HomeMy WebLinkAboutSW3201003_SUPPLEMENT - EZ COVER PAGE_20201103SUPPLEMENT-EZ COVER PAGE
FORMS LOADED
PROJECT INFORMATION
1
Project Name
Auto Finance & Car Care Center
2
Project Area (ac)
5.717
3
Coastal Wetland Area (ac)
0
4
_
Surface Water Area ac)
0
5
Is this project High or Low Density?
Hi h
6
Does this project use an off -site SCM?
No
COMPLIANCE WITH 02H .1003(4)�
7
Width of vegetated setbacks provided (feet
N/A
8
Will the vegetated setback remain vegetated?
_
N/A
9
If BUA is proposed in the setback, does it meet NCAC 02H.1003(4)(c-d)?
N/A
10�
Is streambank stabilization proposed on this project?
_
No
NUMBER AND TYPE OF SCMS:
11
Infiltration System
0
12
Bioretention Cell
0
13
Wet Pond
j 0
14
Stormwater Wetland
0
15
Permeable Pavement
p
16
Sand Filter
1
17
Rainwater Harvesting (RWH);
0
18
Green Roof
0
19
Level Spreader -Filter Strip (IS-FS)
0
20
Disconnected Impervious Surface (DIS)
0
21
Treatment Swale
0
22
Dry Pond
0
23
StormFilter
0
24
Silva Cell
_ 0
25
Bayfllter
0
26
Filterra
0
FORMS LOADED
DESIGNER CERTIFICATION
andTitle
Vincent G. Keene P.E.
T27Name
ganization:
Yarbrough -Williams & Houle, Inc.
eet address: -_-
P.O. Box 1198
30
City, State, Zip_ _
----
Pineville, NC 28134
31
!Phone number(s).
704-556-1990
32
1 Email
m i vincek@y-wh.com
Certification Statement:
I certify, under penalty of law that this Supplement-EZ form and all supporting information were prepared under my direction or supervision; that the
information provided in the form is, to the best of my knowledge and belief, true, accurate, and complete: and that the engineering plans,
specifications, operation and maintenance agreements and other supporting information are consistent with the information provided here.
A®5++I IsII11118s1
� O®
II
1763
saes®P,,'Iy- Slzdh+a+ °+,+',�� �j `s !4 2,0
it/� rda
Signature f D ign
- 0V�1�i`�2®
Date
SAND FILTER
1 Drainage area number 1
2 Minimum re uired treatment volume cu ft9432 sf
GENERAL MU ; FROM 02H .105
" s the SCM sized to treat the SW from all surfaces at build -out? Yes
4
is the SCM located away from contaminated soils? Yes
5
What are the side slopes of the SCM (H:V)? !— 3:1
6
Does the SCM have retaining walls, gabion walls or other engineered NI O —
side slopes?
7
Are the inlets, outlets, and receiving stream protected from erosion Yes '
(1 0-year storm)?
Is there an overflow or bypass for inflow volume in excess of the
design volume? Yes
h
What is the method for dewatering the SCM for maintenance? Pum ( referred)
11f applicable, will the SCM be cleaned out after construction? Yes
Does the maintenance access comply with General MDC (8)? Yes
Does the drainage easement comply with General MDC (9)? Yes
the SCM is on a single family lot, does (will?) the plat comply with
eneral MDC (10)? Yes
417
' Yes
s there an O&M Agreement that complies with General MDC (1�----4
there an O&M Plan that complies with General MDC (12)v Yes
_
oes the SCM follow the device specific MDC? Yes v
as the SCM designed b an NC licensed rofessionai? Yes
SAND' FILTER
MDC FROM 02H..1056
18
NOT
SHWT elevation (fmsl) ENCOUNTERED
(DUG TO 677.5
19'Type
20
of sand filter (open or closed) Open
If closed, will the filter will be pre -cast or pour -in -place?
21
If closed, top of grate elevation (fmsl) i
EE�
22
Is this sand filter designed to attenuate peak flows? Yas
[Sediment Chamber
23
Volume that can be retained in the sediment chamber (cubic feet)
44760 cf
24
Will there be a permanent pool in the sediment chamber?
No
25
Bottom of the sediment chamber fmsl)
685.00
26
jArea of the sediment chamber (square feet)
1850 sf
27
Ph sical de th of the sediment chamber (inches)
24 in
28
Ponding depth in the sediment chamber, above any permanent pool
(inches) ;
24 in
29
Elevation of top of weir between chambers fmsl)
687
30
lVolume that can be retained in the sand chamber cubic feet) 37862 cf
31
Bottom of the sand chamber (fmsl) 684.50
32
_
Area of the sand chamber (square feet) 10150 sf
33
Physical depth of the sand chamber (inches) 66 in
34
_
Ponding depth in the sand chamber, above the sand surface 50 in
(inches)
35
Elevation of the bypass device (fmsl) 687.3
36
Type of bypass device 4' WEIR
37
38!Sand
39!Depth
_
Mechanism for distributing flow over the sand surface — 3" layer of sod or
_ ( washed stone
ASTM C-33
MEDIUM
specification for sand chamber AGGREGATE
CONCRETE
SAND
above underd rain pipe (inches) 30 in
40
Will the media be maintained to drain at least two inches per hour at
the sand surface? Yes
411
_
Is at least one clean -out pipe provided at the low point of each
underdrain line? Yes
42
Will clean -out pipes be canoed? Ve
ATIONAL INFORMATION
43 i' Please use this space to provide any additional information about
_sand filters)
Sand Filter 1 8:51 AM 10/15/2020
DRAINAGE AREAS
1
Is this a high densit ro ect?
Yes 1
2
If so, number of drainage areas/SCMs
1
3
boes this project have low density areas?
No
4
'1 If so, number of low density draina a areas
0
5
Is all/part of this project subject to previous rule
versions?
No
FORMS LOADED
rDRAIN AGE AREA INFORMATION
4 Type of SCM
Entire Site
1
Sand Filter
5
Total drainage area (sq ft
_
211701
211701
6
Onsite drainage area (sq ft
196484
196484
7
Offsite drainage areas ft
15086
15086
8
Total BUA in project (sq ft
113994 sf
113994 sf
9
New BUA on subdivided lots (subject to permitting)
s ft
10permitting)
New BUA not on subdivided lots (subject to
s
113994 sf
113994 sf
11
Offsite BUA (sq ft)
12
Breakdown of new BUA not on subdivided lots:
Parkin _(sq ft)
67604 sf
67604 sf
Sidewalk (sq ft
3190 sf
3190 sf
Roof (sq ft
42500 sf
42500 sf
Roadway s ft
Future (sq ft
Other, please specify in the comment box
below (sg ft
700 sf
700 sf
j
13
New infiltrating permeable pavement on
subdivided lots s ft
14
New infiltrating permeable pavement not on
subdivided lots (sq ft
_
15
Existing BUA that will remain (not subject to
ermittin s ft
16
Existing BUA that is already permitted (sq ft
17
_
Existing BUA that will be removed (sq ft)
18
Percent BUA
54%
_
54°!a
19
Design storm inches
1.0 in
4. I in
20
Design volume of SCM cu ft
9432 cf
9432 cf
21
Calculation method for design volume
_
1" WQV
1" WQV
ADDITIONAL INFORMATION
22
Please use this space to provide any additional information about the
drainage area(s)_
Other includes areas for trash dumpster. Treated the 1" WQV, detained 1, 2,
and 10 year storms. Designed for 1' of freeboard in the 100 year storm.