Loading...
HomeMy WebLinkAboutSW6210503_Design Calculations (Outlets)_20210518• U 1.11011 a9v I• DATE DESIGN PHASE M02-08-21 PRELIM PROJECT NAME PROJECT NO CONSTR / X / Townsend Estates 1651 REVISION RECORD LOCATION BY Near Raeford, North Carolina UP OTHER (SPECIFY) CHECKED BY CSB Storm Outlet Structure FES No.= PO 2 Pipe Dia= 36 in Q10 = 84.77 cfs Qfull = 108.06 cfs Vfull = 15.27 fps From Fig. 8.06.b.1: From Fig. 8.06.b.2: t 3 Length Storm Outlet Structure FES No.= FES 18 Pipe Dia= 36 in Q10 = 56.63 cfs Qfull = 179.20 cfs Vfull = 25.32 fps From Fig. 8.06.b.1: From Fig. 8.06.b.2: Zone D50 DMAX Riprap Class Apron Thickness Apron Length Apron Width @ Outlet Apron Width @ End Zone D50 DMAX Riprap Class Apron Thickness Apron Length Apron Width @ Outlet Apron Width @ End Q10/Qfu11 = 0.78 V/Vfu I = 1.10 V = 16.9 fps = 2 = 8 in = 12 in = B = 18 in = 18.0 ft = 9 ft = 21.0 ft Q10/QfuI1 = 0.32 V/Vfu11 = 0.87 V = 22.1 fps = 2 = 8 in = 12 in = B = 18 in = 18.0 ft = 9 ft = 21.0 ft 1651 Storm.xlsx LATEST REVISION: 5/18/2021 1:38 PM PAGE 1 OF 1