOLTS OR BOLTED CLAMPS.K.ALL WIRING LUGS THROUGHOUT THE PROJECT, INCLUDING, BUT NOT LIMITED TO, BREAKERS,PANELBOARD/SWITCHBOARD LUGS, SAFETY SWITCH LUGS, MOTOR STARTER LUGS, TRANSFORMERSLUGS, WIRING DEVICE TERMINALS, AND ALL EQUIPMENT LUGS/TERMINALS SHALL BE RATED FORUSE WITH 75 DEGREE INSULATED CONDUCTORS AT THEIR 75 DEGREE AMPACITY AND SHALL BESIZED AND SELECTED TO MATCH THE CONDUCTOR SIZE AND MATERIAL.L.CIRCUIT JOINTS SHALL NOT BE MADE ON DEVICE TERMINALS.M.WIRE WITHIN PANELBOARDS SHALL BE NEATLY TRAINED, SQUARED, BUNCHED, AND TAGGED.N.ALL SYSTEM FURNITURE CONNECTIONS SHALL COMPLY WITH NEC 605.O.GROUND ALL EQUIPMENT PER NEC ARTICLE 250. BOND WHERE CONDUITS ENTER ENCLOSURESTHROUGH CONCENTRIC KNOCKOUTS. ALL FLEX, INCLUDING FIXTURE TAPS, SHALL INCLUDE GREENGROUNDING CONDUCTOR, #12 AWG MINIMUM. PROVIDE GREEN INSULATED EQUIPMENTGROUNDING CONDUCTOR IN EACH CONDUIT, SIZED PER NEC 250-122.P.ALL CONDUCTORS INSTALLED IN VERTICAL RACEWAYS SHALL BE SUPPORTED AT INTERVALS ASREQUIRED PER NEC 300-19.Q.THE ELECTRICAL CONTRACTOR SHALL FOLLOW AND APPLY THE TABLE BELOW, REGARDLESS WHATTHE PANEL SCHEDULE INDICATES, FOR SIZING ALL 120V & 277V, 20 AMP BRANCH CIRCUITS(COPPER CONDUCTORS) TO ALLOW A MAXIMUM OF 3% VOLTAGE DROP FROM THE CIRCUIT BREAKERTO THE FIRST DEVICE ON THE BRANCH CIRCUIT AND ACHIEVE A MAXIMUM OF 5% VOLTAGE DROPACROSS THE ENTIRE BRANCH CIRCUIT:VOLTAGECONDUCTOR LENGTH *BRANCH CIRCUIT1200' - 50'#1212051' - 90'#1012091' - 140'#8120141' - 225'#62770' - 125'#12277126' - 200'#10277201' - 330'#8277331' - 525'#6*- THE LENGTH IS MEASURED FROM THE CIRCUIT BREAKER TO THE FIRST DEVICE WHICH THEBRANCH CIRCUIT SERVES. WHERE THE DISTANCE EXCEEDS ABOVE, CONSULT WITH THEENGINEER.PAINTINGPART 1 GENERALA.SUITABLE FINISH COAT SHALL BE PROVIDED FOR ALL EQUIPMENT. PANEL TUBS, COVERS, ETC.SHALL BE PRIMED AND ENAMELED TO BLEND WITH ADJACENT SURFACES, OR SHALL BEMANUFACTURER'S STANDARD COLOR BAKED ENAMEL FINISH, OR AS DIRECTED BY THE ARCHITECT.NEW GAS DETECTIONALARM CONTROLPANEL5518 DAVID COX ROAD GAS DETECTOR LOCATIONS FOR: JDNA HUNTERSVILLE, NORTH CAROLINASHEET :SHEET TITLE :OFCopyright 2017 Engitecture PLLC17045Project Number:06/02/17ENGITECTURE,PLLCNC License No. P-16253940 Amyington DriveCharlotte, NC 28226704-287-2193E1SPECIFICATIONS,DETAILS &DIAGRAMS -ELECTRICAL <EXIT> <EXIT> <EXIT> <EXIT> <EXIT> <EXIT> <EXIT> <EXIT> <EXIT> <EXIT> <EXIT> <EXIT> <EXIT> <EXIT> <EXIT> <EXIT> <EXIT> GGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGG11223344558455455455444444673333671122311223112231122366666777778888888AAG8G8G8G8G8G8LOCATE INCABINETGAAKEYPADGENERAL NOTES:(APPLY THIS DETAIL ONLY)1.THIS DETAIL SHOWS HOW GAS DETECTION DEVICES ARE CONNECTED TOTHE ALARM CONTROL PANEL. CONTRACTOR SHALL CONNECT ALL GASDETECTION DEVICES IN SERIES FOR EACH N.O. INITIATING CIRCUIT TO BECONNECTED TO THE ALARM CONTROL PANEL.KEYED NOTES:(APPLY THIS DETAIL ONLY)CONTRACTOR SHALL PROVIDE AND INSTALL ALARM CONTROL PANEL.LOCATE IN VICINITY OF FIRE ALARM CONTROL PANEL. FIELD VERIFYLOCATION. CONNECT ALARM CONTROL PANEL TO 120 VOLT CIRCUIT THATSERVES EXISTING FIRE ALARM SYSTEM. INSTALL SO THAT CELLULARCOMMUNICATOR FOR ALARM PANEL CALLS OUT TO THIRD-PARTY CENTRALMONITORING STATION WHICH SHALL BE A NATIONWIDE UL/FMA COMPANY.CELLULAR COMMUNICATOR SELECTED SHALL BE A TOTAL CONNECTSYSTEM ALLOWING IT TO CALL MULTIPLE CELLULAR DEVICES. THE TOTALCONNECT THIRD-PARTY CENTRAL MONITORING SYSTEM SHALL CALL THESITE AND THEN DISPATCH FIRE/EMERGENCY SERVICES. THE THIRD PARTYCENTRAL MONITORING COMPANY SHALL CONTACT THE "CALL LIST" TOENSURE AWARENESS AND ALSO NOTIFY THE "CALL LIST" WHICH ZONE THEALARM OCCURS. THE ALARM ZONE CAN ALSO BE READ FROM THE GASDETECTION CONTROL PANEL KEYPAD.1#1 GAS DETECTIONALARM CONTROLPANELGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGZONE 1ZONE 2ZONE 3ZONE 4ZONE 5ZONE 6ZONE 7ZONE 8(2) WIRES FOR POWER AND (2)WIRES FOR ALARM SIGNAL FOREACH ZONE CIRCUITGAS DETECTION UNIT(TYPICAL OF ALL)GENERAL NOTES:(APPLY THIS DETAIL ONLY)1.REFER TO DETAIL 2/THIS DRAWING FOR GAS DETECTION SYSTEM INSTALLATION DETAIL.2.EACH GAS DETECTION ZONE CIRCUIT WILL BE MONITORED BY THE GAS DETECTION ALARMCONTROL PANEL AND THIRD-PARTY CENTRAL MONITORING COMPANY. IN THE EVENT OF A ALARMSIGNAL FROM A DEVICE, AN INDICATOR LIGHT FOR THE ZONE IN ALARM WOULD ILLUMINATE ONTHE KEYPAD ON THE CONTROL PANEL TO NARROW DOWN WHICH DEVICE IS IN ALARM. THEINDICATOR LIGHT FOR THE DEVICE IN ALARM WOULD BE ILLUMINATED ON THE DEVICE ITSELF.GGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGG5518 DAVID COX ROAD GAS DETECTOR LOCATIONS FOR: JDNA HUNTERSVILLE, NORTH CAROLINASHEET :SHEET TITLE :OFCopyright 2017 Engitecture PLLC17045Project Number:06/02/17ENGITECTURE,PLLCNC License No. P-16253940 Amyington DriveCharlotte, NC 28226704-287-21931FLOOR PLAN - GAS DETECTIONGSYMBOL LEGENDMACURCO 'GD-2A' COMBUSTIBLE GAS DETECTOR (LAYOUT BASED ONMANUFACTURER RECOMMENDED 900SF COVERAGE AREA)CONTRACTOR SHALL PROVIDE AND INSTALL. SURFACE MOUNT ORINSTALL DEVICE OVER A FOUR-INCH SQUARE OR DOUBLE GANGJUNCTION BOX. DEVICES SHALL BE MOUNTED AT APPROXIMATELY 32'AFF.THE NUMBER NEXT TO EACH DEVICE DENOTES THE INITIATING DEVICEZONE CIRCUIT ON THE ALARM CONTROL PANEL THAT THE DEVICESHALL BE CONNECTED TO. CONTRACTOR SHALL CONNECT DEVICESTOGETHER ON EACH INITIATING ZONE CIRCUIT PER THE WIRINGDIAGRAM SHOWN ON DRAWING 1/E3 AND ROUTE EACH CIRCUIT TO THEALARM CONTROL PANEL.3/32" = 1'-0"E2FLOOR PLAN -GAS DETECTIONAAUDIBLE/VISUAL ALARM. COORDINATE EXACT LOCATION WITHMANUFACTURER OF GAS DETECTION SYSTEM. Appendix A Methane Sensor Specification Sheet Macurco™ Combustible Gas Detector GD-2A For use with alarm control panels Methane and Propane Gas Detection The GD-2A is a low voltage electronic detector of combustible, heating type gases. The GD-2A is designed forconnection to UL Listed Fire Alarm/Burglary Control Panels. Alarm control panels that work on 12 or 24 VDC canprovide battery backup to the GD-2A detectors. This product is for use in ordinary indoor locations of family livingunits and office workspaces. The GD-2A is intended for installation in buildings in non-hazardous locations suchas residences, retail stores, office buildings, and institutional buildings. This combustible gas detector has beenevaluated by UL for methane (natural gas) and propane (LP) gas. It is NOT designed to detect smoke, fire orcarbon monoxide. Easy OperationA green LED signifies that the GD-2A is armed. If gas is detected, the Red LEDturns on and the alarm condition relay is activated. Features• Supervised Sensor• Simple installation and operation• SPDT Alarm and N.C. Trouble Relay• Can be self-restoring or latching• Califoirnia State Fire Marshal Listed• Solid State Electronic sensors: no maintenance or recalibration• Sensitivity tested based on UL 1484 Standard for Residential Gas Detectors• Listed to UL Standard 2075 for the Standard for Safety for Gas and Vapor Detector and Sensors Manufactured by Aerionics, Inc. Round Rock, TX – Phone: 1-877-367-7891 – Email: info@aerionicsinc.com – www.macurco.com GD-2A Specifications • Size: 4 ½ x 5 x 1 5/8 inches • Shipping Weight: 0.54 pound • Voltage: 12 to 24 VAC or VDC • Current (non-alarm): 45 mA @ 12 VDC, 22 mA @ 24 VDC, 65 mA @ 12 VAC, 45 mA @ 24 VAC • Current (in alarm): 70 mA @ 12 VDC, 35 mA @ 24 VDC, 100 mA @ 12 VAC, 65 mA @ 24 VAC • Color: white • Sensor Maintenance: not required • Alarm Relay Rating: 0.125 A, 40 V, 3 VA • Trouble Relay: 0.250 A, 40 V, 10 VA • Operating Temperature Range: 32° to 120° F • Alarm Set Point: Per UL 1484, 25% LEL Installation The three part plastic case allows the GD-2A to be either surface mounted or installed over a four-inch square or double gang electrical box, providing a near flush mount. LocationA GD-2A is usually located in each room (except kitchens or bathrooms) where there are gas appliances or through which gas pipes pass. Do NOT mount the GD-2A in a corner. Do NOT mount the GD-2A in kitchens orbathrooms - alcohol’s, ammonia, cleaning solvents, paint thinner, gasoline vapors, and aerosol propellants(aerosol cans such as hair spray usually contain a combustible gas) may cause alarms. Do NOT mount theGD-2A where the normal ambient temperature is below 32° F (0° C) or exceeds 120° F (50° C). If the gas usedis natural gas (methane) mount the GD-2A on a wall about one foot down from the ceiling. If the gas used is propane (LP), mount the GD-2A on a wall or column one foot above the floor. Use the same spacing as for smokedetectors- 30-foot centers, 900 square feet per detector. TYPICAL COVERAGE 900 SQUARE FEET Gas Detection Experts Made in the U.S.A. with US and imported materials © Aerionics 2012. All rights reserved. Macurco is a trademark of Aerionics, Inc. TYPICAL CONNECTION OF TWO GD-2A TO AN ALARM CONTROL PANEL Appendix B Methane Warning System Installation Certification June 8, 2017 5518 David Cox – Methane Warning System 3940 Amyington Drive | Charlotte, NC | 28226 704.287.2193 1 To: BIN – ILN LLC c/o Beacon Partners 610 East Morehead Street, Ste 250 Charlotte, NC 28202 Attn: John Core Project #: 17045 From: Greg Wiley, PE Re: Methane Warning System In accordance with the contract documents, based on on-site observations on Friday, June 2nd, 2017 and the data comprising the attached invoice, the undersigned engineer (the “Engineer”) certifies to BIN – ILN LLC (“Owner”) and Hartz Mountain Industries, Inc., and its designee, 5518 and 5600 David Cox Road LLC (collectively, “Buyer”) that to the best of the Engineer’s knowledge, information and belief the work (“Work”) described in the Methane Warning System Design Plan dated May 16, 2017, from Hart & Hickman for the installation of a methane detection system (the “Design Plan”) has been completed, the quality of the Work is in accordance with the Design Plan, the approved construction plans and all applicable Codes were followed. Appendix C Installation Photographs Photograph 1: View of GD-2A sensor in office area Photograph 2: View of GD-2A sensor in Warehouse FAI-012LOFTIS-BLYTH CONSTRUCTION SITE CHARLOTTE, NORTH CAROLINA 2923 S. Tryon Street, Suite 100 Charlotte, NC 28203 704.586.0007(p) 704.586.0373(f) Photograph 3: View of interior siren and alarm strobe Photograph 4: View of exterior siren and alarm strobe FAI-012LOFTIS-BLYTH CONSTRUCTION SITE CHARLOTTE, NORTH CAROLINA 2923 S. Tryon Street, Suite 100 Charlotte, NC 28203 704.586.0007(p) 704.586.0373(f) Photograph 5: View of Methane Warning System battery backup Photograph 6: View of Methane Warning System control panel FAI-012LOFTIS-BLYTH CONSTRUCTION SITE CHARLOTTE, NORTH CAROLINA 2923 S. Tryon Street, Suite 100 Charlotte, NC 28203 704.586.0007(p) 704.586.0373(f)